1 00:00:00,000 --> 00:00:07,760 In this lesson, we verify communication with an EM133-XM over Wi-Fi, in PAS, open monitor, 2 00:00:08,480 --> 00:00:09,440 then communication test. 3 00:00:10,160 --> 00:00:14,700 This demonstration uses device address 1 and the approved IP address shown on screen. 4 00:00:15,580 --> 00:00:19,680 Read one word from firmware register 2565 using function 3. 5 00:00:20,000 --> 00:00:22,580 Send the request, inspect the response, then repeat. 6 00:00:23,180 --> 00:00:26,420 Both reads return 1210, with no reported communication errors. 7 00:00:26,980 --> 00:00:28,540 This checks a stable firmware value. 8 00:00:28,540 --> 00:00:30,300 It is not a unique serial number. 9 00:00:35,000 --> 00:00:37,960 Next, choose MeterSetup, then Upload Setups. 10 00:00:38,400 --> 00:00:43,520 Upload means copying configuration from the meter into the local PAS site file. 11 00:00:44,160 --> 00:00:48,080 Check that the selected file is your demonstration site before accepting the 12 00:00:48,080 --> 00:00:51,260 overwrite warning. Wait for the upload complete message. 13 00:00:51,960 --> 00:00:56,700 Download Setups sends settings in the opposite direction, so do not confuse the two commands. 14 00:00:56,700 --> 00:01:00,840 This session reads the configuration without changing CT settings. 15 00:01:05,000 --> 00:01:07,980 For the clock, open monitor, then RTC. 16 00:01:09,080 --> 00:01:10,800 Compare the computer and device times first. 17 00:01:11,360 --> 00:01:13,240 Set synchronises the meter to the computer, 18 00:01:13,880 --> 00:01:16,620 an authorised operator completes authentication if required. 19 00:01:17,440 --> 00:01:19,520 This edit shows separate before and after shots. 20 00:01:20,320 --> 00:01:22,340 After synchronising, select Read again. 21 00:01:23,200 --> 00:01:24,700 Here, the displayed times agree. 22 00:01:25,180 --> 00:01:27,220 That verifies the read back against this computer. 23 00:01:27,880 --> 00:01:29,760 Not an independently calibrated time reference. 24 00:01:31,000 --> 00:01:34,200 To retrieve records, open logs, then upload logs. 25 00:01:34,800 --> 00:01:37,680 Save into a new log database, separate from the site configuration. 26 00:01:38,820 --> 00:01:42,620 In this take, PAS uploads the event log and data log one, 27 00:01:42,920 --> 00:01:45,460 and reports 1093 records uploaded. 28 00:01:46,240 --> 00:01:48,160 Let the transfer finish before opening the file. 29 00:01:48,920 --> 00:01:53,580 The saved database also contains an RTC set event at the synchronisation time. 30 00:01:54,100 --> 00:01:55,980 That event was checked directly in the database 31 00:01:55,980 --> 00:01:59,740 because navigating the PAS report caused the application to close. 32 00:01:59,740 --> 00:02:02,880 upload success and report viewing are separate checks. 33 00:02:05,000 --> 00:02:09,340 Pro-tip, while online, right-click the selected site and open properties. 34 00:02:10,360 --> 00:02:13,740 Check the model, serial number and firmware before interpreting measurements. 35 00:02:14,900 --> 00:02:16,740 Scroll to inspect the connection and configuration. 36 00:02:17,980 --> 00:02:20,360 Offline properties may show saved information instead. 37 00:02:21,680 --> 00:02:22,300 Another useful tip. 38 00:02:23,180 --> 00:02:27,040 If the expected OK button is hidden, Enter can activate the dialog default. 39 00:02:27,880 --> 00:02:29,980 In this recording it worked from the file name field. 40 00:02:30,760 --> 00:02:32,720 Check the focus and expected action first.