PM130E DC · DATASHEET

PM130E DC energy meter datasheet

Multi-function direct current (DC) energy meter for substations, data centres and renewables.

Transcribed from the SATEC Australia datasheet TBV1.1, 17 September 2026 (PDF, 8 pages, 391 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PM130E DC is a multi-function direct current (DC) energy meter designed for single channel DC metering. Measuring DC volts, amps, power, energy and demand to Class 0.5/1.0 accuracy per AS/IEC 62053-41, it is built for utility substations, data centres, renewable energy systems, SCADA integration and building management systems.

Current is measured via a DC shunt (single-channel), with direct voltage measurement to 670 V DC and extended ranges to 1500 V DC — or higher on application — using the SATEC Voltage Ratio Module (VRM). Every unit ships with a standard RS-485 port, with optional Ethernet, 4G modem and PROFIBUS interfaces, up to 16 digital/analogue I/O, dual 92×92 mm / 4-inch round panel mounting and an optional DIN-rail mounting kit.

Current input options

Main features

Feature capabilities

DC energy metering

  • DC volts
  • DC amps
  • DC power
  • DC energy
  • DC ampere demand
  • DC volt demand

Billing / TOU energy meter (PM130E-DCC only)

  • Total and per-channel energy measurements
  • Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 day types, 8 tariff changes per day
  • Easy programmable tariff calendar schedule
  • Automatic daily energy and maximum demand profile log for total and tariff registers

Programmable logical controller

  • Embedded programmable controller
  • 16 control setpoints — programmable thresholds and delays
  • Optional relay output control and alarming (load control)
  • 1-cycle response time (20 ms @ 50 Hz)

Event and data recording

  • Non-volatile memory: 48 days for 2 daily TOU records, half-hourly writing of 4 parameters, over 100 events recorded during the period
  • Event recorder for internal diagnostic events and setup changes
  • Two data recorders — periodic data logs plus automatic daily energy and max-demand profile log

Display

  • 3-row (2×4 characters + 1×5 characters) bright LED display, adjustable brightness and update rate
  • Auto-scroll with adjustable page exposition time; auto-return to a default page
  • LED bar graph showing percent load against a user-definable nominal load current

Real-time clock

  • Standard meter clock: non-backed, ~1 min/month error @ 25°C, 30-second retention
  • TOU module clock: battery-backed, ~7 s/month error @ 25°C (±2.5 ppm), 36-month retention

Voltage input options

  • Direct measurement: 0–670 V DC
  • Extended range to 1500 V DC via the SATEC Voltage Ratio Module (VRM)
  • Ranges above 1500 V DC on application — measuring up to 3000 V DC

Current options

  • DC shunts — 50, 60, 75 or 100 mV (shunt dependent)

Digital and analogue I/O

  • TOD (TOU+4DI) — 4 digital inputs, 1 ms scan, battery-backed RTC; last 5 input-change events with timestamps
  • DIOR — 4 digital inputs, 2 relay outputs, 1-cycle update; unlatched, latched, pulse and KYZ; solid-state or electromechanical
  • 12DIOR — 12 digital inputs, 4 relay outputs, optional Ethernet or additional RS-485 port
  • 4AO — 4 optically isolated analogue outputs (0–20 mA / 4–20 mA / 0–1 mA / ±1 mA), 1-cycle update
  • 8DI — 8 digital inputs, 1 ms scan time

Communication

  • On-board: standard 2-wire RS-485
  • Optional: Ethernet (10/100Base-T), 4G modem, multipurpose RS-232/422/485, PROFIBUS
  • Client (Modbus/TCP over Ethernet or 4G): TCP notification client for event/periodic reports to a remote server; Expertpower client on a subscription basis
  • Protocols: Modbus RTU, SATEC ASCII, DNP 3.0 (Level 2), IEC 60870-5-101 (standard), IEC 60870-5-104 (requires Ethernet)

Unique design and meter security

  • Pass-through CT connection for minimal burden
  • Built-in auxiliary terminal for loose CT wires
  • Dual panel mounting — 92×92 mm square or 4-inch round cutout
  • Password security protecting meter setups and accumulated data from unauthorised changes

Software support and firmware

  • Power Analysis Software (PAS) — SATEC’s free configuration and data-acquisition tool
  • Expertpower — SATEC’s internet-based energy management platform (subscription)
  • eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics
  • Firmware upgrade via a serial or Ethernet port

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Environmental conditions
Operating temperature−30°C to 60°C (−22°F to 140°F)
Storage temperature−40°C to 85°C (−40°F to 185°F)
Humidity0–95% RH, non-condensing
Construction and materials
Weight0.70 kg (1.54 lb)
Dimensions [H×W×D]114×114×109 mm (4.5×4.5×4.3″)
Case enclosurePC/ABS blend plastic
Front panelPC plastic
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
Packaging caseCarton & Stratocell® (PE foam) brackets
LabelsPolyester film (UL94-V0)
Display
TypeHigh-brightness 7-segment LED, two 4-digit + one 5-digit window
Bar graph3-colour LED, 40–110% load
Keypad6 push buttons
Voltage inputs
Nominal voltage (L-N)0–670 V DC · use VRM above 670 V DC*
Over-voltage withstand1000VAC continuous, 2000VAC for 1 s
Input impedance1 MΩ
Wire sizeUp to 12 AWG (3.5 mm²)

* Measuring up to 3000 V DC on application.

Current inputs
TypeDC shunts
Wire size12 AWG (3.5 mm²)
Galvanic isolation3500VAC
Power supply
120/230V AC-DC option85–265V AC 50/60/400 Hz, 88–290VDC · 9VA burden · 2500VAC isolation (input to ground)
12VDC option9.5–18V DC · 4VA burden · 1500VDC isolation
24/48VDC option18.5–58VDC · 4VA burden · 1500VDC isolation · up to 12 AWG (3.5 mm²) wire
Real-time clock
Standard meter clockNon-backed · ~1 min/month error @ 25°C · 30 s retention
TOU module clockBattery-backed · ~7 s/month error @ 25°C (±2.5 ppm) · 36-month retention
Optional relay outputs
Electromechanical (4DI/DO or 12DI/DO)2 or 4 relays, 5A/250VAC or 5A/30VDC, 1 contact (SPST Form A)
Galvanic isolation3000VAC (contacts–coil) · 750VAC (open contacts)
Operate / release time10 ms max / 5 ms max
Wire size14 AWG (1.5 mm²)
Solid-state (4DI/2DO)2 relays, 0.15A/250V AC/DC, 1 contact (SPST Form A)
Galvanic isolation3750VAC 1 min
Operate / release time1 ms max / 0.25 ms max
Optional digital inputs
Type4 or 12 inputs (4DI/2DO or 12DI/4DO module); dry contact, internally wetted @ 24VDC, or wet contact @ 250VDC (12DI/4DO only)
SensitivityOpen >100 kΩ · closed <100 Ω
Galvanic isolation3750VAC 1 min
Scan time1 ms
Optional analogue outputs
Ranges (on order)±1 mA · 0–20 mA · 4–20 mA · 0–1 mA
Isolation2500VAC 1 min
Accuracy0.5% FS
Update time1 cycle
Communication ports
COM1 — RS-485 (built-in)Optically isolated
Isolation / baud3000VAC 1 min · up to 115.2 kbps
ProtocolsModbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101
COM2 (optional module): EthernetTransformer-isolated 10/100BaseT · Modbus/TCP (502), IEC 60870-5-104, DNP3/TCP (20000) · 4 simultaneous connections
COM2 (optional module): Cellular portModbus/TCP (502), DNP3/TCP (20000) · SMA connector
COM2 (optional module): PROFIBUS DP (IEC 61158)RS-485 isolated · 9600 bit/s–12 Mbit/s auto-detect · 32 bytes in/out
COM2 (optional module): RS-232/422/485Isolated · up to 115.2 kbps · Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101

The printed sub-heading row 'COM2 (optional module)' is joined into the labels of the four rows under it.

Standards compliance

Accuracy

  • Complies with AS/IEC 62053-41, Class 0.5/1.0 — accuracy subject to DC shunt input
  • Meets ANSI C12.20-1998, Class 10, 0.5%
  • Complies with IEC 61557-12 (PMD): Total DC Power 0.5 · Total DC Energy 0.5 · DC Current 0.05 · DC Voltage 0.05

Electromagnetic immunity

  • Complies with IEC 61000-6-2
  • IEC 61000-4-2 level 3 — electrostatic discharge
  • IEC 61000-4-3 level 3 — radiated electromagnetic RF fields
  • IEC 61000-4-4 level 3 — electrical fast transient
  • IEC 61000-4-5 level 3 — surge
  • IEC 61000-4-6 level 3 — conducted radio frequency
  • IEC 61000-4-8 — power-frequency magnetic field
  • Meets ANSI/IEEE C37.90.1 — fast transient SWC

Electromagnetic emission

  • Complies with IEC 61000-6-4 — radiated/conducted Class A
  • Complies with IEC CISPR 22 — radiated/conducted Class A

Safety and construction

  • Meets IEC 61010-1:2006

AC and impulse insulation

  • Complies with IEC 62052-11 — 2500VAC for 1 minute
  • 6kV/500Ω @ 1.2/50 μs impulse

Ordering information

MODEL – CURRENT – DISPLAY – POWER – PROTOCOL – MOUNTING – TEST/CERT

Model
DC energy power versionPM130E-DCC
Current inputs
DC shuntRS5
Display resolution
Low resolution — 1A, 1V—
High resolution — 0.01A, 0.1VH
Power supply
85–265V AC & 85–290V DCACDC
9.5–18V DC1DC
18.5–58V DC (24VDC, 48VDC)23DC
Communication protocol
Modbus and DNP 3.0—
Modbus and IEC 60870-5-101/104†870
Mounting
Panel mount (standard)—
DIN rail mountingDIN
Testing
Full functional test, calibration at various work loads & detailed test report—

† –104 requires Ethernet — does not work over a cellular network.

Expansion modules

Max. 1 per instrument, order separately.

Expansion module
4 Analogue Outputs: ±1mA / 0–20mA / 0–1mA / 4–20mA / 0–3mA / ±3mA / 0–5mA / ±5mAAO1–AO8
Ethernet (TCP/IP)ETH
PROFIBUSPRO
RS232/422/485RS232
4G Modem** — G=Europe, V=Verizon (US), A=AT&T (US), T=Telstra (AUS)T4x
4 Digital Inputs / 2 Relay Outputs, 250V/5A ACDIOR
4 Digital Inputs / 2 SSR Outputs, 250V/0.1A ACDIOS
TOU + 4 Digital Inputs (RTC battery)TOD
8 Digital Inputs (dry contact)8DI
12 Digital Inputs / 4 Relay Outputs, 250V/5A AC12DIOR
12DIOR digital input rating — DRC, 48V, 125V or 250VDRC / 48V / 125V / 250V
12DIOR communication port — none, RS-485 or Ethernet— / 485 / ETH

** Does not support the 870 protocol; supplied with a bendable antenna.