1 00:00:00,000 --> 00:00:04,000 We're inspecting saved offline settings for an EM133-XM. 2 00:00:04,000 --> 00:00:06,540 From MeterSetup, choose Memory/Log. 3 00:00:07,000 --> 00:00:09,560 Select Data Log Two and open Setup Recorder. 4 00:00:10,380 --> 00:00:11,920 Check that Log Number Two is displayed. 5 00:00:12,880 --> 00:00:15,460 This list defines the values stored together in each record. 6 00:00:16,520 --> 00:00:20,620 The log number identifies the file; its selected parameters determine what it contains. 7 00:00:21,740 --> 00:00:25,960 Now return to Log Memory, select Data Log Two and open Configure File. 8 00:00:26,820 --> 00:00:29,360 Read Number of Records for the file's allocated capacity. 9 00:00:30,280 --> 00:00:32,980 Retention also depends on how often records are added. 10 00:00:33,740 --> 00:00:37,160 One record every fifteen minutes gives ninety-six records a day. 11 00:00:38,140 --> 00:00:40,400 Divide the allocated record count by that daily rate. 12 00:00:41,240 --> 00:00:44,140 Additional event-triggered records shorten the available history. 13 00:00:45,060 --> 00:00:50,780 To inspect the recording trigger, open MeterSetup, General Setup, then Control/Alarm Setpoints. 14 00:00:51,660 --> 00:00:53,880 Check both the trigger and its Data Log action. 15 00:00:53,880 --> 00:00:58,940 The trigger determines when to record; the action chooses the destination; the 16 00:00:58,940 --> 00:01:00,460 recorder list defines the contents. 17 00:01:01,160 --> 00:01:03,500 This walkthrough inspects settings without sending changes. 18 00:01:04,060 --> 00:01:07,860 Pro tip: expand the plus beside your site, then Memory/Log. 19 00:01:08,300 --> 00:01:12,000 Log Memory and Data Recorder open the same setup screens from the Site Tree.