PTS · DATASHEET
PTS pole-top MV voltage and current sensor datasheet
Pole-top MV voltage and current sensors for Smart Grid monitoring.
Transcribed from the SATEC Australia datasheet TBV1.0, 29 September 2026 (PDF, 4 pages, 747 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
SATEC Pole-Top Sensors (PTS) are line post insulators with built-in voltage and current sensing for medium voltage distribution networks. They replace existing pole insulators and install without cutting the line. Utilities gain real-time visibility of overhead feeders for distribution automation and Smart Grid programmes.
Each sensor produces a low-level, non-hazardous signal instead of conventional CT and VT secondaries. Paired with the SATEC PM174 or PM175 power quality analyser and calibrated as a system, the sensors deliver Class 0.5S measurements along with waveforms, harmonics and phasors from remote pole locations.
PTS 15: Pole-top sensor for 15kV networks. 110kV impulse (BIL) rating.
PTS 25: Pole-top sensor for 25kV networks. 150kV impulse (BIL) rating.
PTS 35: Pole-top sensor for 35kV networks. 200kV impulse (BIL) rating.
Main features
- Voltage and current sensing in one line post insulator
- Replaces existing pole insulators
- Installs with no line cutting
- 15kV, 25kV and 35kV insulation classes
- Linear outputs up to fault levels
- Non-hazardous voltage on the signal output
- 600A:10V current signal output ratio
- Class 0.5S system accuracy with PM174 or PM175 calibration
- Completely sealed against moisture
- Anti-tracking polymer concrete construction
- Operating range of -40°C to +65°C
- Suits aluminium and copper conductors
Feature capabilities
Sensor design
- Compact, economical power line sensing
- Voltage (PT) and current (CT) sensing combined in the insulator
- Linear outputs up to fault levels
- Native sensor accuracy of 2% for current and 1% for voltage
- Low-level, non-hazardous voltage on the output
- Completely sealed against moisture
System accuracy and monitoring (with SATEC PM174 or PM175)
- Analyser inputs designed to interface with low-level sensor outputs
- Calibrated as a system to Class 0.5S accuracy
- Precise real-time measurements
- Waveform capture and power quality features
- Phasors and phase rotation
- Directional harmonics and neutral currents
- Local display and on-board memory for data redundancy
Distribution network management
- Line losses and load balance
- Capacitor controls and voltage regulation
- Outage detection and fault location
- Harmonics monitoring
- Power theft detection
- Demand reduction during peak load times
Complete cabinet package
- Custom SATEC enclosure for the PM174 or PM175 input connections
- Communications modem for real-time data to SCADA
- Supplied as a complete pole-mounted package
- Expandable as monitoring needs grow
Communications and integration
- DNP3 protocol for utility SCADA integration
- Real-time data from remote pole locations
- Monitor, coordinate and operate distribution systems in real time
- Waveform, harmonic and power quality data delivered to the control room
Software support
- Power Analysis Software (PAS) to program and monitor the PM174 or PM175
- Expertpower web platform for energy management and power quality analysis
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
| Insulation class | 15kV |
|---|---|
| Impulse (BIL) | 110kV |
| Leakage distance | 41.6 cm (16.4 in) |
| Dry arc distance | 22.3 cm (8.8 in) |
| Corona (extinction) | 11kV |
| Low frequency dry flashover | 80kV |
| Low frequency wet flashover | 60kV |
| Overall height | 33.5 cm (13.2 in) |
| Cantilever strength (ultimate) | 1270 kg (2800 lb) |
| Weight | 17.6 kg (39 lb) |
| Shipping weight | 20 kg (44 lb) |
| Insulation class | 25kV |
|---|---|
| Impulse (BIL) | 150kV |
| Leakage distance | 62.2 cm (24.5 in) |
| Dry arc distance | 32 cm (12.6 in) |
| Corona (extinction) | 19kV |
| Low frequency dry flashover | 110kV |
| Low frequency wet flashover | 85kV |
| Overall height | 42.4 cm (16.7 in) |
| Cantilever strength (ultimate) | 1270 kg (2800 lb) |
| Weight | 22.2 kg (49 lb) |
| Shipping weight | 24.5 kg (54 lb) |
| Insulation class | 35kV |
|---|---|
| Impulse (BIL) | 200kV |
| Leakage distance | 89.6 cm (35.3 in) |
| Dry arc distance | 41.4 cm (16.3 in) |
| Corona (extinction) | 26kV |
| Low frequency dry flashover | 125kV |
| Low frequency wet flashover | 100kV |
| Overall height | 52.8 cm (20.8 in) |
| Cantilever strength (ultimate) | 1270 kg (2800 lb) |
| Weight | 26.7 kg (59 lb) |
| Shipping weight | 29 kg (64 lb) |
| Ratio | 600A:10V |
|---|---|
| Output burden/load | Calibrated for a 10 kΩ or greater load |
| Open circuit voltage | 10V at 600A line current |
| Divider ratio | Depends on network |
|---|---|
| Output impedance | Calibrated for a 1 MΩ load |
| Sensor native accuracy | 2% for current, 1% for voltage |
|---|---|
| With SATEC PM174 or PM175 calibration | Class 0.5S |
| Temperature range | -40°C to +65°C (-40°F to +149°F) |
|---|
| Conductor diameter | 6.35 mm to 31.75 mm (0.25 in to 1.25 in) |
|---|---|
| Keeper | Two-sided keeper in aluminium (for aluminium conductor) or galvanised ductile iron (for copper conductor) |
| Body material | Moulded from Polysil, a high dielectric strength, anti-tracking polymer concrete developed under an EPRI contract |
|---|---|
| Mounting | Vertical mounting only |
| Application limit | Not for dead-end use |
| Installation | Replaces an existing pole insulator with no line cutting |
Ordering information
PTS
| Pole-Top Sensor, line post voltage and current sensor | PTS |
|---|
| For 15kV networks | 15 |
|---|---|
| For 25kV networks | 25 |
| For 35kV networks | 35 |
Example: PTS 25 is a Pole-Top Sensor for a 25kV network.