PTS · DATASHEET

PTS pole-top MV voltage and current sensor datasheet

Pole-top MV voltage and current sensors for Smart Grid monitoring.

Transcribed from the SATEC Australia datasheet TBV1.0, 29 September 2026 (PDF, 4 pages, 747 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

SATEC Pole-Top Sensors (PTS) are line post insulators with built-in voltage and current sensing for medium voltage distribution networks. They replace existing pole insulators and install without cutting the line. Utilities gain real-time visibility of overhead feeders for distribution automation and Smart Grid programmes.

Each sensor produces a low-level, non-hazardous signal instead of conventional CT and VT secondaries. Paired with the SATEC PM174 or PM175 power quality analyser and calibrated as a system, the sensors deliver Class 0.5S measurements along with waveforms, harmonics and phasors from remote pole locations.

PTS 15: Pole-top sensor for 15kV networks. 110kV impulse (BIL) rating.

PTS 25: Pole-top sensor for 25kV networks. 150kV impulse (BIL) rating.

PTS 35: Pole-top sensor for 35kV networks. 200kV impulse (BIL) rating.

Main features

Feature capabilities

Sensor design

  • Compact, economical power line sensing
  • Voltage (PT) and current (CT) sensing combined in the insulator
  • Linear outputs up to fault levels
  • Native sensor accuracy of 2% for current and 1% for voltage
  • Low-level, non-hazardous voltage on the output
  • Completely sealed against moisture

System accuracy and monitoring (with SATEC PM174 or PM175)

  • Analyser inputs designed to interface with low-level sensor outputs
  • Calibrated as a system to Class 0.5S accuracy
  • Precise real-time measurements
  • Waveform capture and power quality features
  • Phasors and phase rotation
  • Directional harmonics and neutral currents
  • Local display and on-board memory for data redundancy

Distribution network management

  • Line losses and load balance
  • Capacitor controls and voltage regulation
  • Outage detection and fault location
  • Harmonics monitoring
  • Power theft detection
  • Demand reduction during peak load times

Complete cabinet package

  • Custom SATEC enclosure for the PM174 or PM175 input connections
  • Communications modem for real-time data to SCADA
  • Supplied as a complete pole-mounted package
  • Expandable as monitoring needs grow

Communications and integration

  • DNP3 protocol for utility SCADA integration
  • Real-time data from remote pole locations
  • Monitor, coordinate and operate distribution systems in real time
  • Waveform, harmonic and power quality data delivered to the control room

Software support

  • Power Analysis Software (PAS) to program and monitor the PM174 or PM175
  • Expertpower web platform for energy management and power quality analysis

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Ratings by model: PTS 15
Insulation class15kV
Impulse (BIL)110kV
Leakage distance41.6 cm (16.4 in)
Dry arc distance22.3 cm (8.8 in)
Corona (extinction)11kV
Low frequency dry flashover80kV
Low frequency wet flashover60kV
Overall height33.5 cm (13.2 in)
Cantilever strength (ultimate)1270 kg (2800 lb)
Weight17.6 kg (39 lb)
Shipping weight20 kg (44 lb)
Ratings by model: PTS 25
Insulation class25kV
Impulse (BIL)150kV
Leakage distance62.2 cm (24.5 in)
Dry arc distance32 cm (12.6 in)
Corona (extinction)19kV
Low frequency dry flashover110kV
Low frequency wet flashover85kV
Overall height42.4 cm (16.7 in)
Cantilever strength (ultimate)1270 kg (2800 lb)
Weight22.2 kg (49 lb)
Shipping weight24.5 kg (54 lb)
Ratings by model: PTS 35
Insulation class35kV
Impulse (BIL)200kV
Leakage distance89.6 cm (35.3 in)
Dry arc distance41.4 cm (16.3 in)
Corona (extinction)26kV
Low frequency dry flashover125kV
Low frequency wet flashover100kV
Overall height52.8 cm (20.8 in)
Cantilever strength (ultimate)1270 kg (2800 lb)
Weight26.7 kg (59 lb)
Shipping weight29 kg (64 lb)
Current signal output
Ratio600A:10V
Output burden/loadCalibrated for a 10 kΩ or greater load
Open circuit voltage10V at 600A line current
Voltage signal output
Divider ratioDepends on network
Output impedanceCalibrated for a 1 MΩ load
Accuracy
Sensor native accuracy2% for current, 1% for voltage
With SATEC PM174 or PM175 calibrationClass 0.5S
Operating temperature
Temperature range-40°C to +65°C (-40°F to +149°F)
Conductor diameter range
Conductor diameter6.35 mm to 31.75 mm (0.25 in to 1.25 in)
KeeperTwo-sided keeper in aluminium (for aluminium conductor) or galvanised ductile iron (for copper conductor)
Construction and installation
Body materialMoulded from Polysil, a high dielectric strength, anti-tracking polymer concrete developed under an EPRI contract
MountingVertical mounting only
Application limitNot for dead-end use
InstallationReplaces an existing pole insulator with no line cutting

Ordering information

PTS

Model
Pole-Top Sensor, line post voltage and current sensorPTS
Network voltage class
For 15kV networks15
For 25kV networks25
For 35kV networks35

Example: PTS 25 is a Pole-Top Sensor for a 25kV network.