EM235 PRO · MODULES

Can these EM235 PRO expansion modules and auxiliary supply be combined?

EM235 PRO product illustration
EM235 PRO product illustration

Quick answer

The April 2026 datasheet's order string allows I/O modules "Max. 3 per device" and an auxiliary power supply "Max. 1 per device". The manual and datasheet agree that one add-on module doesn't need the auxiliary (AUX) supply.

They conflict about more than one module:

  • The manual's features list, the manual's AUX section and the datasheet say three modules need the AUX supply, fitted as a fourth module.
  • The table on page 44 lists one three-module combination, three 8DI-WET modules, with no AUX supply, limited to −40 to 50 °C.
  • The sources disagree about two modules.

SATEC Australia's advice: plan an AUX supply for any combination of more than one module, unless we have confirmed your exact combination.

Applies to

This page covers the standard EM235 PRO DIN-rail meter.

The module rules come from the manual and datasheet, which cover the EM235 and PM335 PRO together. The clearance figures and fitting steps come from the EM235 quick start. FCAS variants aren't covered.

The "Optional Built-in Digital and Analog I/O" is ordered separately from the add-on modules. The order string lists it under "BUILT-IN I/O" as "2 x DI (dry contact) + 1 x SSR output + 1 x Universal AI (-1mA to 20mA)".

The add-on modules

The order string's "OPTIONAL MODULES", as written:

DescriptionCode
4 Relay Outputs - 250V / 5A ACEMR4
4 SSR Outputs - 250V / 0.1A ACSSR4
4 Digital inputs (Dry Contact @ 24V DC) + 2 SSR outputs4DIOS-DRC
4 Digital inputs (Dry Contact @ 24V DC) + 2 EMR outputs4DIOR-DRC
8 Digital Inputs - Dry ContactDI8-DRC
8 Digital Inputs - 24, 48, 125, 250 V DCDI8-24, 48, 125, 250 V
4 Analog Outputs; configurable range4AO
AUX. P.S. AC/DC 88-264V AC / 90-290V DCAUX-ACDC
24V DC (9-36V DC)AUX-24DC

The footnote reads: "* Auxiliary power supply required when configured with 3 modules".

The datasheet's specification tables give some module ratings differently from the order string. For example, the solid-state relay module is rated at 100mA/800V AC there. SATEC Australia's advice: check the ratings with technical support before ordering.

The manual says the meter can be equipped with up to three of each of the 8DI, 4RO, 4DI/2RO and 4AO modules.

When the auxiliary supply is needed

I/O modulesWhat the sources say
1No AUX supply needed. All sources agree.
2Conflict. The manual's features list and the datasheet say "Up to 2 expansion modules: self-energized". The manual's I/O section says "When connecting more than 1 external module external aux power supply is needed", except for the combinations in its table. Every combination in that table with more than one module and no AUX supply is limited to −40 to 50 °C.
3Conflict. The manual's features list, its AUX section and the datasheet say the AUX supply is needed, as a fourth module. The page 44 table lists 3 × 8DI-WET with no AUX supply, at −40 to 50 °C.

The table in the I/O section lists modules named 8DI-DRY, 8DI-WET, 4DO and CELL. "4DO" and "CELL" don't appear in the datasheet's order string. The table doesn't list 4AO or 4DI/2RO, and one entry is blank. We don't reproduce the table here.

Fitting the auxiliary supply

  • The manual says the AUX supply module "should be the last one assembled in the chain of connected modules".
  • The AC/DC AUX module is rated 88–264 V AC. The manual gives its DC range as 125–300 V DC; the datasheet gives 90–290 V DC.
  • The 24 V DC AUX module is rated 9–36 V DC.
  • The manual is inconsistent about the meter's own supply. Page 12 says: "When using 3 modules on the PRO with the AUX PS there a need to wire the PS on the PRO meter itself as well". Page 47 says the 24 V DC AUX module "can provide the supplying power to the meter alone (no power connected to the main power supply), even in case of three optional module connected".

SATEC Australia's advice: check the AUX module's label for its rating, and keep the meter's own supply connected unless we have confirmed otherwise for your order.

Space and fitting

The EM235 quick start says:

  • "it is recommended to maintain a minimal gap of 30-100mm to the right of the unit, allowing future installation of additional detachable SATEC modules (figure 5; depending on number of added modules, 17.8mm each)";
  • "DO NOT HOT-SWAP. When adding/removing modules, make sure the unit is disconnected from power supply";
  • "Remove cover (sticker on right side of unit) to reveal port";
  • "Attach the module tightly and tighten the clips";
  • "Power on the unit".

The manual says: "Ensure that all incoming power sources are shut OFF before installing a module." The quick start says: "Only a licensed electrician may perform the installation and wiring of the EM235."

Before you order or add a module

SATEC Australia's advice:

  1. From the meter label and your purchase records, note the order code and list the modules already fitted.
  2. Count the I/O modules in the planned combination, and decide where the AUX supply will go.
  3. Note the site's operating temperature range. The manual ties some combinations to a temperature range.
  4. Send these details to technical support and confirm the combination before ordering.

Contact SATEC Australia technical support through our contact form.

Manuals and source pages

  • EM235/PM335 PRO Installation and Operation Manual, BG0612 Rev. A8, December 2024 (PDF on our site). Printed page numbers match the PDF pages:
    • Optional Expansion Add-on Modules and the auxiliary supply modules, pages 11–12.
    • Module mounting, page 21.
    • External Modules connection and the module table, page 44.
    • The 8DI, 4RO, 4DI/2RO, AUX and 4AO modules, pages 45–47.
  • PRO EM235 Quick Start, BG0634 Rev. A1, pages 1 and 4.
  • The manufacturer's PRO Series datasheet, April 2026, pages 4, 7 and 10. The Australian datasheet also says, on page 3, that up to two modules are self-energised and that three need the auxiliary supply module.
  • Evidence checked 22 November 2026.

Source review: 22 November 2026.