APPLICATION NOTE

Time of Use (TOU) control application note

An Application Note

Transcribed from the SATEC document ADVANCED ENERGY MANAGEMENT UTILISING TOU-BASED CONTROL STRATEGY, September 2025, September 2025 (PDF, 7 pages, 409 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.

General

In the dynamic landscape of diverse energy sources and tariffs, SATEC introduces innovative control solutions for Battery Energy Storage Systems (BESS), Generators, and Electric Vehicles (EVs), utilising the Time Of Use (TOU) functionality embedded in all SATEC meters, thus eliminating the need for additional Programmable Logic Controllers (PLCs).

What is TOU?

Time-of-Use (TOU) is an energy pricing strategy that differentiates rates based on It’s based on day of week, time of day, and season. This approach is employed by utilities to manage peak demand by imposing varying tariffs, with increased rates during typical peak consumption periods.

SATEC devices and TOU

SATEC devices support up to 8 TOU Profiles, 16 Registers groups, and a maximum of 32 calendar/season settings.

PAS setup tree: Energy/TOU Setup, with Billing/TOU Registers, TOU Daily Profiles and TOU Calendar. Drawing not reproduced on this page. See page 2 of the PDF.

Configuring TOU via PAS Software:

The initial step involves configuring the TOU calendar and TOU Daily Profiles within the device.

PAS screenshot: TOU Calendar tab (example settings). Drawing not reproduced on this page. See page 3 of the PDF.

TOU Calendar (values shown in the page 3 screenshot)
No.Season/ PeriodDay TypeWeek of MonthWeekdayTill WeekdayMonthDayTill MonthTill DayYear
1#1#1----SundayThursdayJuly----August--------
2#1#2----Friday----July----August--------
3#1#3----Saturday----July----August--------
4#2#1----SundayThursdayDecember----February--------
5#2#2----Friday----December----February--------
6#2#3----Saturday----December----February--------
7#3#1----SundayThursdayMarch----June--------
8#3#2----Friday----March----June--------
9#3#3----Saturday----March----June--------
10#3#1----SundayThursdaySeptember----November--------
11#3#2----Friday----September----November--------
12#3#3----Saturday----September----November--------
13----------------------------------------
14----------------------------------------
15----------------------------------------
16----------------------------------------

PAS screenshot: TOU Daily Profiles tab, Daily Tariff Profile (example settings). Drawing not reproduced on this page. See page 3 of the PDF.

Daily Tariff Profile, Season #1, Day Type #1 (values shown in the page 3 screenshot)
No.Tariff Start TimeTariff No.
100:00#3
207:00#2
310:00#1
417:00#2
521:00#3
600:00#1
700:00#1
800:00#1

PAS screenshot: Billing/TOU Registers tab, with Billing/TOU Registers and Register Source List (example settings). Drawing not reproduced on this page. See page 4 of the PDF.

Billing/TOU Registers (values shown in the page 4 screenshot)
Reg.TOUUse ProfileDmd ProfileSum ProfileUnits
1TickedTickedTickedTickedkWh
2TickedTickedTickedTickedkvarh
3Not tickedNot tickedNot tickedNot ticked----
4Not tickedNot tickedNot tickedNot ticked----
5Not tickedNot tickedNot tickedNot ticked----
6Not tickedNot tickedNot tickedNot ticked----
7Not tickedNot tickedNot tickedNot ticked----
8Not tickedNot tickedNot tickedNot ticked----
9Not tickedNot tickedNot tickedNot ticked----
10Not tickedNot tickedNot tickedNot ticked----
11Not tickedNot tickedNot tickedNot ticked----
12Not tickedNot tickedNot tickedNot ticked----
13Not tickedNot tickedNot tickedNot ticked----
14Not tickedNot tickedNot tickedNot ticked----
15Not tickedNot tickedNot tickedNot ticked----
16Not tickedNot tickedNot tickedNot ticked----
Register Source List (values shown in the page 4 screenshot)
No.Source InputMultiplierTarget
1kWh IMPORT1.000Reg #1
2kvarh IMPORT1.000Reg #2
3------------
4------------
5------------
6------------
7------------
8------------
9------------
10------------
11------------
12------------
13------------
14------------
15------------
16------------

After configuring TOU settings, press Send to upload the data to the device and activate the TOU profiles.

Using the configured TOU profiles, the user may set triggers for various operations within the capabilities of the specific device model.

Setting these triggers enables events, such as relay operation, or reading the setpoint flag via Modbus, providing a robust control mechanism.

Supported Devices

EM133-XM

PAS screenshot: EM133 - General Setup, Control/Alarm Setpoints tab (example settings). Drawing not reproduced on this page. See page 5 of the PDF.

Control/Alarm Setpoints (values shown in the page 5 screenshot)
No.Trigger parameterOperate limitRelease limitOperate delayRelease delayAction
1MINUTE INTERVAL15----0.00.0DATA LOG #1
2TOU TARIFF#1----5.05.0OPERATE REL #1
3------------------------
4RELAY #1 ON--------0.00.0EVENT LOG

SATEC EM133-XM is an energy meter, ideal for a wide range of applications such as revenue metering, industrial power monitoring and for interfacing with SCADA in utility substations.

PM17X, PRO Series, PM180, EM720/920

These devices offer flexibility with the choice of separate or complex setpoints for TOU profiles and tariffs.

PAS screenshot: Control/Alarm Setpoints tab, Setpoint No. 1, with Setpoint Triggers, Actions and Delays (example settings). Drawing not reproduced on this page. See page 6 of the PDF.

Setpoint Triggers, Setpoint No. 1 (values shown in the page 6 screenshot)
OR/ANDInput GroupTrigger ParameterRelationOperate limitRelease limit
ORTOU PRMSACTIVE TARIFF=#1----
ORTOU PRMSACTIVE PROFILE=#1----
OR--------------------
OR--------------------
Actions (values shown in the page 6 screenshot)
No.ActionTargetParameter
1SET EVENT FLAG#1----
2OPERATE RELAY#1----
3------------
4------------
Delays, s (values shown in the page 6 screenshot)
Operate delay0.000
Release delay0.000

The PM180 is a high-performance Class Power Quality Analyser that can simultaneously host several applications, including Phasor Measurement Unit functionality.

The PRO series combines metering, control and Class A Power Quality analysis, providing a solution for substation automation and energy management, bundling multiple capabilities in one device.

EM720/920: these unique devices combine highly accurate revenue grade metering with Class A power quality analysis. This includes virtual metering, based on transformer and lines losses calculation.

Possible Applications | BESS and Generators

Tariff Optimisation – BESS/Generators

Set triggers to optimise the operation of BESS and generators based on specific tariff structures, considering different rates during peak and off-peak hours and seasons.

EV | Charging Optimisation

Utilise triggers to schedule charging of EV during off-peak TOU periods when electricity rates are lower. This helps lower charging costs for EV owners, and reduces the load on the grid during peak hours.

Employ triggers in fleet management systems to coordinate the charging schedules of multiple EVs according to most cost-effective tariffs from the utility.

Mobile Energy Storage

Configure triggers to allow bidirectional charging, turning EVs into mobile energy storage units. During high TOU rates, EVs can discharge stored energy back to the grid, or power homes and businesses.

General Incentive Programs

Utilise triggers to align EV charging, BESS or Generators with utility incentive programs that offer discounts or rewards for charging during specific TOU periods.