Class A Power Quality Analysis and Class 0.2S Energy Metering.
Transcribed from the SATEC Australia datasheet TBV1.1, 9 September 2026 (PDF, 7 pages, 1070 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The PM17x PRO Series brings power quality analysis, revenue-grade metering and embedded control together in one panel instrument. It suits substation and industrial automation, utility SCADA and commercial energy management, where one device has to replace several. Class 0.2S accuracy and Class A Ed. 3.1 power quality performance sit in the same enclosure.
Each meter is supplied with a three-row bright LED display or as a transducer version with no display. An extra-wide 10 to 1,000V AC line-to-line input rating and a fourth voltage input (Vref) widen the measurement range. Dual-port Ethernet, RS-485 and USB 2.0 Type C cover communications, with IEC 61850 Ed. 2, DNP3.0 and IEC 60870-5-101/104 support. A fourth current input enables residual and leakage current detection.
PM172 PRO: Power and revenue meter with power quality analysis and data logging
PM174 PRO: Class A Ed. 3.1 analyser reporting to the IEEE 1159 power quality standard
PM175 PRO: Class A Ed. 3.1 analyser reporting to the EN 50160 power quality standard
Main features
Class 0.2S four-quadrant active and reactive energy metering to AS/IEC 62053-22 and ANSI C12.20 Class 10
Class A Ed. 3.1 power quality analyser per IEC 61000-4-30, tested to IEC 62586-1 and IEC 62586-2
EN 50160 and IEEE 1159 compliance statistics with IEC 61000-4-7 harmonic analysis to the 63rd order
Extra-wide voltage rating of 10 to 1,000V AC line-to-line plus a fourth voltage input (Vref)
Four isolated current inputs, the fourth enabling residual and leakage current detection
Dual-port 10/100 Base-T Ethernet, RS-485 and USB 2.0 Type C with IEC 61850 Ed. 2 support
1 µs time synchronisation via IRIG-B or PTP v2 (IEEE 1588)
16GB memory for long-term waveform and data recording
Feature capabilities
Class A Power Quality Recorder (PM174 and PM175 PRO)
Class A Ed. 3.1 measurement methods per IEC 61000-4-30
EN 50160 compliance statistics and event log (PM175 PRO)
IEEE 1159 power quality reporting (PM174 PRO)
Power quality event triggering with programmable limits
Flicker measurement per IEC 61000-4-15
Harmonic Analyser
Harmonics to the 63rd order for volts and amps per IEC 61000-4-7
THD for volts and amps, TDD, K-factor and interharmonics
Directional power harmonics and harmonic power factor
IEEE 519 harmonic analysis
Phasor diagrams and symmetrical components
Waveform Recording
8 fast waveform recorders with 7-channel simultaneous capture (V1–V3, I1–I4)
Selectable AC sampling rate of 32, 64, 128 or 256 samples per cycle
20 pre-fault cycles retained ahead of each trigger
Synchronised waveforms from multiple devices in a single plot
COMTRADE and PQDIF export through PAS software
Event and Data Recording
16 data recorders with programmable periodic logs, triggered by any internal or external event
Event recorder for internal diagnostics, control events and I/O operations
32 digital counters for external pulses and internal events
16 programmable timers from half a cycle to 24 hours
16GB memory for long-term waveform and data recording
Billing and TOU Energy Meter
Class 0.2S four-quadrant active and reactive polyphase static meter to AS/IEC 62053-22 and ANSI C12.20 Class 0.2
Time-of-Use with 16 summary totalisation registers plus TOU energy and demand registers
Accumulation of energy pulses from external wattmeters
Block and sliding demand with up to 64 energy sources
Demand meter for amps, volts and harmonic demands
Embedded Programmable Controller
64 control setpoints with OR/AND logic and extensive trigger options
Programmable thresholds and delays with relay control
Event-driven data recording
Cross-triggering between multiple devices over Ethernet for synchronous event capture, across up to sixteen triggering channels
AC Measurement
Fully isolated AC inputs for direct connection to AC feeders
Four isolated voltage inputs rated 10 to 1,000V AC line-to-line at 50/60 Hz
Four isolated current inputs with 1A or 5A CT secondary, HACS, LPCT-D or RS5 options
Three-phase power meter measuring true RMS volts, amps, powers, power factors, unbalance and neutral current
Fourth voltage input (Vref) rated 0 to 300V AC/DC
Leakage and Residual Current
Accurate residual current calculation through a fourth current input monitoring the neutral line
Alerts and control thresholds configurable in response to detected leakage current
Built-in I/O
2 optically isolated digital inputs, 24V DC dry contact, with programmable debounce from 1 ms to 1 second
1 solid state relay output with unlatched, latched and pulse operation plus fail-safe alarm notification
1 optically isolated analogue input of configurable range (±1mA, 0–1mA, 0–20mA, 4–20mA)
IRIG-B time synchronisation input
Time Synchronisation
1 µs satellite-synchronised clock accuracy via IRIG-B or PTP v2 (IEEE 1588)
SNTP time synchronisation
1 pps synchronisation via digital input
Internal real-time clock with three-year battery retention
Communications
RS-485 serial port to 115,200 bps with Modbus RTU/ASCII, DNP3.0 and IEC 60870-5-101