WEBVTT

00:00:00.000 --> 00:00:05.500
This Expertpower lesson shows how to review an existing billing period.

00:00:05.500 --> 00:00:10.740
We will find the saved invoice record, set the matching month in Billing Data, then

00:00:10.740 --> 00:00:12.940
check the account's energy view.

00:00:12.940 --> 00:00:17.200
Names, identifiers and financial values are concealed.

00:00:17.200 --> 00:00:21.640
The dates and energy values remain the actual recorded values.

00:00:21.640 --> 00:00:25.560
In Manager, open Billing, then Invoices History.

00:00:25.560 --> 00:00:28.840
The selected account appears in the context row above the table.

00:00:28.840 --> 00:00:32.940
Check that account before interpreting the result.

00:00:32.940 --> 00:00:37.780
A meter, a member channel and a virtual billing account can represent different

00:00:37.780 --> 00:00:42.920
scopes. A similar name alone is not enough to establish that they are the same billing

00:00:42.920 --> 00:00:48.180
record. In this example, the saved row starts on the first of

00:00:48.180 --> 00:00:52.640
October and ends on the first of November, twenty twenty-six.

00:00:52.640 --> 00:00:55.520
The row shows thirty-one days.

00:00:55.520 --> 00:00:56.800
Read those actual row dates.

00:00:56.800 --> 00:01:01.960
The range at the top is a separate lookup context and is not proof of the saved

00:01:01.960 --> 00:01:06.180
invoice's period. The row also has approval and deletion

00:01:06.180 --> 00:01:09.880
controls. We leave those untouched.

00:01:09.880 --> 00:01:14.800
Finding a saved record does not establish who created it, whether it was sent, or

00:01:14.800 --> 00:01:16.160
whether its contents are correct.

00:01:16.967 --> 00:01:20.827
Open Billing, then Billing Data for the same account.

00:01:20.827 --> 00:01:25.667
Check the device name again and read the loaded Bill period and Number of days in bill

00:01:25.667 --> 00:01:31.167
period. In this session, returning to the page reset the preview to the

00:01:31.167 --> 00:01:34.847
first through the ninth of November, with eight days.

00:01:34.847 --> 00:01:38.547
That is a different period from the October record.

00:01:38.547 --> 00:01:42.007
It is not evidence that the saved invoice is wrong.

00:01:42.007 --> 00:01:44.127
Open the Date control.

00:01:44.127 --> 00:01:46.947
This billing page offers Time Range and Fixed Time.

00:01:46.947 --> 00:01:51.727
Time Range provides separate start and end dates.

00:01:51.727 --> 00:01:54.887
For our complete named month, choose Fixed Time.

00:01:54.887 --> 00:01:58.347
Select October and the year twenty twenty-six.

00:01:58.347 --> 00:02:03.147
The preview below still shows the old period until the selection is applied.

00:02:03.147 --> 00:02:06.427
Use Update, then check the loaded page.

00:02:06.427 --> 00:02:10.767
Our October period runs from the first of October to the first of November and shows

00:02:10.767 --> 00:02:15.567
thirty-one days. The end is the start of the following month.

00:02:15.567 --> 00:02:19.447
Check the actual dates and the day count together after every account or page

00:02:19.447 --> 00:02:24.367
change. A selected month in an open panel is only an intermediate

00:02:24.367 --> 00:02:29.227
step. The status now says An invoice exists.

00:02:29.227 --> 00:02:32.407
Check history before proposing another run.

00:02:32.407 --> 00:02:36.747
This viewing lesson does not save or recreate an invoice.

00:02:36.747 --> 00:02:41.967
The existing-record indicator also does not approve the prices, the source data or the

00:02:41.967 --> 00:02:42.627
issued document.

00:02:43.600 --> 00:02:48.080
In Billing Data, open Display Options and enable Show readings table.

00:02:48.080 --> 00:02:51.460
Scroll down to see the components used in this preview.

00:02:51.460 --> 00:02:55.680
Here the nine consumption entries add to five thousand, six hundred and fifty-eight

00:02:55.680 --> 00:03:00.460
kilowatt-hours. The charge table above shows that same energy

00:03:00.460 --> 00:03:04.760
usage, while the daily charge quantity is thirty-one days.

00:03:04.760 --> 00:03:09.700
We have concealed prices and financial totals, so this demonstration cannot validate

00:03:09.700 --> 00:03:12.120
their arithmetic or tariff.

00:03:12.120 --> 00:03:16.960
Next, open Consumption, Electricity, then Total.

00:03:16.960 --> 00:03:20.140
The selected record remains the same billing account.

00:03:20.140 --> 00:03:24.740
Confirm the first of October to the first of November at the top, with Days as the

00:03:24.740 --> 00:03:30.120
display resolution. Open the date panel to check midnight at both boundaries,

00:03:30.120 --> 00:03:33.620
then close it without changing the range.

00:03:33.620 --> 00:03:37.420
In Consumption Summary, read Active energy import, in

00:03:37.420 --> 00:03:41.053
kilowatt-hours. The usage is five thousand, six hundred and

00:03:41.053 --> 00:03:46.180
fifty-eight. The previous and present registers differ by the same

00:03:46.180 --> 00:03:50.480
amount. That agrees with the Billing Data preview for this account and

00:03:50.480 --> 00:03:54.640
month. It does not prove the contents of the issued invoice

00:03:54.640 --> 00:03:59.860
PDF. The daily bars and Consumption Table let you look more

00:03:59.860 --> 00:04:01.820
closely at the period.

00:04:01.820 --> 00:04:05.580
Read the quantity and units before comparing values.

00:04:05.580 --> 00:04:09.420
A whole virtual account can contain several member records.

00:04:09.420 --> 00:04:13.960
One member's total is only part of the account; establish its mapping and contribution

00:04:13.960 --> 00:04:16.800
before making that comparison.

00:04:16.800 --> 00:04:21.600
An empty panel, a flat section or a missing bar is a prompt to check the

00:04:21.600 --> 00:04:24.640
selection, dates and source data.

00:04:24.640 --> 00:04:28.160
It does not by itself prove zero consumption or a meter outage.

00:04:28.160 --> 00:04:33.600
The underlying meter's logged records and the processed consumption view are different

00:04:33.600 --> 00:04:39.060
sources. When an investigation needs them, check the configured interval and

00:04:39.060 --> 00:04:43.260
the actual timestamps, including the time basis and period boundaries.

00:04:44.267 --> 00:04:49.367
The embedded network operator's playbook uses these checks as a sequence:

00:04:49.367 --> 00:04:54.187
establish the account, read the saved period, align the preview, then trace the

00:04:54.187 --> 00:04:59.027
energy. Keep a short evidence note stating the record, dates,

00:04:59.027 --> 00:05:02.987
units, source and what remains unresolved.

00:05:02.987 --> 00:05:07.127
The working playbook below this lesson follows the same order.

00:05:07.127 --> 00:05:10.907
Two documented cases explain why the sequence matters.

00:05:10.907 --> 00:05:15.047
After a shared meter replacement, old and new records can require investigation

00:05:15.047 --> 00:05:20.507
together. Check their actual data and the affected units before treating an old

00:05:20.507 --> 00:05:25.467
record as harmless or deciding that a duplicate bill exists.

00:05:25.467 --> 00:05:29.547
In a missing data case, distinguish absent raw records from a processing

00:05:29.547 --> 00:05:34.367
delay. Reprocessing cannot recreate a source record that was never

00:05:34.367 --> 00:05:37.747
received. Any operational change needs its own authorised

00:05:37.747 --> 00:05:42.987
procedure. Matching the account, days and energy is one

00:05:42.987 --> 00:05:44.847
part of billing review.

00:05:44.847 --> 00:05:50.147
Rates, invoice readings, estimates, document content and delivery each need their own

00:05:50.147 --> 00:05:55.267
evidence. The issued invoice PDF is a separate check.

00:05:55.267 --> 00:05:59.427
A green indicator on this screen is not a release decision.

00:05:59.427 --> 00:06:04.427
For your next review, begin with the saved record, confirm the account and dates after

00:06:04.427 --> 00:06:08.047
each navigation, and compare like with like.

00:06:08.047 --> 00:06:11.507
Stop at any unresolved mismatch and record the evidence for

00:06:11.507 --> 00:06:16.587
investigation. That gives the operator a clear question to resolve before

00:06:16.587 --> 00:06:18.847
anyone changes or releases an invoice.
