1 00:00:00,000 --> 00:00:04,680 We're inspecting saved offline settings for an EM133-XM. 2 00:00:04,960 --> 00:00:07,180 From MeterSetup, choose Memory/Log. 3 00:00:07,540 --> 00:00:10,000 Select Data Log Three and open Setup Recorder. 4 00:00:10,580 --> 00:00:13,760 Check Log Number Three, then review the parameters selected for its records. 5 00:00:14,760 --> 00:00:18,360 Return to Log Memory, select Data Log Three and open Configure File. 6 00:00:19,020 --> 00:00:20,880 The record count sets the file's capacity. 7 00:00:21,560 --> 00:00:24,420 File Type determines what happens when that capacity is reached. 8 00:00:25,380 --> 00:00:27,740 Wrap-around replaces the oldest records with new ones. 9 00:00:28,180 --> 00:00:30,020 That is first in, first out. 10 00:00:30,660 --> 00:00:32,840 A non-wrap file stops recording when full. 11 00:00:33,560 --> 00:00:36,540 Changing the partition or clearing a file is a separate operation. 12 00:00:37,500 --> 00:00:41,280 Upload the required history and check the saved archive before either operation. 13 00:00:42,020 --> 00:00:46,860 Next, open MeterSetup, General Setup, then Control/Alarm Setpoints. 14 00:00:47,760 --> 00:00:51,400 Inspect the trigger and its Data Log action together so records reach the intended file. 15 00:00:52,000 --> 00:00:54,920 The reference lists near the end of the manual explain trigger and 16 00:00:54,920 --> 00:00:58,140 parameter names; check the choices available for your XM model. 17 00:00:58,780 --> 00:01:00,300 No settings are sent in this walkthrough. 18 00:01:00,640 --> 00:01:03,900 Pro tip: expand your site and its Memory/Log branch. 19 00:01:04,500 --> 00:01:08,640 Log Memory and Data Recorder provide quick access to these same setup screens.