Split core current transformers for retrofit energy metering.
Transcribed from the SATEC Australia datasheet TBV1.0, 30 September 2026 (PDF, 6 pages, 1256 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
SCT-DP split core current transformers are designed for fast installation in new and existing low voltage networks. The core opens so the transformer can be fitted around an existing cable or busbar without disconnecting the primary conductor. This suits retrofit energy metering, sub-metering and power monitoring projects where a shutdown is costly or impractical.
Five window sizes cover primary currents from 100A to 5000A with a 5A or 1A secondary. Accuracy Class 0.5, 1.0 and 3.0 are available depending on ratio and burden, with rated outputs from 1.5VA to 30VA. Busbar centring devices hold the conductor in position and the range is designed to IEC 61869-2 and AS 61869.2.
Main features
Split core design fits around existing cables and busbars
No need to disconnect the primary conductor to install
Primary currents from 100A to 5000A
5A or 1A secondary output
Accuracy Class 0.5, 1.0 or 3.0 (subject to burden)
Rated output from 1.5VA to 30VA
Five window sizes from 20 × 30mm to 80 × 160mm
Busbar centring devices for secure positioning
Insulation level 0.72/3kV
Short time thermal current Ith = 100 × In
Instrument security factor FS < 5
Suitable for 50Hz and 60Hz networks
Designed to IEC 61869-2 and AS 61869.2
Feature capabilities
SCT-DP-23
Compact 20 × 30mm window for cables. Ratios 100/5A to 400/5A.
SCT-DP-58 and SCT-DP-88
50 × 80mm and 80 × 80mm windows. Ratios 250/5A to 1000/5A.
SCT-DP-812 and SCT-DP-816
80 × 120mm and 80 × 160mm windows for busbars. Ratios 500/5A to 5000/5A.
Split Core Retrofit Installation
Core opens and closes around the existing conductor
No need to disconnect cables or busbars to fit the CT
Avoids the primary circuit interruption that conventional CTs require
Saves installation time and cost on switchboard upgrades
Ideal for adding metering to sites already in service
Wide Window Range
SCT-DP-23: 20 × 30mm window
SCT-DP-58: 50 × 80mm window
SCT-DP-88: 80 × 80mm window
SCT-DP-812: 80 × 120mm window
SCT-DP-816: 80 × 160mm window for large busbars
Metering Accuracy
Accuracy Class 0.5, 1.0 and 3.0 depending on ratio and burden
Rated output from 1.5VA to 30VA
Higher ratios support higher burdens for longer secondary runs
Select ratio, class and VA from the ratings tables on page 5
Busbar Centring and Mounting
Centring devices hold the busbar in the middle of the window
Never open circuit the secondary while the primary is energised
Installation by a qualified electrician to site safety procedures
Typical Applications
Retrofit sub-metering in commercial buildings
Energy monitoring upgrades in industrial plants
Data centre and critical power monitoring
Water, wastewater and council infrastructure
Sites where a shutdown is not practical
Complete SATEC Metering System
Pairs with SATEC power meters and energy meters
Meter data can be viewed and managed in the Expertpower platform
New installations: CT-MES solid core CTs
High accuracy options: HACS current sensors
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
Electrical
Primary current
100A to 5000A
Secondary current
5A or 1A
Frequency
50Hz / 60Hz
Insulation level
0.72/3kV
Short time thermal current
Ith = 100 × In
Accuracy and output
Accuracy class
0.5, 1.0, 3.0 (subject to burden)
Rated output
1.5VA to 30VA
Instrument security factor
FS < 5
Design standard
IEC 61869-2, AS 61869.2
Construction
Core type
Split core
Window sizes
20 × 30mm to 80 × 160mm
Overall size
89 × 111mm to 184 × 245mm
Weight
0.75kg to 4.30kg
Busbar centring
Centring devices included
Installation
Installation
Around existing cable or busbar
Fixing
Base fixing holes
Primary disconnection
Not required
Model overview: SCT-DP-23
Window A × B (mm)
20 × 30
Ratio range (A)
100/5 to 400/5
Accuracy classes
0.5, 1.0, 3.0
Rated output (VA)
1.5 to 5
Overall D × E (mm)
89 × 111
Weight (kg)
0.75
Model overview: SCT-DP-58
Window A × B (mm)
50 × 80
Ratio range (A)
250/5 to 1000/5
Accuracy classes
0.5, 1.0
Rated output (VA)
2.5 to 5
Overall D × E (mm)
114 × 145
Weight (kg)
0.90
Model overview: SCT-DP-88
Window A × B (mm)
80 × 80
Ratio range (A)
250/5 to 1000/5
Accuracy classes
0.5, 1.0
Rated output (VA)
2.5 to 10
Overall D × E (mm)
144 × 145
Weight (kg)
1.05
Model overview: SCT-DP-812
Window A × B (mm)
80 × 120
Ratio range (A)
500/5 to 3000/5
Accuracy classes
0.5, 1.0
Rated output (VA)
2.5 to 20
Overall D × E (mm)
144 × 185
Weight (kg)
1.25
Model overview: SCT-DP-816
Window A × B (mm)
80 × 160
Ratio range (A)
1000/5 to 5000/5
Accuracy classes
0.5, 1.0
Rated output (VA)
10 to 30
Overall D × E (mm)
184 × 245
Weight (kg)
4.30
Ratio ranges shown for 5A secondary. For 1A secondary ratings please contact SATEC. Dimensions in mm.
Dimensions: SCT-DP-23
A
20
B
30
C
51
D
89
E
111
F
34
G
47
H
40
I
32
Weight (kg)
0.75
All SCT-DP models share the same construction. Window A × B sets the largest cable or busbar the transformer will accept. Dimensions are in millimetres.
Dimensions: SCT-DP-58
A
50
B
80
C
78
D
114
E
145
F
32
G
32
H
32
I
33
Weight (kg)
0.90
Dimensions: SCT-DP-88
A
80
B
80
C
108
D
144
E
145
F
32
G
32
H
32
I
33
Weight (kg)
1.05
Dimensions: SCT-DP-812
A
80
B
120
C
108
D
144
E
185
F
32
G
32
H
32
I
33
Weight (kg)
1.25
Dimensions: SCT-DP-816
A
80
B
160
C
120
D
184
E
245
F
52
G
47
H
52
I
38
Weight (kg)
4.30
A × B = window (aperture). D × E = overall width and height. Side and top view dimensions H, I, 32, 50 and 65 as per drawing.
Ratings: SCT-DP-23, rated output (VA) by accuracy class and ratio (A)
100/5
Class 0.5: n/a · Class 1.0: n/a · Class 3.0: 2.5
150/5
Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a
200/5
Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a
250/5
Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a
300/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
400/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
Ratings: SCT-DP-58, rated output (VA) by accuracy class and ratio (A)
250/5
Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a
300/5
Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a
400/5
Class 0.5: 2.5 · Class 1.0: n/a · Class 3.0: n/a
500/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
600/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
750/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
800/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
1000/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
Ratings: SCT-DP-88, rated output (VA) by accuracy class and ratio (A)
250/5
Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a
300/5
Class 0.5: 2.5 · Class 1.0: n/a · Class 3.0: n/a
400/5
Class 0.5: 2.5 · Class 1.0: n/a · Class 3.0: n/a
500/5
Class 0.5: 2.5 · Class 1.0: n/a · Class 3.0: n/a
600/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
750/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
800/5
Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a
1000/5
Class 0.5: 5 · Class 1.0: 10 · Class 3.0: n/a
Ratings: SCT-DP-812, rated output (VA) by accuracy class and ratio (A)
500/5
Class 0.5: 2.5 · Class 1.0: 10 · Class 3.0: n/a
600/5
Class 0.5: 2.5 · Class 1.0: 10 · Class 3.0: n/a
750/5
Class 0.5: 2.5 · Class 1.0: 10 · Class 3.0: n/a
800/5
Class 0.5: 2.5 · Class 1.0: 10 · Class 3.0: n/a
1000/5
Class 0.5: 5 · Class 1.0: 15 · Class 3.0: n/a
1200/5
Class 0.5: 7.5 · Class 1.0: 20 · Class 3.0: n/a
1250/5
Class 0.5: 7.5 · Class 1.0: 20 · Class 3.0: n/a
1500/5
Class 0.5: 10 · Class 1.0: 20 · Class 3.0: n/a
1600/5
Class 0.5: 10 · Class 1.0: 20 · Class 3.0: n/a
2000/5
Class 0.5: 10 · Class 1.0: 20 · Class 3.0: n/a
2500/5
Class 0.5: 15 · Class 1.0: 20 · Class 3.0: n/a
3000/5
Class 0.5: 20 · Class 1.0: 20 · Class 3.0: n/a
Ratings: SCT-DP-816, rated output (VA) by accuracy class and ratio (A)
1000/5
Class 0.5: 10 · Class 1.0: 20 · Class 3.0: n/a
1500/5
Class 0.5: 15 · Class 1.0: 25 · Class 3.0: n/a
2000/5
Class 0.5: 15 · Class 1.0: 25 · Class 3.0: n/a
2500/5
Class 0.5: 15 · Class 1.0: 25 · Class 3.0: n/a
3000/5
Class 0.5: 20 · Class 1.0: 30 · Class 3.0: n/a
4000/5
Class 0.5: 20 · Class 1.0: 30 · Class 3.0: n/a
5000/5
Class 0.5: 20 · Class 1.0: 30 · Class 3.0: n/a
Rated output in VA for each ratio and accuracy class with a 5A secondary. n/a means the class is not offered at that ratio. Accuracy class subject to rated burden (p. 6).
Standards compliance
Instrument Transformers
IEC 61869-2: Additional requirements for current transformers
AS 61869.2: Australian adoption of IEC 61869-2
Legacy Standards
IEC 60044-1: Instrument transformers, current transformers
AS 60044.1: Current transformers
BS 7626: Specification for current transformers
Insulation and Thermal
Insulation level 0.72/3kV
Short time thermal current Ith = 100 × In
Instrument security factor FS < 5
Ordering information
MODEL · RATIO · CLASS · RATED OUTPUT · OPTIONS
Model
20 × 30mm window
SCT-DP-23
50 × 80mm window
SCT-DP-58
80 × 80mm window
SCT-DP-88
80 × 120mm window
SCT-DP-812
80 × 160mm window
SCT-DP-816
Ratio
Primary 100A to 5000A
e.g. 600
Secondary 5A
/5
Secondary 1A (contact SATEC)
/1
Accuracy class
Class 0.5
0.5
Class 1.0
1.0
Class 3.0 (SCT-DP-23 only)
3.0
Rated output
Per ratings table, page 5
1.5VA to 30VA
Ordering example: SCT-DP-58 · 600/5 · Class 0.5 · 5VA