FCS-300 · DATASHEET

FCS-300 flux gate current sensor datasheet

Solid-core flux gate current sensor, 300A DC primary.

Transcribed from the SATEC Australia datasheet TBV1.0, 17 September 2026 (PDF, 4 pages, 336 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The UHACS (Flux Gate Sensor) series delivers revenue-grade measurement accuracy for most applications when paired with our PRO Series meters, and is a core building block of SATEC’s flux gate current sensing range for DC energy metering.

Based on advanced active sensing technology, UHACS sensors provide the exceptional linearity and stability required for utility-grade metering across today’s diverse energy landscape, with a solid-core clamp body, a 4-pin plug-in connector and a ±15V dual supply for straightforward installation.

Main features

Feature capabilities

Important notes

  • Incorrect connection may lead to damage of the sensor. Connect the terminals of the power source and output respectively and correctly. Please pay special attention to the 0V / negative current output connection.
  • The best accuracy is achieved when the window is fully filled with bus-bar (current-carrying conductor).
  • The current sensor must not be used with the secondary output open-circuited, that is, while the primary has current or the sensor is powered on, the secondary output terminal must not be disconnected; the current output terminal can only be disconnected once the bus has no current and the sensor is not powered on. Otherwise, high voltage may be induced and there is a danger of electric shock or equipment damage.
  • When you need to move the product, be sure to cut off the power first and unplug all the connecting cables from it.

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

General characteristics
Primary nominal current DC±300A DC
Linear measuring range (1 min)1.1 × In
Primary overload current±360A DC @ 1 min
Nominal output signal±40mA
Supply voltage±15V DC (±5%)
Current consumption (max)±270mA
Galvanic isolation5KV RMS/50Hz/min
Conversion ratio (A/mA)300 : 40
Weight420g (± 50g)
Protection of caseIP61
Accuracy
Zero offset current±1 µA (@25 °C)
Offset temperature coefficient25 ppm / K
Measuring resistance250 Ω
Response time±20 µs (di/dt of 100A/µs rise to 90% In)
Accuracy0.1% (In − 0.05 In)
Linearity0.02% FS
BandwidthDC – 20kHz
Environmental
Operating temperature-40°C ~ +85°C
Storage temperature-55°C ~ +95°C
Pins
1+15V (+)
2−15V (−)
3Pos. output (M)
40V / Neg. output (G)

Ordering information

EL0191

Downloads and related

Questions about this datasheet? Use the contact form.