1 00:00:03,200 --> 00:00:08,684 Welcome to this demonstration on how to change the CT ratio, or primary 2 00:00:08,684 --> 00:00:14,478 current setting, on a SATEC EM133-XM meter. In this example, we've chosen a 3 00:00:14,478 --> 00:00:20,426 two hundred and fifty amp CT with a five amp secondary. We'll enter, save and 4 00:00:20,426 --> 00:00:22,975 check two hundred and fifty amps. 5 00:00:24,700 --> 00:00:31,675 First, check your meter's current input rating. This example uses the five amp 6 00:00:31,675 --> 00:00:38,649 version. Other versions need a matching CT or sensor. For HACS, only use SATEC 7 00:00:38,649 --> 00:00:45,624 supplied High Accuracy Current Sensors. Please consult SATEC if you're unsure. 8 00:00:47,200 --> 00:00:52,429 Let's get familiar with the two buttons. The triangle is SCROLL. The bent 9 00:00:52,429 --> 00:00:57,659 arrow is SELECT and ENTER. A short press means press and release straight 10 00:00:57,659 --> 00:01:02,744 away. For an ordinary ENTER action, hold for around three seconds, then 11 00:01:02,744 --> 00:01:03,318 release. 12 00:01:05,200 --> 00:01:10,030 To open programming from the normal display, we need a longer hold. Hold 13 00:01:10,030 --> 00:01:15,262 SELECT and ENTER for more than five seconds, then release. The password screen 14 00:01:15,262 --> 00:01:16,067 will appear. 15 00:01:17,200 --> 00:01:22,748 The default password is nine, if it hasn't been changed. Give SCROLL nine 16 00:01:22,748 --> 00:01:28,524 quick presses to set the last digit to nine. Now hold ENTER for around three 17 00:01:28,524 --> 00:01:34,148 seconds, then release. If you don't have the configured password, ask your 18 00:01:34,148 --> 00:01:36,504 administrator or contact SATEC. 19 00:01:38,200 --> 00:01:44,395 Next, use SCROLL to move from Reset, through RTC, to Basic. Hold ENTER for 20 00:01:44,395 --> 00:01:49,250 around three seconds, then release to open the Basic menu. 21 00:01:51,200 --> 00:01:56,845 Continue with short SCROLL presses through the wiring configuration, PT ratio 22 00:01:56,845 --> 00:02:02,343 and PT factor, until CT appears. The number below is the present CT primary 23 00:02:02,343 --> 00:02:02,929 current. 24 00:02:04,200 --> 00:02:08,918 Now give SELECT a quick press to edit the number. The digits appear with 25 00:02:08,918 --> 00:02:13,636 leading zeros. Short SELECT presses move to the next digit, while SCROLL 26 00:02:13,636 --> 00:02:18,485 increases that digit. We'll change the example's existing five amps to two 27 00:02:18,485 --> 00:02:19,664 hundred and fifty. 28 00:02:21,200 --> 00:02:26,894 Move to the hundreds digit and set it to two. Move to the tens digit and set 29 00:02:26,894 --> 00:02:32,738 it to five. Then move to the units digit and continue from five, through nine, 30 00:02:32,738 --> 00:02:37,683 to zero. Check that the display reads zero, zero, two, five, zero. 31 00:02:41,200 --> 00:02:46,382 When it matches, hold ENTER for around three seconds, then release to save. 32 00:02:46,382 --> 00:02:51,565 Check that CT now shows two hundred and fifty. Our two hundred and fifty to 33 00:02:51,565 --> 00:02:56,747 five amp CT has a fifty to one ratio, but we enter the primary current, two 34 00:02:56,747 --> 00:02:58,336 hundred and fifty amps. 35 00:03:00,700 --> 00:03:06,038 Finally, hold ENTER for around three seconds and release to return to the main 36 00:03:06,038 --> 00:03:11,170 menu. Give SELECT a short press to choose Exit. Hold ENTER again for around 37 00:03:11,170 --> 00:03:15,276 three seconds, then release to return to the normal display. 38 00:03:18,700 --> 00:03:24,243 Great work! You've changed the CT primary current and checked the saved 39 00:03:24,243 --> 00:03:30,176 setting. Scan the code for the EM132/EM133 User Manual. Get in touch with us 40 00:03:30,176 --> 00:03:32,440 any time, we're here to help.