PM335 PRO · PANEL FIT
Which PM335 PRO drawing should I use to check panel fit?

Quick answer
The manual gives the PM335 PRO cutout as ANSI 4-inch round or DIN 92 × 92 mm square, in a switchgear panel "with width range of 1.0mm (0.04”) to 6.4mm (1/4”)". Its front measures about 113 mm wide by 109 mm high.
The manual's two PM335 drawings and the datasheet give different depth figures, and none of these documents says which figure controls.
SATEC Australia's advice:
- Check your panel against all of the depth figures below.
- Where depth is tight, plan to the largest one.
- Contact technical support before you cut the panel.
Applies to
This page covers the panel-mounted PM335 PRO, which has a 3.5-inch colour display. Its order string starts PRO-PM335.
It doesn't cover:
- the EM235 PRO, a DIN-rail meter with its own drawing, Figure 2-2b;
- the display-less transducer version, which the manual shows on a 35 mm DIN rail in Figure 2-6.
The cutout and panel
Figure 2-3 gives the two cutouts:
- the standard 4-inch round cutout: a 4.0-inch hole, with four 0.198-inch holes, dimensioned 3.375 inches apart;
- the DIN43700 92 × 92 mm square cutout.
The manual says to "Affix the meter using the 4 screws supplied".
Front size
| Source | Width | Height |
|---|---|---|
| Figure 2-1a PM335 PRO Dimensions | 113.35 | 108.64 |
| Figure 2-4 PM335 PRO panel mounting dimensions | 113.40 | 108.70 |
| Datasheet | "Dimensions (PM335) 108.6 × 74.7 × 113.3 mm". It doesn't say which figure is which. |
Figures 2-1a, 2-4 and 2-5 print their dimensions without units.
Depth: the sources differ
| Source | Depth figures shown |
|---|---|
| Figure 2-4 PM335 PRO panel mounting dimensions | 44.80 behind the panel and 20.40 in front of it; rear body 91.5 high |
| Figure 2-1a PM335 PRO Dimensions | 51.00 and 51.95 on one view; 74.35 on another; 22.40 and 20.40 on the side view; rear body 90.00 × 90.00 |
| Datasheet | "Dimensions (PM335) 108.6 × 74.7 × 113.3 mm", and "50mm deep" beside the cutout description |
Figure 2-4 is the only one of these dimensioned from the panel. The others don't show what they measure from.
SATEC Australia's advice:
- Don't add the figures together or average them.
- Where depth is tight, plan to the largest figure (74.7 mm in the datasheet), plus room for the wiring behind the meter.
- Before cutting a tight panel, send us the order code and the panel drawing.
Leave room for add-on modules
Figure 2-5, "PM335 PRO with 4 modules dimensions", shows the main unit at 90.00 and four modules at 71.00, each module 17.80.
For a basic unit with no modules, the quick start says "it is recommended to maintain a minimal gap of 30-100mm to the right (when facing front panel) of the unit, allowing future installation of additional detachable SATEC modules (depending on number of added modules: 17.8mm each)".
SATEC Australia's advice: Figure 2-5 shows space only. Ask technical support before ordering a combination of modules.
Fitting the meter
The manual first says to "Separate the Display unit from the main unit". Its drawing says:
- "INSERT FLAT SCREWDRIVER BLADE AND LIFT SNAP TO SEPARATE BOTH SIDES";
- "SUPPORT HERE WHEN PERFORMING THE SEPARATION".
Its Panel Mounting steps are:
- "Position the Display unit in the Panel cutout."
- "Affix the meter using the 4 screws supplied."
- "Observe orientation !!"
- "Snap and connect the main unit to the mounted display unit."
- "Now the instrument is ready for wiring."
Safety requirements:
- The manual says to ensure "all incoming power sources are shut OFF before installing a module".
- The switchgear metal plate "must be connected to earth (ground) for safety purposes".
- "Only qualified personnel familiar with the instrument and its associated electrical equipment must perform setup procedures."
- The quick start says "Only a licensed electrician may perform installations and wiring of the PM335."
Reading the drawings
The copy of the manual on our site and the manufacturer's copy of the same revision have identical text. The manufacturer's copy has higher-resolution figures.
SATEC Australia's advice: if a dimension is hard to read, use the manufacturer's copy of BG0612 Rev. A8.
What to send technical support
Contact SATEC Australia technical support through our contact form.
SATEC Australia's advice is to include:
- the full order code from the label, and the add-on modules fitted or planned;
- the panel thickness and cutout type;
- the depth available behind the panel and the clearance to the right of the meter;
- the drawing and figure you're working from.
Manuals and source pages
- EM235/PM335 PRO Installation and Operation Manual, BG0612 Rev. A8, December 2024 (PDF on our site). Printed page numbers match the PDF pages:
- PRO PM335 Quick Start, BG0635 Rev. A2, page 1 (PDF on our site).
- eXpertPRO PM335/EM235 Power Quality Analyser datasheet, page 6, and the manufacturer's PRO Series datasheet, April 2026, pages 2 and 8.
- Evidence checked 22 November 2026.
Source review: 22 November 2026.