FCS-600 · DATASHEET
FCS-600 flux gate current sensor datasheet
Solid-core flux gate current sensor, 600A DC primary.
Transcribed from the SATEC Australia datasheet TBV1.0, 17 September 2026 (PDF, 4 pages, 337 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The UHACS (Flux Gate Sensor) series delivers revenue-grade measurement accuracy for most applications when paired with our PRO Series meters, and is a core building block of SATEC’s flux gate current sensing range for DC energy metering.
Based on advanced active sensing technology, UHACS sensors provide the exceptional linearity and stability required for utility-grade metering across today’s diverse energy landscape, with a solid-core clamp body, a 4-pin plug-in connector and a ±15V dual supply for straightforward installation.
Main features
- ±600A DC nominal primary current, with a 1.1×In linear measuring range
- ±720A DC overload rating for 1 minute without damage
- <0.1% (In − 0.05 In) accuracy with 0.02% FS linearity
- Fast ±20 µs response time (di/dt of 100A/µs rise to 90% In)
- DC to 20kHz measurement bandwidth
- 5kV RMS/50Hz galvanic isolation between primary and output
- ±40mA nominal output signal on a simple 600:40 conversion ratio
- Compact solid-core clamp body rated IP61, for panel or bus-bar mounting
Feature capabilities
Important notes
- Incorrect connection may lead to damage of the sensor. Connect the terminals of the power source and output respectively and correctly. Please pay special attention to the 0V / negative current output connection.
- The best accuracy is achieved when the window is fully filled with bus-bar (current-carrying conductor).
- The current sensor must not be used with the secondary output open-circuited, that is, while the primary has current or the sensor is powered on, the secondary output terminal must not be disconnected; the current output terminal can only be disconnected once the bus has no current and the sensor is not powered on. Otherwise, high voltage may be induced and there is a danger of electric shock or equipment damage.
- When you need to move the product, be sure to cut off the power first and unplug all the connecting cables from it.
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
| Primary nominal current DC | ±600A DC |
|---|---|
| Linear measuring range (1 min) | 1.1 × In |
| Primary overload current | ±720A DC @ 1 min |
| Nominal output signal | ±40mA |
| Supply voltage | ±15V DC (±5%) |
| Current consumption (max) | ±430mA |
| Galvanic isolation | 5KV RMS/50Hz/min |
| Conversion ratio (A/mA) | 600 : 40 |
| Weight | 420g (± 50g) |
| Protection of case | IP61 |
| Zero offset current | ±1 µA (@25 °C) |
|---|---|
| Offset temperature coefficient | 40 ppm / K |
| Measuring resistance | 250 Ω |
| Response time | ±20 µs (di/dt of 100A/µs rise to 90% In) |
| Accuracy | <0.1% (In − 0.05 In) |
| Linearity | 0.02% FS |
| Bandwidth (−3dB) | DC – 20kHz |
| Operating temperature | -40°C ~ +85°C |
|---|---|
| Storage temperature | -55°C ~ +95°C |
| 1 | +15V (+) |
|---|---|
| 2 | −15V (−) |
| 3 | Pos. output (M) |
| 4 | 0V / Neg. output (G) |
Ordering information
EL0192
Downloads and related
- Download the datasheet (PDF, TBV1.0, 337 KB)
- Read the PDF in the document library
- All datasheets as web pages