PM335 and EM235 PRO Series power quality analyser datasheet
Advanced power meter and power quality analyser.
Transcribed from the SATEC Australia datasheet TBV1.0, 24 September 2026 (PDF, 8 pages, 2734 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The PRO Series is a modular family of advanced power meters and power quality analysers for substations, utilities, data centres, renewable energy sites and industrial networks. Each model is available as a Class S analyser or as a full IEC 61000-4-30 Class A Ed. 3.1 power quality analyser. It brings together capabilities usually spread across several separate devices.
Every unit delivers Class 0.2S revenue accuracy with AC and DC measurement on wide range inputs. Leakage current detection uses a fourth current input. Dual port Ethernet with IEC 61850 Ed. 2, 16GB of recording memory and up to four add-on modules make it ready for demanding monitoring and control projects.
Main features
Class 0.2S four-quadrant energy metering to AS/IEC 62053-22 and ANSI C12.20 Class 0.2
IEC 61000-4-30 Class A Ed. 3.1 power quality analysis on PQ-A models
EN 50160 statistics and reports plus IEEE 519 harmonic analysis
AC inputs to 1,000V AC (L-L) and direct DC voltage from 10 to 820V DC
Harmonics to the 63rd per IEC 61000-4-7 and flicker per IEC 61000-4-15
Leakage and residual current detection via a fourth current input
Flexible current inputs for 1A/5A CTs, HACS, DC sensors, LPCT and Rogowski clamps
Eight fast waveform recorders at up to 256 samples per cycle
16 programmable data recorders with 16GB of onboard memory
Dual Ethernet, RS-485, infrared and USB-C with Modbus, DNP3, IEC 60870-5-101/104 and IEC 61850
Embedded programmable controller with 64 control setpoints
Up to four add-on I/O, analogue output and auxiliary power modules side by side
Feature capabilities
Models
PRO-PM335: Panel-mount analyser with a 3.5″ TFT colour display. Class S or Class A.
PRO-EM235: DIN-rail analyser with a 1.77″ TFT colour display. Class S or Class A.
PRO-RPM035: Transducer version of the PRO Series analyser. Class S or Class A.
Billing and energy metering
Four-quadrant active and reactive energy polyphase meter: Class 0.2S AS/IEC 62053-22 and Class 0.2 ANSI C12.20
Time-of-Use (TOU) with 16 summary (totalisation) and TOU energy and demand registers for substation energy management
Accumulation of energy pulses from external watt-meters
Block and sliding demands for up to 64 energy sources
Demand meter for amps, volts and harmonic demands
Multi-functional power meter
Three-phase true RMS volts, amps, powers, power factors, unbalance and neutral current
Phasors and symmetrical components
Frequency readings with three and four decimal resolution
32 digital counters for pulses from external sources and internal events
16 programmable timers from ½ cycle to 24 hours for periodic recording and triggering
Harmonic analyser
Per IEC 61000-4-7, up to the 63rd harmonic for volts and amps
THD for volts and amps, TDD and K-factor
Interharmonics for volts and amps
Directional power harmonics (load or source) and harmonic power factor
Time synchronisation and clock
High precision time synchronisation via SNTP or 1 pps through a digital input
IRIG-B time-code input (future release)
Real-time clock with battery backup and three-year retention
Power quality: PQ-A models (Class A Ed. 3.1)
Power quality analysis in full compliance with IEC 61000-4-30 Class A, Edition 3.1
Built-in statistics and reports per EN 50160
IEEE 519 harmonic analysis
Power quality: all models
Sags and swells (dips and overvoltages), interruptions, frequency and voltage variations
Flicker per IEC 61000-4-15 and voltage unbalance
V-I angle, current TDD coefficients and K-factors
Programmable thresholds and hysteresis
Power quality event recorder with waveform and data recording
Selectable sampling rate up to 256 samples per cycle
Redundant auxiliary power supply for recording major dips and interruptions
Fault recorder
Up to 26 external digital triggers from protection relays
Onboard zero-sequence currents and volts plus current and voltage unbalance
Fault waveforms and fast RMS trace
Cross triggering between devices via digital inputs for synchronous event capture
Waveform and data recorders
Eight fast waveform recorders with seven-channel (V1-V3, I1-I4) simultaneous recording
Selectable AC sampling rate of 32, 64, 128 or 256 samples per cycle with 20 pre-fault cycles
Synchronised waveforms from multiple devices in a single plot
Export to COMTRADE and PQDIF formats via PAS software
16 programmable data recorders, periodic or on any internal or external trigger
Event recorder for internal diagnostics, control events and I/O operations
AC measurements
Three fully isolated AC voltage inputs rated 10-1,000V AC (L-L) at 50/60Hz
Four isolated AC current inputs (see Current Inputs in Specifications)
Leakage current detection: residual current calculated via the fourth current input monitoring the neutral line, with configurable alerts and control thresholds
DC measurements
Three isolated DC voltage inputs from 10 to 820V DC, or up to 1,500V DC via an optional adapter
DC voltage accuracy: 0.2%
Four isolated DC current inputs up to 3,000A DC using SATEC U-HACS or Hall Effect sensors
DC current accuracy: 0.2%
DC power calculated from measured voltage and current
Embedded programmable controller
64 control setpoints with OR/AND logic and extensive triggers
Programmable thresholds and delays with relay control
Event-driven data recording with up to 16 triggering channels
Cross triggering between devices via Ethernet for synchronous event capture
Software support
Power Analysis Software (PAS) for configuration, data retrieval and waveform analysis
Expertpower client over Modbus/TCP to a remote or local (stand-alone) Expertpower server
eXpertConnect™ App for mobile configuration, readings and diagnostics
Communications
RS-485 serial port up to 115,200 bps: Modbus RTU/ASCII, DNP3.0, SNTP and IEC 60870-5-101
Two 10/100 Base-T Ethernet ports: Modbus/TCP, DNP3/TCP, IEC 60870-5-104 and IEC 61850, with up to 10 non-intrusive simultaneous connections per port
Infrared port (19,200 bps) with Modbus and DNP3 for local data exchange
USB 2.0 port (type C)
TCP notification client to a remote Modbus/TCP server, on events or periodically
Expansion modules and I/O: up to four modules side by side
Up to two expansion modules are self-energised
Three I/O modules require the auxiliary power supply module
Three daisy-chain slots for plug-in I/O and communication modules
Expansion modules and I/O: optional built-in I/O
Two optically isolated 24V DC dry contact inputs with 1 ms sampling and 1 pps time synchronisation
One solid state relay output for alarms, pulses and remote control
One universal analogue input (±1mA, 0-1mA, 0-20mA, 4-20mA)
Expansion modules and I/O: add-on modules
8 DI: dry contact or 24/48/125/250V wet inputs
4 RO: electromechanical (EMR) or solid state (SSR) relays
4 DI + 2 RO combination module
4 AO: isolated universal analogue outputs
Auxiliary power supply: 88-264V AC / 90-290V DC or 24V DC (9-36V DC)
Applications
Energy management and revenue metering
SCADA and substation automation
Industrial monitoring and power quality
Renewable energy
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
Voltage inputs
Operating range1
0-600V AC (L-N); 0-1,000V AC (L-L)
Direct DC voltage range2
10-820V DC
Input impedance
4MΩ
Burden at 400V
≤ 0.04VA
Burden at 120V
< 0.01VA
Isolation
4,000V AC for 1 min
Wire size
Up to 14 AWG (≤ 2.5 mm²)
1 Minimum value for accurate detection is 6V L-N and 10V L-L. 2 Measuring up to 1,500V DC is possible via an adapter.
Current inputs: 1A or 5A from CT secondary (standard)
Operating range
Continuous 10A RMS
Burden
< 0.2VA at In = 1A or 5A
Overload withstand
15A RMS continuous, 200A (20 × Imax) RMS for ½ second
Current inputs: optional inputs
DC
0-20mA input for DC Hall Effect sensors
HACS
0-20mA inputs for solid or split core SATEC High Accuracy Current Sensors
LPCT sensor interface (V/I)
Voltage input
(3.25/√3) V
Voltage input burden
200kΩ ±1%
Current input
225mV
Current input burden
> 20kΩ
Connector type
2 wires
Power supply
Rated input
57.7-277V AC at 50/60Hz; 48-290V DC
Tolerance
±15%
Burden
11VA AC, 6VA DC
Isolation
4,000V AC for 1 min
Wire size
Up to 14 AWG (≤ 1.5 mm²)
Built-in I/O (optional): digital inputs (2 DI)
Type
Dry contacts, internally wetted at 24V DC
Galvanic isolation
4,000V AC for 1 min
Internal power supply
24V DC
Scan time
1 ms
Connector type
Removable, 5 pins
Wire size
14 AWG (up to 1.5 mm²)
Terminal pitch
5 mm
Built-in I/O (optional): digital output (1 DO)
Type
Solid state relay rated 0.15A / 250V AC/DC, 1 contact (SPST Form A)
Galvanic isolation
4,000V AC for 1 min
Operate time
1 ms max.
Release time
0.25 ms max.
Update time
1 cycle
Connector type
Removable, 4 pins
Wire size
14 AWG (up to 1.5 mm²)
Built-in I/O (optional): analogue input (1 AI)
Type
Universal, -1mA to 20mA (configurable: ±1mA, 0-1mA, 0-20mA, 4-20mA)
Galvanic isolation
4,000V AC for 1 min
Scan time
1 ms
Accuracy
< 0.5% FS
Connector type
Removable, 5 pins
Wire size
14 AWG (up to 1.5 mm²)
Terminal pitch
5 mm
Add-on modules, digital I/O: digital inputs (8 DI)
Type
Dry contacts, internally wetted at 24V DC, or wet contact up to 250V DC
Emission per EN 55011/22 Class B and FCC Part 15 Class B
Environmental
IEC 60529: Protection
IEC 60068-2-1: Cold
IEC 60068-2-2: Dry Heat
IEC 60068-2-30: Damp Heat
IEC 60068-2-5: Solar Radiation
Accuracy
AS/IEC 62053-22:2003, Class 0.2S
IEC 62053-24:2014, Class 0.5S
ANSI C12.20-2015, Class 10 (0.2%)
Power quality
Designed to comply with EN 50160: Power Quality in European Electricity Supply Networks
IEC 61000-4-7: Harmonics and interharmonics measurement
IEC 61000-4-15: Flicker measurement
IEC 61000-4-30 Class A (Ed. 3.1): Power quality measurement methods
Safety and construction
IEC 61010, AS/IEC 62052-11* and IEC 61557-12
UL 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General Requirements, Edition 3, revision date 07/19/2019
CSA C22.2 No. 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General Requirements, Edition 3, revision date 11/2018
AC impulse insulation: meets AS/IEC 62052-11, 4,000V AC for 1 minute and 6kV/500Ω at 1.2/50 µs impulse
IEC 60068-2-6: Vibration (sinusoidal)
IEC 60068-2-27: Shock Test
IEC 60068-2-75: Hammer Test
* Meets standard requirements.
Ordering information
MODEL – CURRENT – CAL. FREQ. – POWER – BUILT-IN I/O – LANGUAGE – PROTOCOL
Model
PM335 panel-mount PQ analyser, Class S
PRO-PM335-PQ-S
EM235 DIN-rail PQ analyser, Class S
PRO-EM235-PQ-S
Transducer version PQ analyser, Class S
PRO-RPM035-PQ-S
PM335 panel-mount PQ analyser, Class A (Ed. 3.1)
PRO-PM335-PQ-A
EM235 DIN-rail PQ analyser, Class A (Ed. 3.1)
PRO-EM235-PQ-A
Transducer version PQ analyser, Class A (Ed. 3.1)
PRO-RPM035-PQ-A
Current inputs
5 Ampere
5A
1 Ampere
1A
5A split core remote HACS, 50/60Hz only
RS5
High Accuracy Current Sensors (HACS), 50/60Hz only
HACS
Pole top sensor interface, 0-10V (voltage and current)
PTS
Pole top sensor interface, 0-10V (voltage), current 5A
PTS-5
LPCT: dedicated low voltage interface for MV sensors
LPCT
3V AC inputs for Rogowski current clamps
FLEX
Calibration at frequency
50Hz
50HZ
60Hz
60HZ
Power supply
88-320V AC / 40-290V DC
ACDC
Built-in I/O
2 × DI (dry contact) + 1 × SSR output + 1 × universal AI (-1mA to 20mA)
IOS
Display language
English
EN
Optional protocols
IEC 61850 communication protocol
850
Expansion modules
Maximum of three I/O modules and one auxiliary power supply module per device.
I/O modules
4 relay outputs, 250V / 5A AC
EMR4
4 SSR outputs, 250V / 0.1A AC
SSR4
4 digital inputs (dry contact at 24V DC) + 2 SSR outputs
4DIOS-DRC
4 digital inputs (dry contact at 24V DC) + 2 EMR outputs
4DIOR-DRC
8 digital inputs, dry contact
DI8-DRC
8 digital inputs, 24, 48, 125 or 250V DC
DI8-24 / 48 / 125 / 250
4 analogue outputs, configurable range
4AO
Auxiliary power supply
AC/DC, 88-264V AC / 90-290V DC
AUX-ACDC
24V DC (9-36V DC)
AUX-24DC
An auxiliary power supply module is required when three I/O modules are fitted.