PM17x PRO · DATASHEET

PM17x PRO power quality analyser datasheet

Class A Power Quality Analysis and Class 0.2S Energy Metering.

Transcribed from the SATEC Australia datasheet TBV1.1, 9 September 2026 (PDF, 7 pages, 1070 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PM17x PRO Series brings power quality analysis, revenue-grade metering and embedded control together in one panel instrument. It suits substation and industrial automation, utility SCADA and commercial energy management, where one device has to replace several. Class 0.2S accuracy and Class A Ed. 3.1 power quality performance sit in the same enclosure.

Each meter is supplied with a three-row bright LED display or as a transducer version with no display. An extra-wide 10 to 1,000V AC line-to-line input rating and a fourth voltage input (Vref) widen the measurement range. Dual-port Ethernet, RS-485 and USB 2.0 Type C cover communications, with IEC 61850 Ed. 2, DNP3.0 and IEC 60870-5-101/104 support. A fourth current input enables residual and leakage current detection.

PM172 PRO: Power and revenue meter with power quality analysis and data logging

PM174 PRO: Class A Ed. 3.1 analyser reporting to the IEEE 1159 power quality standard

PM175 PRO: Class A Ed. 3.1 analyser reporting to the EN 50160 power quality standard

Main features

Feature capabilities

Class A Power Quality Recorder (PM174 and PM175 PRO)

  • Class A Ed. 3.1 measurement methods per IEC 61000-4-30
  • EN 50160 compliance statistics and event log (PM175 PRO)
  • IEEE 1159 power quality reporting (PM174 PRO)
  • Power quality event triggering with programmable limits
  • Flicker measurement per IEC 61000-4-15

Harmonic Analyser

  • Harmonics to the 63rd order for volts and amps per IEC 61000-4-7
  • THD for volts and amps, TDD, K-factor and interharmonics
  • Directional power harmonics and harmonic power factor
  • IEEE 519 harmonic analysis
  • Phasor diagrams and symmetrical components

Waveform Recording

  • 8 fast waveform recorders with 7-channel simultaneous capture (V1–V3, I1–I4)
  • Selectable AC sampling rate of 32, 64, 128 or 256 samples per cycle
  • 20 pre-fault cycles retained ahead of each trigger
  • Synchronised waveforms from multiple devices in a single plot
  • COMTRADE and PQDIF export through PAS software

Event and Data Recording

  • 16 data recorders with programmable periodic logs, triggered by any internal or external event
  • Event recorder for internal diagnostics, control events and I/O operations
  • 32 digital counters for external pulses and internal events
  • 16 programmable timers from half a cycle to 24 hours
  • 16GB memory for long-term waveform and data recording

Billing and TOU Energy Meter

  • Class 0.2S four-quadrant active and reactive polyphase static meter to AS/IEC 62053-22 and ANSI C12.20 Class 0.2
  • Time-of-Use with 16 summary totalisation registers plus TOU energy and demand registers
  • Accumulation of energy pulses from external wattmeters
  • Block and sliding demand with up to 64 energy sources
  • Demand meter for amps, volts and harmonic demands

Embedded Programmable Controller

  • 64 control setpoints with OR/AND logic and extensive trigger options
  • Programmable thresholds and delays with relay control
  • Event-driven data recording
  • Cross-triggering between multiple devices over Ethernet for synchronous event capture, across up to sixteen triggering channels

AC Measurement

  • Fully isolated AC inputs for direct connection to AC feeders
  • Four isolated voltage inputs rated 10 to 1,000V AC line-to-line at 50/60 Hz
  • Four isolated current inputs with 1A or 5A CT secondary, HACS, LPCT-D or RS5 options
  • Three-phase power meter measuring true RMS volts, amps, powers, power factors, unbalance and neutral current
  • Fourth voltage input (Vref) rated 0 to 300V AC/DC

Leakage and Residual Current

  • Accurate residual current calculation through a fourth current input monitoring the neutral line
  • Alerts and control thresholds configurable in response to detected leakage current

Built-in I/O

  • 2 optically isolated digital inputs, 24V DC dry contact, with programmable debounce from 1 ms to 1 second
  • 1 solid state relay output with unlatched, latched and pulse operation plus fail-safe alarm notification
  • 1 optically isolated analogue input of configurable range (±1mA, 0–1mA, 0–20mA, 4–20mA)
  • IRIG-B time synchronisation input

Time Synchronisation

  • 1 µs satellite-synchronised clock accuracy via IRIG-B or PTP v2 (IEEE 1588)
  • SNTP time synchronisation
  • 1 pps synchronisation via digital input
  • Internal real-time clock with three-year battery retention

Communications

  • RS-485 serial port to 115,200 bps with Modbus RTU/ASCII, DNP3.0 and IEC 60870-5-101
  • 2 × Ethernet 10/100 Base-T ports supporting Modbus/TCP, DNP3.0/TCP, IEC 60870-5-104, PTP and IEC 61850
  • Up to 10 non-intrusive simultaneous connections per Ethernet port
  • USB 2.0 port (Type C)
  • TCP notification client reporting to a remote Modbus/TCP server on event or on a time basis

Software Support and Firmware

  • Power Analysis Software (PAS) for configuration, data acquisition, waveforms, phasors and harmonics
  • Expertpower™ web platform for energy management with no client software to install
  • eXpertConnect™ App for mobile connection to the meter covering configuration, readings and diagnostics
  • Expertpower client for Modbus/TCP communication with a remote or local stand-alone Expertpower server
  • Firmware upgrade over a serial or Ethernet port

Display Options

  • Three-row, 7-segment bright LED display of two 4-character rows plus one 6-character row
  • Transducer version supplied with no display
  • Load bar graph indication

Applications

  • Energy management and revenue metering
  • SCADA-ready substation automation
  • Industrial monitoring
  • Renewable energy generation

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Voltage inputs
Operating range10–1,000V AC (L-L) @ 50/60 Hz
Input impedance4MΩ
Burden @ 400V≤ 0.04VA
Burden @ 120V< 0.01VA
Isolation4,000V AC @ 1 min
Wire sizeUp to 14 AWG (≤ 2.5 mm²)
4th voltage (Vref) and LPVT
Vref operating range0–300V AC/DC
LPVT nominal voltage (PM172 PRO only)0.5–5V
LPVT input impedance **2MΩ / 50 pF
LPVT interface **RJ45

** According to IEC 61869-11.

Current input options
1A / 5A from CT secondary (standard)Continuous 10A RMS · burden < 0.2VA @ In=1A or 5A · overload withstand 15A RMS continuous, 200A (20 × Imax) RMS for ½ second
HACS0–20mA inputs for solid-core or split-core SATEC High Accuracy Current Sensors
LPCT-D rating80A / 150 mV @ 50 Hz · 80A / 180 mV @ 60 Hz · RJ45 interface ** · 2MΩ / 50 pF **
LPCT-D max primary650A
RS5 (5A HACS version)Nominal input 2.5 mA · maximum current 5 mA at 200% overload · dedicated to HACS CS05S / RS5 (HX0140)

** According to IEC 61869-11.

Digital inputs (2 DI)
TypeDry contacts, internally wetted @ 24V DC
Internal power supply24V DC
Galvanic isolation4,000V AC @ 1 min
Scan time1 ms
ConnectorRemovable, 5 pins · 5 mm terminal pitch
Wire sizeUp to 14 AWG (≤ 1.5 mm²)
Digital output and analogue input
Relay ratingSolid state relay, 0.15A / 250V AC-DC, 1 contact (SPST Form A)
Galvanic isolation4,000V AC @ 1 min
Operate / release time1 ms max / 0.25 ms max
Update time1 cycle
Analogue input rangeUniversal −1mA to 20mA, configurable ±1mA, 0–1mA, 0–20mA, 4–20mA
Analogue scan time1 ms
ConnectorRemovable, 4 pins (DO), 5 pins (AI)
Power supply
Rated input100–277V AC @ 50/60 Hz · 100–290V DC
Tolerance±15%
Burden11VA @ V AC · 6VA @ V DC
Isolation4,000V AC @ 1 min
Wire sizeUp to 14 AWG (≤ 2.5 mm²)
Auxiliary power supply (built-in)
Rated input9–36V DC (24V)
Output7W
Galvanic isolation4,000V AC @ 1 min · 4kV
Terminal pitch5 mm
Wire sizeUp to 14 AWG (1.5 mm²)
Serial communication
PortRS-485, optically isolated
Baud rateUp to 115,200 bps
Isolation4,000V AC @ 1 min
ProtocolsModbus RTU · DNP3 · IEC 60870-5-101
Ethernet ports (dual)
Type2 × transformer-isolated 10/100 Base-T, RJ45
ProtocolsModbus/TCP (502) · DNP3/TCP (20000) · IEC 60870-5-104 (2404) · IEC 61850 (102)
Simultaneous connections10 per port (5 Modbus/TCP + 5 DNP3/TCP)
Isolation4,000V AC @ 1 min
USB port
TypeUSB 2.0, Type C
IRIG-B
PortOptically isolated IRIG-B input for GPS time synchronisation
Recommended cable51Ω low loss RG58A/U (Belden 8219 or equivalent), BNC connector
Recommended generatorMasterclock GPS-200A GPS time code generator
Real-time clock and log memory
Clock accuracyTypical error ±15 seconds per month, under 5 minutes per year @ 25°C
Battery retentionThree years
Log memory16GB for long-term waveform and data recording
Display options
StandardThree-row 7-segment LED, two 4-character rows plus one 6-character row
Transducer versionNo display (RPM17x PRO model)
Environmental conditions
Operating temperature−40°C to +70°C (−40°F to 158°F)
Display operating temp.−20°C to +70°C (−4°F to 158°F)
Storage temperature−40°C to +85°C (−40°F to 185°F)
Humidity0 to 95% RH, non-condensing
Degree of protectionIP51
Construction
Weight1.23 kg (2.7 lb)
Dimensions [H×W×D]114 × 127 × 127 mm
Panel cutoutDual installation: 4-inch round or 92 × 92 mm square
Materials
Case enclosurePC/ABS blend plastic
Display bodyPC/ABS blend plastic
Front panelPC plastic
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
LabelsPolyester film (UL94-V0)

Standards compliance

Power Quality

  • IEC 61000-4-30 Ed. 3.1: power quality measurement methods, Class A
  • IEC 61000-4-7: general guide on harmonics and interharmonics measurement and instrumentation
  • IEC 61000-4-15: flickermeter
  • IEC 62586-1: product and performance requirements for power quality meters
  • IEC 62586-2: detailed testing procedures verifying classification under IEC 61000-4-30
  • EN 50160: voltage characteristics of electricity supplied by public networks
  • IEEE 1159: recommended practice for monitoring electric power quality

Accuracy

  • Complies with AS/IEC 62053-22:2003, Class 0.2S
  • Complies with IEC 62053-24:2014, Class 0.5S
  • Meets ANSI C12.20-2015, Class 10 (0.2%)

Environmental

  • IEC 60529: degree of protection
  • IEC 60068-2-1: cold
  • IEC 60068-2-2: dry heat
  • IEC 60068-2-30: damp heat
  • IEC 60068-2-5: solar radiation

Electromagnetic Immunity

  • IEC 62052-11 and CLC/TR 50579: conducted disturbances 2 to 150kHz
  • IEEE C62.41 and C37.90.1
  • IEC 61000-6-2
  • IEC 61000-4-2 level 3: electrostatic discharge
  • IEC 61000-4-3 level 3: radiated electromagnetic RF fields
  • IEC 61000-4-4 level 3: electrical fast transient
  • IEC 61000-4-5 level 3: surge
  • IEC 61000-4-6 level 3: conducted radio frequency
  • IEC 61000-4-8: power frequency magnetic field
  • ANSI/IEEE C37.90.1: fast transient SWC

Electromagnetic Emission

  • IEC 61000-6-4: radiated and conducted Class B
  • IEC CISPR 22: radiated and conducted Class B
  • Emission per EN 55011/22 Class B and FCC Part 15 Class B

Safety and Construction

  • IEC 61010, IEC 62052-11 and IEC 61557-12
  • UL 61010-1 Edition 3, safety requirements for electrical equipment for measurement, control and laboratory use
  • CSA C22.2 No. 61010-1 Edition 3
  • AC impulse insulation meets IEC 62052-11: 4,000V AC for 1 minute, 6kV/500Ω @ 1.2/50 µs impulse
  • IEC 60068-2-6: vibration (sinusoidal)
  • IEC 60068-2-27: shock test
  • IEC 60068-2-75: hammer test

Ordering information

MODEL – CURRENT – CALIBRATION – PROTOCOL – MODULE – AUX POWER

Model
PM172 panel-mount power and revenue meterPRO-PM172
PM174 panel-mount Class A analyser (IEEE 1159)PRO-PM174
PM175 panel-mount Class A analyser (EN 50160)PRO-PM175
Transducer version, supplied with no displayPRO-RPM17x
Current inputs
5 Ampere5A
1 Ampere1A
High Accuracy Current Sensors (HACS), 50/60 Hz. Order 3 × HACS separatelyHACS
5A split-core remote HACS, 50/60 Hz onlyRS5
LPCT sensor inputs (RJ45) to 650A primary, 80A/150 mV at 50 HzLPCT-D
Calibration frequency
50 Hz50HZ
60 Hz60HZ
Communication protocol
Modbus, DNP3.0 and IEC 60870-5-101/104 (standard)—
IEC 61850 Ed. 2 ‡850
Optional built-in module (max. 1 per device)
4 relay outputs, 250V / 5A ACEMR4
4 SSR outputs, 250V / 0.1A ACSSR4
4 digital inputs (dry contact 24V DC) plus 2 SSR outputs4DIOS-DRC
4 digital inputs (dry contact 24V DC) plus 2 EMR outputs4DIOR-DRC
8 digital inputs, dry contactDI8-DRC
8 digital inputs, 24 / 48 / 125 / 250V DCDI8-24, 48, 125, 250V
4 analogue outputs, configurable range4AO
Auxiliary power supply
9–36V DC (24V)AUX-24DC

‡ Confirm the IEC 61850 option code with SATEC Australia when ordering.