FCS-1000 · DATASHEET

FCS-1000 flux gate current sensor datasheet

Solid-core flux gate current sensor, 1100A DC / 770A AC primary.

Transcribed from the SATEC Australia datasheet TBV1.0, 17 September 2026 (PDF, 4 pages, 474 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The UHACS (Flux Gate Sensor) series delivers revenue-grade measurement accuracy for most applications when paired with our PRO Series meters, and is a core building block of SATEC’s flux gate current sensing range for DC energy metering.

The FCS-1000 delivers high gain and exceptional measurement accuracy across its full bandwidth, achieved through a multi-point zero-flux system combined with high-frequency ripple sensing — an advanced channel that enhances existing DC sensor technology for the largest bus-bar and cable applications.

Main features

Feature capabilities

Important notes

  • Incorrect connection may lead to damage of the sensor. Connect the terminals of the power source and output respectively and correctly. Please pay special attention to the 0V / negative current output connection.
  • The best accuracy is achieved when the window is fully filled with bus-bar (current-carrying conductor).
  • The current sensor must not be used with the secondary output open-circuited, that is, while the primary has current or the sensor is powered on, the secondary output terminal must not be disconnected; the current output terminal can only be disconnected once the bus has no current and the sensor is not powered on. Otherwise, high voltage may be induced and there is a danger of electric shock or equipment damage.
  • When you need to move the product, be sure to cut off the power first and unplug all the connecting cables from it.

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

General characteristics
Primary nominal current DC±1100A DC
Linear measuring range (1 min)1.1 × IPN_DC
Primary nominal current AC±770A AC (effective value)
Nominal output signal±40mA
Supply voltage±15V DC (±5%)
Current consumption (max)±670mA
Galvanic isolation5KV RMS/50Hz/min
Conversion ratio (A/mA)1000 : 40
Weight4.0kg (± 0.2kg)
Protection of caseIP65
Accuracy
Zero offset current±1 µA (@25 °C)
Offset temperature coefficient25 ppm / K
Measuring resistance250 Ω
Response time20 µs (di/dt of 100A/µs rise to 90% In)
Accuracy0.1% (In − 0.05 In)
Linearity0.02% FS
Bandwidth (−3dB)DC – 20kHz
Environmental
Operating temperature-40°C ~ +85°C
Storage temperature-55°C ~ +95°C
Pins
1+15V (+)
2−15V (−)
30V / Neg. output (G)
4Pos. output (M)
5N/A
6N/A

Ordering information

EL0193

Definition of Part Number: FCS – 1000
Rated input current M = 1000A1000

Downloads and related

Questions about this datasheet? Use the contact form.