PRO Series DC · DATASHEET

PRO Series DC metering datasheet

High accuracy DC power and energy metering.

Transcribed from the SATEC Australia datasheet TBV1.0, 16 September 2026 (PDF, 9 pages, 2622 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PRO Series DC power and energy meters are advanced DC meters, fully compliant and tested to the DC metering standard AS/IEC 62053-41. Available as the panel-mounted PRO-PM335 or DIN-rail PRO-EM235, the range suits battery energy storage systems, EV charging, solar and other DC applications that need revenue-grade measurement, alongside substation and industrial monitoring.

The PRO Series DC measurement system operates via Hall Effect sensors or SATEC’s UHACS (Flux Gate) current sensors, for up to three DC channel inputs, with a wide voltage input range from 10–820V DC standard, extendable to 1500V DC with SATEC’s Voltage Ratio Module (VRM). Dual Ethernet ports with daisy-chain Ethernet, RS-485 and an infrared port are built in, supporting Modbus, IEC 61850 and DNP3 protocols.

PRO-PM335-HACS-DC: Panel-mounted DC meter with a 3.5″ TFT colour display, measuring voltage, current, power, energy and demand with data logging capabilities.

PRO-EM235-HACS-DC: DIN-rail mounted DC meter with a 1.77″ TFT colour display, measuring voltage, current, power, energy and demand with data logging capabilities.

Main features

Feature capabilities

DC power and energy metering

  • Three isolated DC voltage inputs (10–820V DC), extendable up to 1500V DC via VRM
  • DC voltage/current accuracy 0.5%
  • Four isolated DC current inputs up to 2500A DC (via UHACS or Hall Effect sensors)
  • Precise energy & power demand metering: TOU, 16 summary/TOU energy and demand registers, block and sliding demands, up to 64 energy sources
  • 32 digital counters for pulses from external sources and internal events

Event and data recording

  • Event recorder for internal diagnostic events, control events and I/O operations
  • 16 programmable data recorders, logging on a periodic basis or on any internal/external trigger
  • Embedded programmable controller — 64 control setpoints, OR/AND logic, extensive triggers, cross-triggering between devices via Ethernet for synchronous event capture
  • Up to sixteen triggering channels
  • 16 programmable timers, from ½ cycle to 24 hours

High precision time synchronisation

  • SNTP
  • 1 pps via digital input
  • IRIG-B time-code input (future release)
  • Real-time clock with battery backup and three-year retention
  • Backup power supply unit

Communications (standard)

  • Dual Ethernet ports (10/100 Base-T, transformer-isolated), up to 10 simultaneous connections per port
  • Daisy-chain Ethernet
  • RS-485 optically isolated port, up to 115,200 bps
  • Infrared port, front panel access with magnetic head
  • USB 2.0 Type-C port

Expertpower client and notifications

  • Expertpower client for Modbus/TCP communication with a remote or local (stand-alone) SATEC Expertpower server
  • TCP notification client to a remote Modbus/TCP server, on events or periodically, via any IP-enabled communication port
  • Meter security — password protection for meter setups and accumulated data against unauthorised changes

Optional built-in I/O ports

  • 2 optically isolated digital inputs — 24V DC dry contact, 1 ms sampling rate
  • 1 solid-state relay output — unlatched, latched and pulse operation, fail-safe for alarm notifications
  • 1 optically isolated analogue input — configurable universal range

Add-on modules (PRO Series modules only)

  • 8DI — 8 optically isolated digital inputs, dry contact or 24/48/125/250V AC/DC wet
  • 4RO — 4 relays, electromechanical or solid-state, with fail-safe alarm operation
  • 4DI + 2RO combination module
  • 4AO — 4 isolated universal analogue outputs
  • Up to 4 expansion modules side by side; 3 modules requires an auxiliary power supply module

Software support

  • PAS — SATEC’s bundled configuration and data-acquisition tool, including waveforms, phasors and harmonics
  • Expertpower — SATEC’s internet-based energy management software, with no client software installation required
  • eXpertConnect™ App — mobile connection to the meter for on-site configuration, readings and diagnostics

Applications

  • Energy management and revenue metering
  • SCADA-ready industrial automation
  • Substation automation and industrial monitoring
  • Renewable energy and SATEC data centre solutions

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Voltage inputs
Operating range10–820V DC (standard)
Extended rangeUp to 1500V DC via SATEC Voltage Ratio Module (VRM)
Input impedance4 MΩ
Isolation4000V AC @ 1 min
Wire sizeUp to 14 AWG (≤2.5 mm²)
Current inputs — DC Hall Effect sensors
HCS100-S100A split-core
HCS10001000A solid-core
HCS2000-S2000A split-core
Current inputs — UHACS (Flux Gate) sensors
FCS-300300A
FCS-600600A
FCS-10001000A
FCS-2500-132500A

Both Hall Effect and UHACS sensors require a separate power supply; the FCS-2500-13 UHACS sensor requires two power supplies connected in parallel.

Digital inputs (2 DI) — built-in, optional
Contact typeDry contacts, internally wetted @ 24V DC
Galvanic isolation4000V AC @ 1 min
Internal power supply24V DC
Scan time1 ms
Connector typeRemovable, 5 pins
Wire size14 AWG (up to 1.5 mm²)
Terminal pitch5 mm
Digital output (1 DO) — solid-state relay
Rating0.15A/250V AC/DC, 1 contact (SPST Form A)
Galvanic isolation4000V AC @ 1 min
Operate time1 ms max.
Release time0.25 ms max.
Update time1 cycle
Connector typeRemovable, 4 pins
Wire size14 AWG (up to 1.5 mm²)
Analogue input (1 AI)
RangeUniversal, -1mA to 20mA (configurable: ±1mA, 0–1mA, 0–20mA, 4–20mA, etc.)
Galvanic isolation4000V AC @ 1 min
Scan time1 ms
Accuracy<0.5% FS
Connector typeRemovable, 5 pins
Wire size14 AWG (up to 1.5 mm²)
Terminal pitch5 mm
Add-on module — digital inputs (8 DI)
Contact typeDry contact @ 24V DC, or wet contact @ 250V DC (8DI only)
SensitivityOpen >100 kΩ, closed <100 Ω
Galvanic isolation4000V AC @ 1 min
Internal power supply24V DC
Scan time1 ms
Connector typeRemovable, 2×5 pins
Wire sizeUp to 14 AWG (≤1.5 mm²)
Add-on module — digital outputs (4 DO)
Electromechanical (option 1)4 relays, 5A/250V AC or 5A/30V DC, 1 contact (SPST Form A); isolation 3000V AC (contacts–coil), 750V AC (open contacts)
Solid-state (option 2)4 relays, 100mA/800V AC, 1 contact (SPST Form A); isolation 3000V AC @ 1 min (800V peak open contacts)
Operate / release time5–10 ms max. / 5 ms max.
Wire size14 AWG (up to 1.5 mm²)
Digital inputs + outputs (4DI + 2RO)
Combination module4DI + 2RO, per the digital input and output specifications above
Analogue outputs (4 AO)
Ranges±1mA, 0–20mA, 4–20mA, 0–1mA (max. load 10 kΩ or 510 Ω per range, 100% overload)
Accuracy0.5% FS
Scan time1 ms (manually or remotely programmed)
Wire sizeUp to 14 AWG (≤1.5 mm²)
Terminals pitch5 mm
Power supply
Rated input57.7–277V AC @ 50/60 Hz, 48–290V DC
Tolerance±15%
Burden11VA @ V AC, 6VA @ V DC
Isolation4000V AC @ 1 min
Wire sizeUp to 14 AWG (≤1.5 mm²)
Auxiliary power supply module — AC/DC
Rated input88–264V AC / 90–290V DC
Output5W
Burden15VA
Withstand4kV AC @ 1 min
WiringL/+, N/-
Terminals pitch5 mm
Wire sizeUp to 12 AWG (≤2.5 mm²)
Auxiliary power supply module — 24V DC
Rated input9–36V DC
Output7W
Galvanic isolation4000V AC @ 1 min
Isolation4 kV
Terminals pitch5 mm
Wire size14 AWG (up to 1.5 mm²)
Communication — serial
PortRS-485, optically isolated, up to 115,200 bps
Isolation4000V AC @ 1 min
Supported protocolsModbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101
Communication — Ethernet (dual / 2 ports)
PortTransformer-isolated 10/100 Base-T Ethernet, RJ45
Supported protocolsModbus/TCP (port 502), DNP3/TCP (port 20000), IEC 60870-5-104 (port 2404), IEC 61850 (port 102, SNTP)
Simultaneous connections10 (5 Modbus/TCP + 5 DNP3/TCP)
Isolation4000V AC @ 1 min
Communication — infrared (IR)
PortInfrared COM port, front panel access with magnetic head
Supported protocolsModbus RTU & DNP3, IEC 62056-21 (for local meter data exchange)
Isolation4000V AC @ 1 min
Communication — USB
PortFull-speed USB 2.0, Type-C connector
Isolation4000V AC @ 1 min
Supported protocolsTo be confirmed
Log memory
Capacity16GB for long-term waveform and data recording
Display
PM3353.5″ LCD TFT colour display, 320×480 dots resolution
EM2351.77″ LCD TFT colour display, 120×160 dots resolution
Environmental conditions
Operating temperature-40°C to +70°C (-40°F to 158°F)
Display operating temperature-25°C to +70°C (-13°F to 158°F)
Storage temperature-40°C to +85°C (-40°F to 185°F)
Humidity0 to 95% RH, non-condensing
Degree of protectionIP51
Construction
Weight0.70kg (1.54 lb)
Dimensions (PM335)108.6×74.7×113.3 mm
Dimensions (EM235)89.5×72×90 mm
Materials
Case enclosurePlastic PC/ABS blend
Display bodyPlastic PC/ABS blend
Front panelPlastic PC
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
LabelsPolyester film (UL94-V0)

Standards compliance

Electromagnetic immunity

  • IEC 62052-11, CLC/TR 50579 (conducted disturbances 2–150kHz), IEEE C62.41 and C37.90.1
  • IEC 61000-6-2
  • IEC 61000-4-2 level 3: Electrostatic Discharge
  • IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
  • IEC 61000-4-4 level 3: Electrical Fast Transient
  • IEC 61000-4-5 level 3: Surge
  • IEC 61000-4-6 level 3: Conducted Radio Frequency
  • IEC 61000-4-8: Power Frequency Magnetic Field
  • ANSI/IEEE C37.90.1: Fast Transient SWC

Environmental

  • IEC 60529: Protection
  • IEC 60068-2-1: Cold
  • IEC 60068-2-2: Dry Heat
  • IEC 60068-2-30: Damp Heat
  • IEC 60068-2-5: Solar Radiation

Accuracy

  • AS/IEC 62053-22:2003, Class 0.2S
  • IEC 62053-24:2014, Class 0.5S
  • ANSI C12.20–2015, Class 10 (0.2%)

Electromagnetic emission

  • IEC 61000-6-4* Radiated/Conducted Class B
  • IEC CISPR 22* Radiated/Conducted Class B
  • Emission per EN 55011/22 Class B, FCC p.15 Class B

Safety / construction

  • IEC 61010, IEC 62052-11 & IEC 61557-12
  • UL61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use – Part 1: General Requirements, Edition 3, Revision Date 07/19/2019
  • CSA C22.2 No. 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use – Part 1: General Requirements, Edition 3, Revision Date 11/2018
  • AC Impulse Insulation: meets IEC 62052-11 — 4000V AC for 1 minute, 6KV/500Ω @ 1.2/50 µs impulse
  • IEC 60068-2-6: Vibration (sinusoidal)
  • IEC 60068-2-27: Shock Test
  • IEC 60068-2-75: Hammer Test
  • AS 62052-11*

Note

  • * Meets standard requirements.

Ordering information

MODEL – CURRENT – CALIBRATION – POWER – I/O – LANGUAGE – PROTOCOL

Model
PM335 Panel-MountPRO-PM335
EM235 DIN-Rail MountPRO-EM235
Transducer VersionPRO-RPM035
Current inputs
High Accuracy Current Sensors (HACS), 50/60Hz onlyHACS
Calibration for DC current (DC)
DCDC
Power supply
88–320V AC / 40–290V DCACDC
Built-in I/O
2×DI (dry contact) + 1×SSR output + 1×universal AI (-1mA to 20mA)IOS
Display language
EnglishEN
Optional protocols
IEC 61850 Communication Protocol850

Expansion modules

Optional modules* — maximum of 3 modules
4 Relay Outputs – 250V/5A ACEMR4
4 SSR Outputs – 250V/0.1A ACSSR4
4 Digital Inputs (Dry Contact @ 24V DC) + 2 SSR Outputs4DIOS-DRC
4 Digital Inputs (Dry Contact @ 24V DC) + 2 EMR Outputs4DIOR-DRC
8 Digital Inputs – Dry ContactDI8-DRC
8 Digital Inputs – 24, 48, 125, 250V DCDI8-24,48,125,250V
4 Analogue Outputs; configurable range4AO

* Auxiliary power supply required when configured with 3 modules.

Auxiliary power supply — maximum of 1 module
AUX. P.S. AC/DC – 88–264V AC / 90–290V DCAUX-ACDC
24V DC (9–36V DC)AUX-24DC

Downloads and related

Questions about this datasheet? Use the contact form.