1 00:00:00,000 --> 00:00:02,667 The EM133-XM can keep different 2 00:00:02,667 --> 00:00:04,792 kinds of history. In PAS, 3 00:00:04,792 --> 00:00:06,042 Data Logs 1, 2, 4 00:00:06,042 --> 00:00:08,250 and 3 are configurable recorders. 5 00:00:08,250 --> 00:00:10,500 Data Log 16 is the daily billing 6 00:00:10,500 --> 00:00:12,000 and time of use profile. 7 00:00:12,000 --> 00:00:13,417 The Event Log records 8 00:00:13,417 --> 00:00:14,708 configuration changes, 9 00:00:14,708 --> 00:00:16,708 resets and diagnostics. 10 00:00:16,708 --> 00:00:19,833 This tour uses saved offline settings. 11 00:00:19,833 --> 00:00:21,250 It explains the controls 12 00:00:21,250 --> 00:00:22,958 without changing the meter. 13 00:00:22,958 --> 00:00:25,917 Start with MeterSetup > Memory/Log, 14 00:00:25,917 --> 00:00:27,250 then Log Memory. 15 00:00:27,250 --> 00:00:28,750 Read the selected file, 16 00:00:28,750 --> 00:00:29,833 its record limit 17 00:00:29,833 --> 00:00:31,458 and whether it wraps around, 18 00:00:31,750 --> 00:00:33,083 wrap around replaces 19 00:00:33,083 --> 00:00:34,167 the oldest records. 20 00:00:34,167 --> 00:00:35,500 When the file fills, 21 00:00:35,500 --> 00:00:38,208 a non wrap file stops at capacity. 22 00:00:38,208 --> 00:00:39,583 Available history depends 23 00:00:39,583 --> 00:00:41,708 on the allocation and recording rate. 24 00:00:41,708 --> 00:00:44,042 Before clearing or repartitioning, 25 00:00:44,042 --> 00:00:45,625 upload the required logs 26 00:00:45,625 --> 00:00:47,792 and verify the saved archive. 27 00:00:47,792 --> 00:00:49,542 Now open Data Recorder 28 00:00:49,542 --> 00:00:51,417 and select Data Log 1. 29 00:00:51,833 --> 00:00:53,250 The parameter list defines 30 00:00:53,250 --> 00:00:54,958 what each record contains. 31 00:00:54,958 --> 00:00:57,500 An energy trend is one possible use. 32 00:00:57,500 --> 00:00:59,750 Choose the required energy quantities, 33 00:00:59,750 --> 00:01:01,750 check their units and preserve 34 00:01:01,750 --> 00:01:03,917 import and export direction. 35 00:01:03,917 --> 00:01:05,375 The file number does not make 36 00:01:05,375 --> 00:01:07,750 it an energy log automatically. 37 00:01:07,750 --> 00:01:09,958 A cumulative energy reading is also 38 00:01:09,958 --> 00:01:10,958 different from the energy 39 00:01:10,958 --> 00:01:13,000 used during one interval. 40 00:01:13,000 --> 00:01:15,542 Select Data Log 2 to inspect its own 41 00:01:15,542 --> 00:01:18,417 parameter list. On the XM model, 42 00:01:18,417 --> 00:01:20,125 It is an additional configurable 43 00:01:20,125 --> 00:01:21,667 conventional Data Log. 44 00:01:21,667 --> 00:01:23,250 For example, a separate 45 00:01:23,250 --> 00:01:24,125 voltage and current 46 00:01:24,125 --> 00:01:25,375 trend can answer a different 47 00:01:25,375 --> 00:01:27,208 question from the energy trend. 48 00:01:27,208 --> 00:01:29,208 That is a proposed configuration, 49 00:01:29,208 --> 00:01:31,125 not a factory assignment. 50 00:01:31,125 --> 00:01:32,667 Choose the fields deliberately 51 00:01:32,667 --> 00:01:34,542 and check the allocated capacity 52 00:01:34,542 --> 00:01:36,708 before changing the recording rate. 53 00:01:37,208 --> 00:01:38,792 Data Log 3 provides 54 00:01:38,792 --> 00:01:40,292 another independently configured 55 00:01:40,292 --> 00:01:41,750 conventional file. 56 00:01:41,750 --> 00:01:43,542 One possible design is to keep 57 00:01:43,542 --> 00:01:45,125 a condition triggered snapshot 58 00:01:45,125 --> 00:01:47,208 separate from periodic trends. 59 00:01:47,500 --> 00:01:48,625 First define the condition 60 00:01:48,625 --> 00:01:49,833 and the quantities needed 61 00:01:49,833 --> 00:01:50,917 to investigate it. 62 00:01:50,917 --> 00:01:52,458 Then confirm that the selected 63 00:01:52,458 --> 00:01:53,833 setpoint action targets 64 00:01:53,833 --> 00:01:55,000 the intended file. 65 00:01:55,000 --> 00:01:56,917 Do not confuse a stored parameter 66 00:01:56,917 --> 00:01:58,167 snapshot with a waveform 67 00:01:58,167 --> 00:02:00,250 recording or override a setpoint 68 00:02:00,250 --> 00:02:02,042 already controlling another function. 69 00:02:02,042 --> 00:02:03,583 For periodic recording, 70 00:02:03,583 --> 00:02:04,833 use MeterSetup, 71 00:02:04,833 --> 00:02:05,875 General Setup, 72 00:02:05,875 --> 00:02:08,208 then Control/Alarm Setpoints. 73 00:02:08,208 --> 00:02:09,750 The minute interval trigger 74 00:02:09,750 --> 00:02:11,875 determines when a record is requested. 75 00:02:11,875 --> 00:02:13,667 The Data Log action chooses 76 00:02:13,667 --> 00:02:15,125 its destination. 77 00:02:15,125 --> 00:02:16,417 The Data Recorder list 78 00:02:16,417 --> 00:02:18,000 determines its contents. 79 00:02:18,000 --> 00:02:20,167 These are three separate decisions. 80 00:02:20,167 --> 00:02:22,000 Changing the logging interval does not 81 00:02:22,000 --> 00:02:23,375 automatically change the demand 82 00:02:23,375 --> 00:02:25,000 calculation period. 83 00:02:25,000 --> 00:02:26,917 After an authorised live change, 84 00:02:26,917 --> 00:02:28,792 read the settings back and verify 85 00:02:28,792 --> 00:02:30,917 successive uploaded records. 86 00:02:31,208 --> 00:02:33,875 Data Log 16 has a different purpose. 87 00:02:33,875 --> 00:02:35,375 It stores the daily billing 88 00:02:35,375 --> 00:02:37,708 and time of use profile with records 89 00:02:37,708 --> 00:02:39,375 added automatically at midnight. 90 00:02:39,375 --> 00:02:40,500 Its sections follow 91 00:02:40,500 --> 00:02:41,542 the configured billing, 92 00:02:41,542 --> 00:02:43,125 energy and maximum demand 93 00:02:43,125 --> 00:02:44,750 register profiles. 94 00:02:44,750 --> 00:02:46,167 Check the energy sources, 95 00:02:46,167 --> 00:02:48,083 profile selections and tariff 96 00:02:48,083 --> 00:02:49,625 configuration before planning 97 00:02:49,625 --> 00:02:51,375 its memory allocation. 98 00:02:51,375 --> 00:02:53,375 These stored register readings are not 99 00:02:53,375 --> 00:02:55,083 automatically daily consumption 100 00:02:55,083 --> 00:02:56,625 and they are not a substitute 101 00:02:56,625 --> 00:02:58,625 for 5 minute interval energy. 102 00:02:58,875 --> 00:03:00,667 Confirm the time reference and read 103 00:03:00,667 --> 00:03:02,417 the report headings carefully. 104 00:03:02,417 --> 00:03:03,667 The Event Log provides 105 00:03:03,667 --> 00:03:05,292 a timestamped event history. 106 00:03:05,292 --> 00:03:06,917 The manuals document entries 107 00:03:06,917 --> 00:03:08,333 such as setup changes, 108 00:03:08,333 --> 00:03:09,375 clock setting, 109 00:03:09,375 --> 00:03:11,917 log clearing and diagnostic events. 110 00:03:11,917 --> 00:03:13,417 Use timestamps and event 111 00:03:13,417 --> 00:03:14,833 descriptions to understand what 112 00:03:14,833 --> 00:03:16,083 happened around a data gap 113 00:03:16,083 --> 00:03:17,542 or configuration change. 114 00:03:17,542 --> 00:03:19,375 An event entry does not by itself 115 00:03:19,375 --> 00:03:21,042 establish the cause of a fault. 116 00:03:21,042 --> 00:03:22,958 Filtering or sorting a PAS 117 00:03:22,958 --> 00:03:24,250 report changes the view 118 00:03:24,250 --> 00:03:26,333 it does not delete the stored records. 119 00:03:26,333 --> 00:03:27,958 Finally, keep configuration 120 00:03:27,958 --> 00:03:30,292 and history separate. Upload Setups 121 00:03:30,292 --> 00:03:31,875 Saves the meter configuration 122 00:03:31,875 --> 00:03:34,708 Logs > Upload Logs retrieves selected 123 00:03:34,708 --> 00:03:37,000 historical files. Reopen the saved 124 00:03:37,000 --> 00:03:39,042 database. Check the required logs, 125 00:03:39,042 --> 00:03:41,208 timestamps, fields, and coverage, 126 00:03:41,208 --> 00:03:42,750 then retain a second copy. 127 00:03:42,750 --> 00:03:44,708 If that verification fails, 128 00:03:44,708 --> 00:03:45,750 stop before clearing 129 00:03:45,750 --> 00:03:47,250 memory. With each file 130 00:03:47,250 --> 00:03:48,375 Given a clear purpose, 131 00:03:48,375 --> 00:03:50,083 PAS becomes easier 132 00:03:50,083 --> 00:03:51,417 to use for trend review, 133 00:03:51,417 --> 00:03:52,667 daily register history, 134 00:03:52,667 --> 00:03:54,375 and event investigation.