WEBVTT

00:00:00.067 --> 00:00:01.567
How much power was this meter

00:00:01.567 --> 00:00:03.767
recording and when did it change?

00:00:04.400 --> 00:00:07.400
Expertpower's History view helps you answer

00:00:07.400 --> 00:00:10.000
that question without changing the meter.

00:00:10.467 --> 00:00:12.467
This is the SATEC Demo Site,

00:00:12.467 --> 00:00:14.167
Using the existing record

00:00:14.167 --> 00:00:17.367
called PM180 SATEC Income.

00:00:17.600 --> 00:00:20.467
we are demonstrating how to read the screen.

00:00:20.467 --> 00:00:22.933
The record name alone does not prove

00:00:22.933 --> 00:00:25.433
the equipment connected behind it.

00:00:25.433 --> 00:00:29.133
From Manager, open Readings, then History.

00:00:29.133 --> 00:00:30.567
Check current selection

00:00:30.567 --> 00:00:32.700
before interpreting the graph.

00:00:32.967 --> 00:00:35.533
Confirm the site and the device and keep

00:00:35.533 --> 00:00:38.000
that context visible as you work.

00:00:38.667 --> 00:00:41.533
Choose a completed day. Here,

00:00:41.533 --> 00:00:43.967
The reporting range runs from midnight

00:00:43.967 --> 00:00:47.200
on the tenth of November to midnight on the eleventh.

00:00:47.600 --> 00:00:48.967
Read both boundaries,

00:00:48.967 --> 00:00:50.800
then apply the selection.

00:00:51.367 --> 00:00:54.667
Dates are shown month first in this interface.

00:00:54.667 --> 00:00:56.033
Under data type,

00:00:56.033 --> 00:00:57.067
choose Phase,

00:00:57.067 --> 00:00:58.700
then Active Power.

00:00:59.300 --> 00:01:02.700
The unit is kilowatts. Power describes

00:01:02.700 --> 00:01:05.233
the rate of energy use at a reading.

00:01:05.633 --> 00:01:07.700
Energy measured in kilowatt

00:01:07.700 --> 00:01:10.033
hours accumulates over time.

00:01:10.433 --> 00:01:12.267
A power reading and an energy

00:01:12.267 --> 00:01:15.033
total answer different questions.

00:01:15.300 --> 00:01:17.633
The legend identifies phase one,

00:01:17.633 --> 00:01:19.900
Phase two, and phase three.

00:01:20.133 --> 00:01:22.367
These are phases of the selected record,

00:01:22.367 --> 00:01:24.467
not three separate sites.

00:01:24.467 --> 00:01:27.367
Clicking a legend entry hides that trace.

00:01:27.733 --> 00:01:30.233
Hide the other two to inspect phase one,

00:01:30.233 --> 00:01:31.333
then click them again

00:01:31.333 --> 00:01:33.167
to restore the comparison.

00:01:34.133 --> 00:01:35.567
A hidden trace is not

00:01:35.567 --> 00:01:37.433
evidence of a dead phase.

00:01:37.900 --> 00:01:40.033
Look at the time axis and the summary

00:01:40.033 --> 00:01:42.733
together on this displayed day.

00:01:42.733 --> 00:01:47.033
Phase one's maximum is 37.54 kilowatts.

00:01:47.500 --> 00:01:48.867
That is the maximum shown

00:01:48.867 --> 00:01:50.667
for this history selection.

00:01:51.633 --> 00:01:53.633
It does not automatically establish

00:01:53.633 --> 00:01:56.100
the maximum demand used for billing.

00:01:56.767 --> 00:01:58.767
To inspect part of the profile,

00:01:58.767 --> 00:02:01.400
hold the left mouse button inside the plot

00:02:01.400 --> 00:02:03.233
drag across the time window.

00:02:03.233 --> 00:02:06.600
then release. The plotted hours

00:02:06.600 --> 00:02:09.133
narrow and Reset Zoom appears.

00:02:09.133 --> 00:02:12.000
The reporting dates at the top stay the same.

00:02:12.433 --> 00:02:14.167
Click Reset Zoom to restore

00:02:14.167 --> 00:02:16.067
the whole day's context.

00:02:16.433 --> 00:02:18.233
The details table gives

00:02:18.233 --> 00:02:20.533
each reading its own timestamp.

00:02:20.833 --> 00:02:23.033
For example, the midnight row

00:02:23.033 --> 00:02:26.667
shows 10.31 kilowatts for phase one.

00:02:27.067 --> 00:02:28.600
Always read across the same

00:02:28.600 --> 00:02:30.533
row and check the units.

00:02:31.000 --> 00:02:33.600
Do not assume every timestamp is exactly

00:02:33.600 --> 00:02:35.833
on a quarter hour or that a joined

00:02:35.833 --> 00:02:37.800
line proves complete data.

00:02:38.533 --> 00:02:39.700
For demand fields,

00:02:39.700 --> 00:02:41.333
choose Power and Demand,

00:02:41.333 --> 00:02:43.333
then Total Demands.

00:02:43.333 --> 00:02:45.167
Read the full field name.

00:02:45.167 --> 00:02:46.967
Power Demand and Maximum Power

00:02:46.967 --> 00:02:48.967
Demand are separate entries.

00:02:49.733 --> 00:02:51.733
Kilowatts and kilovolt amperes

00:02:51.733 --> 00:02:53.233
are different units.

00:02:53.500 --> 00:02:56.467
Before using a demand figure for a decision,

00:02:56.467 --> 00:02:58.867
confirm the meter's demand interval

00:02:58.867 --> 00:03:01.567
calculation method and reset history.

00:03:02.600 --> 00:03:03.867
Those settings have not

00:03:03.867 --> 00:03:06.200
been established by this demonstration.

00:03:06.767 --> 00:03:08.400
Return to phase and choose

00:03:08.400 --> 00:03:11.167
PF to inspect power factor.

00:03:11.700 --> 00:03:13.867
Preserve the displayed sign.

00:03:13.867 --> 00:03:15.900
A minus sign on its own is not

00:03:15.900 --> 00:03:18.200
a diagnosis of reverse energy,

00:03:18.200 --> 00:03:20.833
incorrect wiring, or a fault.

00:03:21.233 --> 00:03:22.800
Check the meter's documented

00:03:22.800 --> 00:03:24.567
convention and supporting measurements

00:03:24.567 --> 00:03:26.267
before interpreting it.

00:03:26.833 --> 00:03:29.233
Use the same sequence each time.

00:03:29.467 --> 00:03:32.100
Check the selected record and period

00:03:32.100 --> 00:03:33.667
choose the quantity and unit,

00:03:33.667 --> 00:03:35.467
inspect the graph and confirm

00:03:35.467 --> 00:03:37.400
the timestamped details.

00:03:38.467 --> 00:03:39.800
You now have a precise

00:03:39.800 --> 00:03:41.733
observation to investigate

00:03:41.733 --> 00:03:44.567
rather than a conclusion based on one line.