APPLICATION NOTE
Time of Use (TOU) control application note
An Application Note
Transcribed from the SATEC document ADVANCED ENERGY MANAGEMENT UTILISING TOU-BASED CONTROL STRATEGY, September 2025, September 2025 (PDF, 7 pages, 409 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.
General
In the dynamic landscape of diverse energy sources and tariffs, SATEC introduces innovative control solutions for Battery Energy Storage Systems (BESS), Generators, and Electric Vehicles (EVs), utilising the Time Of Use (TOU) functionality embedded in all SATEC meters, thus eliminating the need for additional Programmable Logic Controllers (PLCs).
What is TOU?
Time-of-Use (TOU) is an energy pricing strategy that differentiates rates based on It’s based on day of week, time of day, and season. This approach is employed by utilities to manage peak demand by imposing varying tariffs, with increased rates during typical peak consumption periods.
SATEC devices and TOU
SATEC devices support up to 8 TOU Profiles, 16 Registers groups, and a maximum of 32 calendar/season settings.
PAS setup tree: Energy/TOU Setup, with Billing/TOU Registers, TOU Daily Profiles and TOU Calendar. Drawing not reproduced on this page. See page 2 of the PDF.
Configuring TOU via PAS Software:
The initial step involves configuring the TOU calendar and TOU Daily Profiles within the device.
PAS screenshot: TOU Calendar tab (example settings). Drawing not reproduced on this page. See page 3 of the PDF.
| No. | Season/ Period | Day Type | Week of Month | Weekday | Till Weekday | Month | Day | Till Month | Till Day | Year |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | #1 | #1 | ---- | Sunday | Thursday | July | ---- | August | ---- | ---- |
| 2 | #1 | #2 | ---- | Friday | ---- | July | ---- | August | ---- | ---- |
| 3 | #1 | #3 | ---- | Saturday | ---- | July | ---- | August | ---- | ---- |
| 4 | #2 | #1 | ---- | Sunday | Thursday | December | ---- | February | ---- | ---- |
| 5 | #2 | #2 | ---- | Friday | ---- | December | ---- | February | ---- | ---- |
| 6 | #2 | #3 | ---- | Saturday | ---- | December | ---- | February | ---- | ---- |
| 7 | #3 | #1 | ---- | Sunday | Thursday | March | ---- | June | ---- | ---- |
| 8 | #3 | #2 | ---- | Friday | ---- | March | ---- | June | ---- | ---- |
| 9 | #3 | #3 | ---- | Saturday | ---- | March | ---- | June | ---- | ---- |
| 10 | #3 | #1 | ---- | Sunday | Thursday | September | ---- | November | ---- | ---- |
| 11 | #3 | #2 | ---- | Friday | ---- | September | ---- | November | ---- | ---- |
| 12 | #3 | #3 | ---- | Saturday | ---- | September | ---- | November | ---- | ---- |
| 13 | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- |
| 14 | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- |
| 15 | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- |
| 16 | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- |
PAS screenshot: TOU Daily Profiles tab, Daily Tariff Profile (example settings). Drawing not reproduced on this page. See page 3 of the PDF.
| No. | Tariff Start Time | Tariff No. |
|---|---|---|
| 1 | 00:00 | #3 |
| 2 | 07:00 | #2 |
| 3 | 10:00 | #1 |
| 4 | 17:00 | #2 |
| 5 | 21:00 | #3 |
| 6 | 00:00 | #1 |
| 7 | 00:00 | #1 |
| 8 | 00:00 | #1 |
PAS screenshot: Billing/TOU Registers tab, with Billing/TOU Registers and Register Source List (example settings). Drawing not reproduced on this page. See page 4 of the PDF.
| Reg. | TOU | Use Profile | Dmd Profile | Sum Profile | Units |
|---|---|---|---|---|---|
| 1 | Ticked | Ticked | Ticked | Ticked | kWh |
| 2 | Ticked | Ticked | Ticked | Ticked | kvarh |
| 3 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 4 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 5 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 6 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 7 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 8 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 9 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 10 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 11 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 12 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 13 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 14 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 15 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| 16 | Not ticked | Not ticked | Not ticked | Not ticked | ---- |
| No. | Source Input | Multiplier | Target |
|---|---|---|---|
| 1 | kWh IMPORT | 1.000 | Reg #1 |
| 2 | kvarh IMPORT | 1.000 | Reg #2 |
| 3 | ---- | ---- | ---- |
| 4 | ---- | ---- | ---- |
| 5 | ---- | ---- | ---- |
| 6 | ---- | ---- | ---- |
| 7 | ---- | ---- | ---- |
| 8 | ---- | ---- | ---- |
| 9 | ---- | ---- | ---- |
| 10 | ---- | ---- | ---- |
| 11 | ---- | ---- | ---- |
| 12 | ---- | ---- | ---- |
| 13 | ---- | ---- | ---- |
| 14 | ---- | ---- | ---- |
| 15 | ---- | ---- | ---- |
| 16 | ---- | ---- | ---- |
After configuring TOU settings, press Send to upload the data to the device and activate the TOU profiles.
Using the configured TOU profiles, the user may set triggers for various operations within the capabilities of the specific device model.
Setting these triggers enables events, such as relay operation, or reading the setpoint flag via Modbus, providing a robust control mechanism.
Supported Devices
EM133-XM
- Features an on-board relay, making it well-suited for TOU applications.
- Trigger can be set only for Tariff.
PAS screenshot: EM133 - General Setup, Control/Alarm Setpoints tab (example settings). Drawing not reproduced on this page. See page 5 of the PDF.
| No. | Trigger parameter | Operate limit | Release limit | Operate delay | Release delay | Action |
|---|---|---|---|---|---|---|
| 1 | MINUTE INTERVAL | 15 | ---- | 0.0 | 0.0 | DATA LOG #1 |
| 2 | TOU TARIFF | #1 | ---- | 5.0 | 5.0 | OPERATE REL #1 |
| 3 | ---- | ---- | ---- | ---- | ---- | ---- |
| 4 | RELAY #1 ON | ---- | ---- | 0.0 | 0.0 | EVENT LOG |
SATEC EM133-XM is an energy meter, ideal for a wide range of applications such as revenue metering, industrial power monitoring and for interfacing with SCADA in utility substations.
- Accuracy: Class 0.5S per AS/IEC 62053-22
- Digital & Analogue I/O options
- Broad-range frequency measurement: 25-400 Hz
PM17X, PRO Series, PM180, EM720/920
These devices offer flexibility with the choice of separate or complex setpoints for TOU profiles and tariffs.
PAS screenshot: Control/Alarm Setpoints tab, Setpoint No. 1, with Setpoint Triggers, Actions and Delays (example settings). Drawing not reproduced on this page. See page 6 of the PDF.
| OR/AND | Input Group | Trigger Parameter | Relation | Operate limit | Release limit |
|---|---|---|---|---|---|
| OR | TOU PRMS | ACTIVE TARIFF | = | #1 | ---- |
| OR | TOU PRMS | ACTIVE PROFILE | = | #1 | ---- |
| OR | ---- | ---- | ---- | ---- | ---- |
| OR | ---- | ---- | ---- | ---- | ---- |
| No. | Action | Target | Parameter |
|---|---|---|---|
| 1 | SET EVENT FLAG | #1 | ---- |
| 2 | OPERATE RELAY | #1 | ---- |
| 3 | ---- | ---- | ---- |
| 4 | ---- | ---- | ---- |
| Operate delay | 0.000 |
| Release delay | 0.000 |
The PM180 is a high-performance Class Power Quality Analyser that can simultaneously host several applications, including Phasor Measurement Unit functionality.
- Power Quality Analyser (Class A)
- Up to 48 digital and analog I/O
- PMU per IEEE C37.118.1
- Disturbance Direction Detection
The PRO series combines metering, control and Class A Power Quality analysis, providing a solution for substation automation and energy management, bundling multiple capabilities in one device.
- AC/DC metering
- Power Quality Analyser (Class A):
- IEC 61850
- Dual port Ethernet
EM720/920: these unique devices combine highly accurate revenue grade metering with Class A power quality analysis. This includes virtual metering, based on transformer and lines losses calculation.
- Power Quality Analyser (Class A)
- Revenue grade metering (Class 0.2S)
- Virtual Metering Point (calculated)
- Six-hour operation back-up battery (EM720)
Possible Applications | BESS and Generators
Tariff Optimisation – BESS/Generators
Set triggers to optimise the operation of BESS and generators based on specific tariff structures, considering different rates during peak and off-peak hours and seasons.
EV | Charging Optimisation
Utilise triggers to schedule charging of EV during off-peak TOU periods when electricity rates are lower. This helps lower charging costs for EV owners, and reduces the load on the grid during peak hours.
Employ triggers in fleet management systems to coordinate the charging schedules of multiple EVs according to most cost-effective tariffs from the utility.
Mobile Energy Storage
Configure triggers to allow bidirectional charging, turning EVs into mobile energy storage units. During high TOU rates, EVs can discharge stored energy back to the grid, or power homes and businesses.
General Incentive Programs
Utilise triggers to align EV charging, BESS or Generators with utility incentive programs that offer discounts or rewards for charging during specific TOU periods.