PM335 and EM235 · DATASHEET

PM335 and EM235 PRO Series power quality analyser datasheet

Advanced power meter and power quality analyser.

Transcribed from the SATEC Australia datasheet TBV1.0, 24 September 2026 (PDF, 8 pages, 2734 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PRO Series is a modular family of advanced power meters and power quality analysers for substations, utilities, data centres, renewable energy sites and industrial networks. Each model is available as a Class S analyser or as a full IEC 61000-4-30 Class A Ed. 3.1 power quality analyser. It brings together capabilities usually spread across several separate devices.

Every unit delivers Class 0.2S revenue accuracy with AC and DC measurement on wide range inputs. Leakage current detection uses a fourth current input. Dual port Ethernet with IEC 61850 Ed. 2, 16GB of recording memory and up to four add-on modules make it ready for demanding monitoring and control projects.

Main features

Feature capabilities

Models

  • PRO-PM335: Panel-mount analyser with a 3.5″ TFT colour display. Class S or Class A.
  • PRO-EM235: DIN-rail analyser with a 1.77″ TFT colour display. Class S or Class A.
  • PRO-RPM035: Transducer version of the PRO Series analyser. Class S or Class A.

Billing and energy metering

  • Four-quadrant active and reactive energy polyphase meter: Class 0.2S AS/IEC 62053-22 and Class 0.2 ANSI C12.20
  • Time-of-Use (TOU) with 16 summary (totalisation) and TOU energy and demand registers for substation energy management
  • Accumulation of energy pulses from external watt-meters
  • Block and sliding demands for up to 64 energy sources
  • Demand meter for amps, volts and harmonic demands

Multi-functional power meter

  • Three-phase true RMS volts, amps, powers, power factors, unbalance and neutral current
  • Phasors and symmetrical components
  • Frequency readings with three and four decimal resolution
  • 32 digital counters for pulses from external sources and internal events
  • 16 programmable timers from ½ cycle to 24 hours for periodic recording and triggering

Harmonic analyser

  • Per IEC 61000-4-7, up to the 63rd harmonic for volts and amps
  • THD for volts and amps, TDD and K-factor
  • Interharmonics for volts and amps
  • Directional power harmonics (load or source) and harmonic power factor

Time synchronisation and clock

  • High precision time synchronisation via SNTP or 1 pps through a digital input
  • IRIG-B time-code input (future release)
  • Real-time clock with battery backup and three-year retention

Power quality: PQ-A models (Class A Ed. 3.1)

  • Power quality analysis in full compliance with IEC 61000-4-30 Class A, Edition 3.1
  • Built-in statistics and reports per EN 50160
  • IEEE 519 harmonic analysis

Power quality: all models

  • Sags and swells (dips and overvoltages), interruptions, frequency and voltage variations
  • Flicker per IEC 61000-4-15 and voltage unbalance
  • V-I angle, current TDD coefficients and K-factors
  • Programmable thresholds and hysteresis
  • Power quality event recorder with waveform and data recording
  • Selectable sampling rate up to 256 samples per cycle
  • Redundant auxiliary power supply for recording major dips and interruptions

Fault recorder

  • Up to 26 external digital triggers from protection relays
  • Onboard zero-sequence currents and volts plus current and voltage unbalance
  • Fault waveforms and fast RMS trace
  • Cross triggering between devices via digital inputs for synchronous event capture

Waveform and data recorders

  • Eight fast waveform recorders with seven-channel (V1-V3, I1-I4) simultaneous recording
  • Selectable AC sampling rate of 32, 64, 128 or 256 samples per cycle with 20 pre-fault cycles
  • Synchronised waveforms from multiple devices in a single plot
  • Export to COMTRADE and PQDIF formats via PAS software
  • 16 programmable data recorders, periodic or on any internal or external trigger
  • Event recorder for internal diagnostics, control events and I/O operations

AC measurements

  • Three fully isolated AC voltage inputs rated 10-1,000V AC (L-L) at 50/60Hz
  • Four isolated AC current inputs (see Current Inputs in Specifications)
  • Leakage current detection: residual current calculated via the fourth current input monitoring the neutral line, with configurable alerts and control thresholds

DC measurements

  • Three isolated DC voltage inputs from 10 to 820V DC, or up to 1,500V DC via an optional adapter
  • DC voltage accuracy: 0.2%
  • Four isolated DC current inputs up to 3,000A DC using SATEC U-HACS or Hall Effect sensors
  • DC current accuracy: 0.2%
  • DC power calculated from measured voltage and current

Embedded programmable controller

  • 64 control setpoints with OR/AND logic and extensive triggers
  • Programmable thresholds and delays with relay control
  • Event-driven data recording with up to 16 triggering channels
  • Cross triggering between devices via Ethernet for synchronous event capture

Software support

  • Power Analysis Software (PAS) for configuration, data retrieval and waveform analysis
  • Expertpower client over Modbus/TCP to a remote or local (stand-alone) Expertpower server
  • eXpertConnect™ App for mobile configuration, readings and diagnostics

Communications

  • RS-485 serial port up to 115,200 bps: Modbus RTU/ASCII, DNP3.0, SNTP and IEC 60870-5-101
  • Two 10/100 Base-T Ethernet ports: Modbus/TCP, DNP3/TCP, IEC 60870-5-104 and IEC 61850, with up to 10 non-intrusive simultaneous connections per port
  • Infrared port (19,200 bps) with Modbus and DNP3 for local data exchange
  • USB 2.0 port (type C)
  • TCP notification client to a remote Modbus/TCP server, on events or periodically

Expansion modules and I/O: up to four modules side by side

  • Up to two expansion modules are self-energised
  • Three I/O modules require the auxiliary power supply module
  • Three daisy-chain slots for plug-in I/O and communication modules

Expansion modules and I/O: optional built-in I/O

  • Two optically isolated 24V DC dry contact inputs with 1 ms sampling and 1 pps time synchronisation
  • One solid state relay output for alarms, pulses and remote control
  • One universal analogue input (±1mA, 0-1mA, 0-20mA, 4-20mA)

Expansion modules and I/O: add-on modules

  • 8 DI: dry contact or 24/48/125/250V wet inputs
  • 4 RO: electromechanical (EMR) or solid state (SSR) relays
  • 4 DI + 2 RO combination module
  • 4 AO: isolated universal analogue outputs
  • Auxiliary power supply: 88-264V AC / 90-290V DC or 24V DC (9-36V DC)

Applications

  • Energy management and revenue metering
  • SCADA and substation automation
  • Industrial monitoring and power quality
  • Renewable energy

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Voltage inputs
Operating range10-600V AC (L-N); 0-1,000V AC (L-L)
Direct DC voltage range210-820V DC
Input impedance4MΩ
Burden at 400V≤ 0.04VA
Burden at 120V< 0.01VA
Isolation4,000V AC for 1 min
Wire sizeUp to 14 AWG (≤ 2.5 mm²)

1 Minimum value for accurate detection is 6V L-N and 10V L-L. 2 Measuring up to 1,500V DC is possible via an adapter.

Current inputs: 1A or 5A from CT secondary (standard)
Operating rangeContinuous 10A RMS
Burden< 0.2VA at In = 1A or 5A
Overload withstand15A RMS continuous, 200A (20 × Imax) RMS for ½ second
Current inputs: optional inputs
DC0-20mA input for DC Hall Effect sensors
HACS0-20mA inputs for solid or split core SATEC High Accuracy Current Sensors
LPCT sensor interface (V/I)
Voltage input(3.25/√3) V
Voltage input burden200kΩ ±1%
Current input225mV
Current input burden> 20kΩ
Connector type2 wires
Power supply
Rated input57.7-277V AC at 50/60Hz; 48-290V DC
Tolerance±15%
Burden11VA AC, 6VA DC
Isolation4,000V AC for 1 min
Wire sizeUp to 14 AWG (≤ 1.5 mm²)
Built-in I/O (optional): digital inputs (2 DI)
TypeDry contacts, internally wetted at 24V DC
Galvanic isolation4,000V AC for 1 min
Internal power supply24V DC
Scan time1 ms
Connector typeRemovable, 5 pins
Wire size14 AWG (up to 1.5 mm²)
Terminal pitch5 mm
Built-in I/O (optional): digital output (1 DO)
TypeSolid state relay rated 0.15A / 250V AC/DC, 1 contact (SPST Form A)
Galvanic isolation4,000V AC for 1 min
Operate time1 ms max.
Release time0.25 ms max.
Update time1 cycle
Connector typeRemovable, 4 pins
Wire size14 AWG (up to 1.5 mm²)
Built-in I/O (optional): analogue input (1 AI)
TypeUniversal, -1mA to 20mA (configurable: ±1mA, 0-1mA, 0-20mA, 4-20mA)
Galvanic isolation4,000V AC for 1 min
Scan time1 ms
Accuracy< 0.5% FS
Connector typeRemovable, 5 pins
Wire size14 AWG (up to 1.5 mm²)
Terminal pitch5 mm
Add-on modules, digital I/O: digital inputs (8 DI)
TypeDry contacts, internally wetted at 24V DC, or wet contact up to 250V DC
SensitivityOpen: input resistance > 100kΩ; Closed: input resistance < 100Ω
Galvanic isolation4,000V AC for 1 min
Internal power supply24V DC
Scan time1 ms
Connector typeRemovable, 2 × 5 pins
Wire size14 AWG (up to 1.5 mm²)
Add-on modules, digital I/O: digital outputs (4 DO), electromechanical relay
Rating4 relays, 5A / 250V AC and 5A / 30V DC, 1 contact (SPST Form A)
Isolation, contacts to coil3,000V AC for 1 min
Isolation, open contacts750V AC
Operate time10 ms max.
Release time5 ms max.
Add-on modules, digital I/O: digital outputs (4 DO), solid state relay
Rating4 relays, 100mA / 800V AC, 1 contact (SPST Form A)
Isolation, contacts to coil3,000V AC for 1 min
Isolation, open contacts800V peak
Operate time5 ms max.
Release time5 ms max.
Update time1 cycle
Wire size14 AWG (up to 1.5 mm²)
Add-on modules, digital I/O: combination module (4 DI + 2 RO)
Combination module (4 DI + 2 RO)Four digital inputs and two relay outputs, per the specifications above
Add-on modules: analogue outputs (4 AO)
TypeUniversal (configurable) isolated analogue outputs
Scan time1 ms
Ranges (manually or remotely programmed)±1mA, max. load 10kΩ (100% overload); 0-20mA, max. load 510Ω; 4-20mA, max. load 510Ω; 0-1mA, max. load 10kΩ (100% overload)
Accuracy0.5% FS
Wire sizeUp to 14 AWG (≤ 1.5 mm²)
Terminal pitch5 mm
Auxiliary power supply (module): AC/DC module
Rated input88-264V AC / 90-290V DC
Output5W
Burden15VA
Withstand4kV AC for 1 min
WiringL/+, N/-
Terminal pitch5 mm
Wire sizeUp to 12 AWG (≤ 2.5 mm²)
Auxiliary power supply (module): 24V DC module
Rated input9-36V DC
Output7W
Galvanic isolation4,000V AC for 1 min
Terminal pitch5 mm
Wire size14 AWG (up to 1.5 mm²)
Communication ports: serial
TypeRS-485 optically isolated, up to 115,200 bps
Supported protocolsModbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101
Isolation4,000V AC for 1 min
Communication ports: Ethernet (dual, 2 ports)
TypeTransformer-isolated 10/100 Base-T, RJ45
Supported protocolsModbus/TCP (port 502); DNP3/TCP (port 20000); IEC 60870-5-104 (port 2404); IEC 61850 (port 102); SNTP
Simultaneous connections10 (5 Modbus/TCP + 5 DNP3/TCP)
Isolation4,000V AC for 1 min
Communication ports: infrared (IR)
TypeFront panel IR port with magnetic head
Supported protocolsModbus RTU, DNP3 and IEC 62056-21 for local meter data exchange
Isolation4,000V AC for 1 min
Communication ports: USB
TypeFull speed USB 2.0
Connector typeUSB Type C
Supported protocolsModbus
Isolation4,000V AC for 1 min
Real-time clock
AccuracyTypical error ±15 seconds per month, < 5 minutes per year at 25°C
RetentionBattery backup, three years
Log memory
Capacity16GB for long-term waveform and data recording
Display
PM3353.5″ TFT colour LCD, 320 × 480 dots
EM2351.77″ TFT colour LCD, 120 × 160 dots
Environmental conditions
Operating temperature-40°C to +70°C (-40°F to 158°F)
Display operating temperature-25°C to +70°C (-13°F to 158°F)
Storage temperature-40°C to +85°C (-40°F to 185°F)
Humidity0 to 95% RH non-condensing
Degree of protectionIP51
Construction
Weight0.70kg (1.54 lb)
Dimensions (PM335)108.6 × 74.7 × 113.3 mm
Dimensions (EM235)89.5 × 72 × 90 mm
Mounting (PM335)Panel mount, 4″ round or 92 × 92 mm square cutout, 50 mm deep
Mounting (EM235)DIN-rail
EnclosureAnti-tamper sealed; power connections at bottom, communications and I/O at top
Materials
Case enclosurePlastic PC/ABS blend
Display bodyPlastic PC/ABS blend
Front panelPlastic PC
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
LabelsPolyester film (UL94-V0)

Standards compliance

Electromagnetic immunity

  • AS/IEC 62052-11, CLC/TR 50579 (conducted disturbances 2-150kHz), IEEE C62.41 and C37.90.1
  • IEC 61000-6-2
  • IEC 61000-4-2 level 3: Electrostatic Discharge
  • IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
  • IEC 61000-4-4 level 3: Electric Fast Transient
  • IEC 61000-4-5 level 3: Surge
  • IEC 61000-4-6 level 3: Conducted Radio Frequency
  • IEC 61000-4-8: Power Frequency Magnetic Field
  • ANSI/IEEE C37.90.1: Fast Transient SWC

Electromagnetic emission

  • IEC 61000-6-4*: Radiated/Conducted Class B
  • IEC CISPR 22*: Radiated/Conducted Class B
  • Emission per EN 55011/22 Class B and FCC Part 15 Class B

Environmental

  • IEC 60529: Protection
  • IEC 60068-2-1: Cold
  • IEC 60068-2-2: Dry Heat
  • IEC 60068-2-30: Damp Heat
  • IEC 60068-2-5: Solar Radiation

Accuracy

  • AS/IEC 62053-22:2003, Class 0.2S
  • IEC 62053-24:2014, Class 0.5S
  • ANSI C12.20-2015, Class 10 (0.2%)

Power quality

  • Designed to comply with EN 50160: Power Quality in European Electricity Supply Networks
  • IEC 61000-4-7: Harmonics and interharmonics measurement
  • IEC 61000-4-15: Flicker measurement
  • IEC 61000-4-30 Class A (Ed. 3.1): Power quality measurement methods

Safety and construction

  • IEC 61010, AS/IEC 62052-11* and IEC 61557-12
  • UL 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General Requirements, Edition 3, revision date 07/19/2019
  • CSA C22.2 No. 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General Requirements, Edition 3, revision date 11/2018
  • AC impulse insulation: meets AS/IEC 62052-11, 4,000V AC for 1 minute and 6kV/500Ω at 1.2/50 µs impulse
  • IEC 60068-2-6: Vibration (sinusoidal)
  • IEC 60068-2-27: Shock Test
  • IEC 60068-2-75: Hammer Test
  • * Meets standard requirements.

Ordering information

MODEL – CURRENT – CAL. FREQ. – POWER – BUILT-IN I/O – LANGUAGE – PROTOCOL

Model
PM335 panel-mount PQ analyser, Class SPRO-PM335-PQ-S
EM235 DIN-rail PQ analyser, Class SPRO-EM235-PQ-S
Transducer version PQ analyser, Class SPRO-RPM035-PQ-S
PM335 panel-mount PQ analyser, Class A (Ed. 3.1)PRO-PM335-PQ-A
EM235 DIN-rail PQ analyser, Class A (Ed. 3.1)PRO-EM235-PQ-A
Transducer version PQ analyser, Class A (Ed. 3.1)PRO-RPM035-PQ-A
Current inputs
5 Ampere5A
1 Ampere1A
5A split core remote HACS, 50/60Hz onlyRS5
High Accuracy Current Sensors (HACS), 50/60Hz onlyHACS
Pole top sensor interface, 0-10V (voltage and current)PTS
Pole top sensor interface, 0-10V (voltage), current 5APTS-5
LPCT: dedicated low voltage interface for MV sensorsLPCT
3V AC inputs for Rogowski current clampsFLEX
Calibration at frequency
50Hz50HZ
60Hz60HZ
Power supply
88-320V AC / 40-290V DCACDC
Built-in I/O
2 × DI (dry contact) + 1 × SSR output + 1 × universal AI (-1mA to 20mA)IOS
Display language
EnglishEN
Optional protocols
IEC 61850 communication protocol850

Expansion modules

Maximum of three I/O modules and one auxiliary power supply module per device.

I/O modules
4 relay outputs, 250V / 5A ACEMR4
4 SSR outputs, 250V / 0.1A ACSSR4
4 digital inputs (dry contact at 24V DC) + 2 SSR outputs4DIOS-DRC
4 digital inputs (dry contact at 24V DC) + 2 EMR outputs4DIOR-DRC
8 digital inputs, dry contactDI8-DRC
8 digital inputs, 24, 48, 125 or 250V DCDI8-24 / 48 / 125 / 250
4 analogue outputs, configurable range4AO
Auxiliary power supply
AC/DC, 88-264V AC / 90-290V DCAUX-ACDC
24V DC (9-36V DC)AUX-24DC

An auxiliary power supply module is required when three I/O modules are fitted.

Downloads and related