EM133-XM — set CT primary to 250 A Synthetic narration. Welcome to this demonstration on how to change the CT ratio, or primary current setting, on a SATEC EM133-XM meter. In this example, we've chosen a two hundred and fifty amp CT with a five amp secondary. We'll enter, save and check two hundred and fifty amps. First, check your meter's current input rating. This example uses the five amp version. Other versions need a matching CT or sensor. For HACS, only use SATEC supplied High Accuracy Current Sensors. Please consult SATEC if you're unsure. Let's get familiar with the two buttons. The triangle is SCROLL. The bent arrow is SELECT and ENTER. A short press means press and release straight away. For an ordinary ENTER action, hold for around three seconds, then release. To open programming from the normal display, we need a longer hold. Hold SELECT and ENTER for more than five seconds, then release. The password screen will appear. The default password is nine, if it hasn't been changed. Give SCROLL nine quick presses to set the last digit to nine. Now hold ENTER for around three seconds, then release. If you don't have the configured password, ask your administrator or contact SATEC. Next, use SCROLL to move from Reset, through RTC, to Basic. Hold ENTER for around three seconds, then release to open the Basic menu. Continue with short SCROLL presses through the wiring configuration, PT ratio and PT factor, until CT appears. The number below is the present CT primary current. Now give SELECT a quick press to edit the number. The digits appear with leading zeros. Short SELECT presses move to the next digit, while SCROLL increases that digit. We'll change the example's existing five amps to two hundred and fifty. Move to the hundreds digit and set it to two. Move to the tens digit and set it to five. Then move to the units digit and continue from five, through nine, to zero. Check that the display reads zero, zero, two, five, zero. When it matches, hold ENTER for around three seconds, then release to save. Check that CT now shows two hundred and fifty. Our two hundred and fifty to five amp CT has a fifty to one ratio, but we enter the primary current, two hundred and fifty amps. Finally, hold ENTER for around three seconds and release to return to the main menu. Give SELECT a short press to choose Exit. Hold ENTER again for around three seconds, then release to return to the normal display. Great work! You've changed the CT primary current and checked the saved setting. Scan the code for the EM132/EM133 User Manual. Get in touch with us any time, we're here to help.