UHACS FCS-2500/13 · DATASHEET

UHACS FCS-2500/13 flux gate current sensor datasheet

Solid core flux gate current sensor for high-accuracy DC energy metering.

Transcribed from the SATEC Australia datasheet TBV1.0, 21 September 2026 (PDF, 4 pages, 452 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The UHACS FCS-2500/13 is a solid core flux gate current sensor built for high-current DC energy metering, measuring a primary nominal current of up to ±2,500A DC (±1,750A AC effective). It suits substations, battery energy storage systems (BESS), EV charging infrastructure, data centres and other high-current DC installations where accurate, isolated current measurement is required.

A multi-point zero-flux technology system is combined with high-frequency ripple sensing to deliver high gain and exceptional measurement accuracy across the sensor’s entire bandwidth, providing an advanced measurement channel that enhances existing DC sensor technology. The sensor outputs a linear ±40mA signal from a ±24VDC (±5%) supply, with 5kV galvanic isolation between the primary conductor and the secondary output, and is designed for pairing with SATEC PRO Series DC energy meters.

Main features

Feature capabilities

Applications

  • Battery energy storage system (BESS) metering
  • EV charging infrastructure
  • Industrial and commercial DC bus applications
  • Data centre power systems
  • Solar PV and hybrid renewable installations
  • Rail and high-voltage DC infrastructure

Important notes

  • Incorrect connection may lead to damage of the sensor. Connect the terminals of the power source and output respectively and correctly.
  • The best accuracy is achieved when the window is fully filled with bus-bar (current-carrying conductor).

Electrical hazard

  • The current sensor must not be used with the secondary output open-circuited. That is, whenever the primary has current or the sensor is powered on, the secondary output terminal must not be disconnected. Only when the bus has no current and the sensor is not powered on can the current output terminal be disconnected. Otherwise, high voltage may be induced and there is a danger of electric shock or equipment damage.
  • Before moving the product, be sure to cut off the power first and unplug all connecting cables.

Compatible SATEC meters

  • The UHACS FCS-2500/13 is designed for pairing with SATEC PRO Series DC energy meters for single or multi-channel DC current measurement.
  • See SATEC’s DC Setup Guide for PRO-UHACS for full wiring and commissioning guidance.

Wiring sensors

  • The output current (M) is developed across an external measuring resistor Rm ≤ 250Ω and read via an ammeter or a SATEC meter’s current input, referenced to G. The best accuracy is achieved when the sensor window is fully filled with the bus-bar (current-carrying conductor).

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

General characteristics
Primary nominal current (DC)±2,500A DC
Linear measuring range (1 min)1.1 × primary nominal current DC (up to 2,750A DC)
Primary nominal current (AC)±1,750A AC (AC effective/RMS value)
Nominal output signal±40mA
Supply voltage±24VDC (±5%)
Current consumption±1.2A
Galvanic isolation5kV RMS/50Hz for 1 minute
Conversion ratio2,500A : 40mA
Environmental
Operating temperature−40°C to +80°C (−40°F to 176°F)
Storage temperature−55°C to +95°C (−67°F to 203°F)
Accuracy
Zero offset current±1 µA (at 25°C)
Offset temperature coefficient25 ppm/K
Measuring resistance250Ω
Response time±20μs (di/dt of 100A/µs)
Accuracy0.1%
Linearity0.02% FS
Connections
1 (+)+24V DC supply
2 (−)−24V DC supply (0V reference)
3 (G)Ground
4 (M)Output signal (±40mA)
5 (—)Not assigned
6 (—)Not assigned

Each row gives the pin number, the pin label in brackets and the function, as printed in the three-column Connections table.

Construction
Weight7.2 ± 0.5 kg
Protection ratingIP45

Ordering information

MODEL – RATED CURRENT

Model
Solid core flux gate current sensorFCS
Rated current
2,500A DC primary nominal current2500

The source specification does not define further order-code segments (e.g. the “/13” case-size suffix used in this sensor’s full product name, UHACS FCS-2500/13).

Downloads and related

Questions about this datasheet? Use the contact form.