PM130E DC · DATASHEET
PM130E DC energy meter datasheet Multi-function direct current (DC) energy meter for substations, data centres and renewables.
Transcribed from the SATEC Australia datasheet TBV1.1, 17 September 2026 (PDF, 8 pages, 391 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form .
Overview Current input options Main features Feature capabilities Specifications Standards compliance Ordering information Downloads and related Overview The PM130E DC is a multi-function direct current (DC) energy meter designed for single channel DC metering. Measuring DC volts, amps, power, energy and demand to Class 0.5/1.0 accuracy per AS/IEC 62053-41, it is built for utility substations, data centres, renewable energy systems, SCADA integration and building management systems.
Current is measured via a DC shunt (single-channel), with direct voltage measurement to 670 V DC and extended ranges to 1500 V DC — or higher on application — using the SATEC Voltage Ratio Module (VRM). Every unit ships with a standard RS-485 port, with optional Ethernet, 4G modem and PROFIBUS interfaces, up to 16 digital/analogue I/O, dual 92×92 mm / 4-inch round panel mounting and an optional DIN-rail mounting kit.
Main features Accuracy: Class 0.5/1.0 per AS/IEC 62053-41 Communication: built-in RS-485; optional Ethernet, 4G modem, PROFIBUS Open protocols: Modbus RTU, DNP3.0, IEC 60870-5-101/104 Digital and analogue I/O modules: up to 16 I/O Dual mounting: suitable for 4-inch round and 92×92 mm square cutouts DIN-rail mounting option LED bar-graph: displays load as a percentage of nominal current Non-volatile event and data recording (48 days) Feature capabilities DC energy metering DC volts DC amps DC power DC energy DC ampere demand DC volt demand Billing / TOU energy meter (PM130E-DCC only) Total and per-channel energy measurements Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 day types, 8 tariff changes per day Easy programmable tariff calendar schedule Automatic daily energy and maximum demand profile log for total and tariff registers Programmable logical controller Embedded programmable controller 16 control setpoints — programmable thresholds and delays Optional relay output control and alarming (load control) 1-cycle response time (20 ms @ 50 Hz) Event and data recording Non-volatile memory: 48 days for 2 daily TOU records, half-hourly writing of 4 parameters, over 100 events recorded during the period Event recorder for internal diagnostic events and setup changes Two data recorders — periodic data logs plus automatic daily energy and max-demand profile log Display 3-row (2×4 characters + 1×5 characters) bright LED display, adjustable brightness and update rate Auto-scroll with adjustable page exposition time; auto-return to a default page LED bar graph showing percent load against a user-definable nominal load current Real-time clock Standard meter clock: non-backed, ~1 min/month error @ 25°C, 30-second retention TOU module clock: battery-backed, ~7 s/month error @ 25°C (±2.5 ppm), 36-month retention Voltage input options Direct measurement: 0–670 V DC Extended range to 1500 V DC via the SATEC Voltage Ratio Module (VRM) Ranges above 1500 V DC on application — measuring up to 3000 V DC Current options DC shunts — 50, 60, 75 or 100 mV (shunt dependent) Digital and analogue I/O TOD (TOU+4DI) — 4 digital inputs, 1 ms scan, battery-backed RTC; last 5 input-change events with timestamps DIOR — 4 digital inputs, 2 relay outputs, 1-cycle update; unlatched, latched, pulse and KYZ; solid-state or electromechanical 12DIOR — 12 digital inputs, 4 relay outputs, optional Ethernet or additional RS-485 port 4AO — 4 optically isolated analogue outputs (0–20 mA / 4–20 mA / 0–1 mA / ±1 mA), 1-cycle update 8DI — 8 digital inputs, 1 ms scan time Communication On-board: standard 2-wire RS-485 Optional: Ethernet (10/100Base-T), 4G modem, multipurpose RS-232/422/485, PROFIBUS Client (Modbus/TCP over Ethernet or 4G): TCP notification client for event/periodic reports to a remote server; Expertpower client on a subscription basis Protocols: Modbus RTU, SATEC ASCII, DNP 3.0 (Level 2), IEC 60870-5-101 (standard), IEC 60870-5-104 (requires Ethernet) Unique design and meter security Pass-through CT connection for minimal burden Built-in auxiliary terminal for loose CT wires Dual panel mounting — 92×92 mm square or 4-inch round cutout Password security protecting meter setups and accumulated data from unauthorised changes Software support and firmware Power Analysis Software (PAS) — SATEC’s free configuration and data-acquisition tool Expertpower — SATEC’s internet-based energy management platform (subscription) eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics Firmware upgrade via a serial or Ethernet port Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications Environmental conditions Operating temperature −30°C to 60°C (−22°F to 140°F) Storage temperature −40°C to 85°C (−40°F to 185°F) Humidity 0–95% RH, non-condensing
Construction and materials Weight 0.70 kg (1.54 lb) Dimensions [H×W×D] 114×114×109 mm (4.5×4.5×4.3″) Case enclosure PC/ABS blend plastic Front panel PC plastic PCB FR4 (UL94-V0) Terminals PBT (UL94-V0) Plug-in connectors Polyamide PA6.6 (UL94-V0) Packaging case Carton & Stratocell® (PE foam) brackets Labels Polyester film (UL94-V0)
Display Type High-brightness 7-segment LED, two 4-digit + one 5-digit window Bar graph 3-colour LED, 40–110% load Keypad 6 push buttons
Voltage inputs Nominal voltage (L-N) 0–670 V DC · use VRM above 670 V DC* Over-voltage withstand 1000VAC continuous, 2000VAC for 1 s Input impedance 1 MΩ Wire size Up to 12 AWG (3.5 mm²)
* Measuring up to 3000 V DC on application.
Current inputs Type DC shunts Wire size 12 AWG (3.5 mm²) Galvanic isolation 3500VAC
Power supply 120/230V AC-DC option 85–265V AC 50/60/400 Hz, 88–290VDC · 9VA burden · 2500VAC isolation (input to ground) 12VDC option 9.5–18V DC · 4VA burden · 1500VDC isolation 24/48VDC option 18.5–58VDC · 4VA burden · 1500VDC isolation · up to 12 AWG (3.5 mm²) wire
Real-time clock Standard meter clock Non-backed · ~1 min/month error @ 25°C · 30 s retention TOU module clock Battery-backed · ~7 s/month error @ 25°C (±2.5 ppm) · 36-month retention
Optional relay outputs Electromechanical (4DI/DO or 12DI/DO) 2 or 4 relays, 5A/250VAC or 5A/30VDC, 1 contact (SPST Form A) Galvanic isolation 3000VAC (contacts–coil) · 750VAC (open contacts) Operate / release time 10 ms max / 5 ms max Wire size 14 AWG (1.5 mm²) Solid-state (4DI/2DO) 2 relays, 0.15A/250V AC/DC, 1 contact (SPST Form A) Galvanic isolation 3750VAC 1 min Operate / release time 1 ms max / 0.25 ms max
Optional digital inputs Type 4 or 12 inputs (4DI/2DO or 12DI/4DO module); dry contact, internally wetted @ 24VDC, or wet contact @ 250VDC (12DI/4DO only) Sensitivity Open >100 kΩ · closed <100 Ω Galvanic isolation 3750VAC 1 min Scan time 1 ms
Optional analogue outputs Ranges (on order) ±1 mA · 0–20 mA · 4–20 mA · 0–1 mA Isolation 2500VAC 1 min Accuracy 0.5% FS Update time 1 cycle
Communication ports COM1 — RS-485 (built-in) Optically isolated Isolation / baud 3000VAC 1 min · up to 115.2 kbps Protocols Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101 COM2 (optional module): Ethernet Transformer-isolated 10/100BaseT · Modbus/TCP (502), IEC 60870-5-104, DNP3/TCP (20000) · 4 simultaneous connections COM2 (optional module): Cellular port Modbus/TCP (502), DNP3/TCP (20000) · SMA connector COM2 (optional module): PROFIBUS DP (IEC 61158) RS-485 isolated · 9600 bit/s–12 Mbit/s auto-detect · 32 bytes in/out COM2 (optional module): RS-232/422/485 Isolated · up to 115.2 kbps · Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101
The printed sub-heading row 'COM2 (optional module)' is joined into the labels of the four rows under it.
Standards compliance Accuracy Complies with AS/IEC 62053-41, Class 0.5/1.0 — accuracy subject to DC shunt input Meets ANSI C12.20-1998, Class 10, 0.5% Complies with IEC 61557-12 (PMD): Total DC Power 0.5 · Total DC Energy 0.5 · DC Current 0.05 · DC Voltage 0.05 Electromagnetic immunity Complies with IEC 61000-6-2 IEC 61000-4-2 level 3 — electrostatic discharge IEC 61000-4-3 level 3 — radiated electromagnetic RF fields IEC 61000-4-4 level 3 — electrical fast transient IEC 61000-4-5 level 3 — surge IEC 61000-4-6 level 3 — conducted radio frequency IEC 61000-4-8 — power-frequency magnetic field Meets ANSI/IEEE C37.90.1 — fast transient SWC Electromagnetic emission Complies with IEC 61000-6-4 — radiated/conducted Class A Complies with IEC CISPR 22 — radiated/conducted Class A AC and impulse insulation Complies with IEC 62052-11 — 2500VAC for 1 minute 6kV/500Ω @ 1.2/50 μs impulse Ordering information MODEL – CURRENT – DISPLAY – POWER – PROTOCOL – MOUNTING – TEST/CERT
Model DC energy power version PM130E-DCC
Current inputs DC shunt RS5
Display resolution Low resolution — 1A, 1V — High resolution — 0.01A, 0.1V H
Power supply 85–265V AC & 85–290V DC ACDC 9.5–18V DC 1DC 18.5–58V DC (24VDC, 48VDC) 23DC
Communication protocol Modbus and DNP 3.0 — Modbus and IEC 60870-5-101/104† 870
Mounting Panel mount (standard) — DIN rail mounting DIN
Testing Full functional test, calibration at various work loads & detailed test report —
† –104 requires Ethernet — does not work over a cellular network.
Expansion modules Max. 1 per instrument, order separately.
Expansion module 4 Analogue Outputs: ±1mA / 0–20mA / 0–1mA / 4–20mA / 0–3mA / ±3mA / 0–5mA / ±5mA AO1–AO8 Ethernet (TCP/IP) ETH PROFIBUS PRO RS232/422/485 RS232 4G Modem** — G=Europe, V=Verizon (US), A=AT&T (US), T=Telstra (AUS) T4x 4 Digital Inputs / 2 Relay Outputs, 250V/5A AC DIOR 4 Digital Inputs / 2 SSR Outputs, 250V/0.1A AC DIOS TOU + 4 Digital Inputs (RTC battery) TOD 8 Digital Inputs (dry contact) 8DI 12 Digital Inputs / 4 Relay Outputs, 250V/5A AC 12DIOR 12DIOR digital input rating — DRC, 48V, 125V or 250V DRC / 48V / 125V / 250V 12DIOR communication port — none, RS-485 or Ethernet — / 485 / ETH
** Does not support the 870 protocol; supplied with a bendable antenna.
Downloads and related Questions about this datasheet? Use the contact form .