PRO PM335 · QUICK START GUIDE
PRO PM335 quick start guide
PRO PM335 Quick Start Manual
Transcribed from the SATEC document PRO PM335 Quick Start Manual, BG0635 REV.A2, date not printed (PDF, 4 pages, 379 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.
PRO PM335 Quick Start Manual
This guide instructs the user on installation, wiring, configuring and operating the PM335 multi-meter. This guide does not substitute the full user manual or the detailed safety instructions. To download the manual and other related material, please visit our website: www.satec-global.com
Figure 1: PM335 front panel. Drawing not reproduced on this page. See page 1 of the PDF.
- Diagnostic message LED
- Graphic display
- Wh/kvarh Pulse LED
- Navigation buttons
- Load bar graph
- IR COM port
- USB port
Installation
The PM335 is designed for 4-inch round / 92x92mm square panel mounting.
Please note to leave room for future expansion: when a basic units (no modules), it is recommended to maintain a minimal gap of 30-100mm to the right (when facing front panel) of the unit, allowing future installation of additional detachable SATEC modules (depending on number of added modules: 17.8mm each).
Electrical Connections
The following steps correspond with a low-voltage three phase network (figure 2):
- Make sure all power sources are disconnected.
- Make sure that your designated power supply corresponds with the unit's rating.
- Connect the power supply (bottom-left of back panel) via 12 AWG wires and a designated circuit breaker.
- Standard external current transformers: connect the CT's (14 AWG minimum) "+" pole to the device's I1+ current input (unit’s bottom right of rear end, as in figure 2) and the "-" pole to the adjacent I1- current input. Repeat this for the following two phases, I2 and I3. Verify proper polarity in your connections in accordance with the arrow printed on the external CTs. “HACS” CTs: connect the red/white wire to the "+" terminal and the black/orange (colors vary according to the CT model) wire to the "-" terminal.
- Connect the voltage measurement inputs (22-12 AWG; bottom-center of rear end).
- Connect the com wire (26-12 AWG, shielded) to COM1 (RS485, top-left of rear-end).
- Power-on the unit.
Figure 2: Electrical wiring. Drawing not reproduced on this page. See page 2 of the PDF.
Basic Configuration and Operation
The PRO PM335 is operated via the LCD display, 2 LEDs and 4 pushbuttons (figure 1: front panel).
When powered on, the device will default to displaying voltages, for basic setup back up (<- button) to the home screen navigate with arrows to “setup” (select with ✓), enter default password (“9”) and select (“apply”). Open “general setup” to reveal “basic setup” for configuration.
Figure 3: Screenshot sequence for basic setup. Drawing not reproduced on this page. See page 3 of the PDF.
Connecting Optional SATEC Modules
- DO NOT HOT-SWAP. When adding modules, make sure the unit is disconnected from power supply
- Remove cover (sticker on right side of unit) to reveal port
- Attach the module tightly and tighten the clips
- Power on the unit
General Information and System Defaults
- Default password: 9
- Default IP: 192.168.0.203 (ETH1)
- Default current mode (HACS model): Alternating Current (AC)
- Default serial com settings (RS485): 19,200 Baudrate; address = 1
- For convenient configuration please use SATEC’s PAS engineering software, connecting your PC to the USB port (type C) at the right side of the front panel To download PAS (free): www.satec-global.com/power-analysis-software make sure to update .exe file with the most recent update available on webpage