APPLICATION NOTE

DC measurement application note

DC Measurement

Transcribed from the SATEC document DC Measurement, July 2021, July 2021 (PDF, 4 pages, 1871 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.

DC Measurement

Systems which either produce or consume direct current are becoming commonplace. This includes commercial clients and industrial applications, raising the demand for accurate metering of DC systems. Using the PRO Series meters as platform, SATEC has developed DC metering capability via Hall Effect sensors (HES). This now allows accurate metering of DC systems, combining the familiar SATEC features of data logging, high-accuracy and our advanced options for communication protocols and control (I/O).

SATEC DC metering platform

DC Voltage Measurement

Voltage Ratio Module, front view showing terminals V1 to V3. Drawing not reproduced on this page. See page 1 of the PDF.

Each meter can monitor 3 independent DC circuits via 3 independent DC voltage Inputs.

Measuring up to 800V DC is carried out via direct connection to the SATEC meter: Measuring 1500V DC and 2500V DC systems is possible via a special SATEC Voltage Ratio Module (VRM).

Correct Connection: METER UNIT. These connections must be implemented as shown (connection diagram, inputs +V1/-V1, +V2/-V2, +V3/-V3 through the Voltage Ratio Module to the meter). Drawing not reproduced on this page. See page 1 of the PDF.

For DC High Voltage connection: recommended distance between SATEC VRM and SATEC meter should not exceed 2 meters, using cables featuring minimum 600V insulation.

Voltage Ratio Module Characteristics

When using SATEC VRM the correct ratio coefficient must be fed by PAS software (“basic configuration” tab)

PAS screenshot: PRO - General Setup, Basic Setup tab, Basic Configuration, with PT Ratio set to 3.5 highlighted. Drawing not reproduced on this page. See page 2 of the PDF.

DC Current Measurement (Hall Effect Sensors)

The PRO Series

The device has 4 independent current inputs rated at 20mA nominal current, to which the user may connect standard Hall Effect sensors featuring 0-20mA/+-20mA outputs.

It is mandatory to use cabling featuring double insulation (600V) when connecting HES to PRO Series meters.

Likewise, when using the PRO series (unlike the PM130 PLUS), it is mandatory to use a separate power supply for each sensor.

Requirements for power supply for Hall Effect Sensors:

DC power is calculated with indication for direction of power flow. Energy is calculated separately for each channel (except for I4).

Typical Current measurement accuracy: up to 0.2% (depending on HES type).

Wiring diagram: meter terminals L/+, N/-, V1, V2, V3, N and current inputs I1+ I1-, I2+ I2-, I3+ I3-, I4+ I4-, each connected to a Hall Effect sensor (+ - 0 I+ GND) with its own P.S. +/-15VDC supply. Drawing not reproduced on this page. See page 3 of the PDF.

It is mandatory to setup the PRO meter to DC mode using PAS Software.

PAS screenshot: Basic Setup tab, Basic Configuration, with Nominal Frequency, Hz set to DC highlighted. Drawing not reproduced on this page. See page 3 of the PDF.

Test results of Hall Effect Sensor with 100A DC Nominal current (SPLIT CORE)
Calibrator, ATest result CS100EK2-K, AError, %
10.991.010
21.981.010
32.980.671
43,990.250
54.980.401
880
109.990.10
15150
0200
25250
30300
4040.03-0.074
4545.04-0.088
5050.04-0.079
6060.07-0.116
7070.09-0.128
8080.12-0.149
9090.16-0.177
100100.18-0.179
120120.17-0.141
150150.14-0.093
180180.18-0.099
200200.22-0.109

Chart of the test results: CALIBRATOR against CS100EK2-K, 0 to 200 A. Drawing not reproduced on this page. See page 4 of the PDF.

Split-core Hall Effect sensor (photograph). Drawing not reproduced on this page. See page 4 of the PDF.