PM175 PRO · SUPPLY

Which auxiliary supply rating applies to my PM175 PRO?

PM175 PRO product photograph
PM175 PRO product photograph from the SATEC Australia website

The PM175 PRO's manual and datasheets give different supply ranges. This page sets out what each document says and what to check before connecting a supply. It covers the PM175 PRO (175-PRO) only; the legacy PM175 has a different manual and supply terminals.

Check the label first

The manual says: "Before connecting your meter to the power source, check the label on the back of the device to ensure that it is equipped with the appropriate power supply."

SATEC Australia's advice: photograph the label and take the supply rating from it. Don't choose a range from the table below. Contact SATEC Australia before connecting if the label is missing or unreadable, or if the site supply is near either end of the labelled range.

What the documents say

DocumentWhat it says
Manual BG0657 Rev. A2, section 1.1.7 "Power inputs (power supply)", page 13"PM17X PRO supports AC power input as default", "AC range 80-264 V", "DC range 120-290 V DC", "DC power input might be ordered as an option", "Rating: 24VDC: 9-36 VDC"
Manual BG0657 Rev. A2, terminal drawing, page 26The label in the drawing reads "PS: 90-290 VDC 11VA 80-277VAC"
Manual BG0657 Rev. A2, section 18.3 "Power Supply Installation", page 210"Rated input: 85-277 V AC @ 50/60 Hz, 100-290VDC¹ (voltage is presented as nominal value, admissible tolerance of ± 15% from mains), Burden 11VA", with footnote 1: "UL Listing covers the nominal Voltage Input up to 240V L-N (CAT - III)"
Factory PM17x PRO datasheet (July 2025), page 6, and SATEC Australia PM17x PRO datasheet TBV1.1, page 4, "POWER SUPPLY""Rated input" 100-277V AC @ 50/60 Hz, 100-290V DC; "Tolerance" ±15%; "Burden" 11VA @ V AC, 6VA @ V DC

These documents don't say which range applies to which hardware.

The 9–36 V DC (24 V) supply

  • The manual's section 4.1.7, "12/24V DC Input Power Module", says: "The PM17X PRO is working as default using AC power. The PM17X PRO might be ordered in a DC power supply input option. The 24VDC module designed to provide the power supply ability of the meter in the low DC Voltage range. Input Voltage range of PS 24VDC: 9-36 VDC."
  • Both datasheets have a section headed "AUXILIARY POWER SUPPLY (BUILT-IN)", which lists "Rated input" 9-36V DC (24V) and "Output" 7W.
  • In the SATEC Australia datasheet's ordering information, "AUXILIARY POWER SUPPLY" is a separate field, with the order code AUX-24DC.

The documents don't say whether this supply replaces the main supply or works alongside it. SATEC Australia's advice: don't treat it as a backup supply unless SATEC Australia confirms that for your unit.

Connecting the supply

The manual's instructions:

  • "AC power supply: connect the line wire to terminal 10 and the neutral wire to terminal 9."
  • "DC power supply: connect the positive wire to terminal 10 and the negative wire to terminal 9."
  • "The power source can be dedicated-fused, or from a monitored voltage if it is within the instrument power supply range."
  • "a switch or circuit-breaker shall be included in the building installation"; "It shall be in close proximity to the equipment and within easy reach of the OPERATOR"; "It shall be marked as the disconnecting device for the equipment."
  • "Before installing, ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment."

SATEC Australia's advice: have a licensed electrician do the installation.

Figures that are not the meter's supply

Page 215 of the manual gives power supply figures under "Lindsey Sensor Interface", in section 18.9 "Special Sensor Interface". Those are for that sensor interface, not the meter's own supply.

What to send SATEC Australia

SATEC Australia's advice: include these details when you ask about a PM175 PRO supply:

  • a photo of the rear label, showing the serial number and the supply marking
  • the full order code, if you have the order documents
  • the supply voltage available at the site, and whether it is AC or DC
  • whether a 24 V DC supply is fitted or wanted

Manual and datasheet

Need help?

Contact SATEC Australia technical support through our contact form.

Source review: 22 November 2026.

Contact SATEC technical support

Back to Knowledge Base home