# PRO PM335 quick start guide

> PRO PM335 quick start guide as a web page: PRO PM335 Quick Start Manual. Transcribed from SATEC document BG0635 REV.A2; drawings are in the PDF.

Source page: https://satec-global.com.au/support/guides/pm335-pro-quick-start/

---

PRO PM335 · QUICK START GUIDE

# PRO PM335 quick start guide

PRO PM335 Quick Start Manual

Transcribed from the SATEC document [PRO PM335 Quick Start Manual, BG0635 REV.A2, date not printed](https://satec-global.com.au/documentation/PRO-PM335-quickstart.pdf) (PDF, 4 pages, 379 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## PRO PM335 Quick Start Manual

This guide instructs the user on installation, wiring, configuring and operating the PM335 multi-meter. This guide does not substitute the full user manual or the detailed safety instructions. To download the manual and other related material, please visit our website: www.satec-global.com

**Warning**Warning! Only a licensed electrician may perform installations and wiring of the PM335.

Figure 1: PM335 front panel. Drawing not reproduced on this page. [See page 1 of the PDF](https://satec-global.com.au/documentation/PRO-PM335-quickstart.pdf#page=1).

- Diagnostic message LED
- Graphic display
- Wh/kvarh Pulse LED
- Navigation buttons
- Load bar graph
- IR COM port
- USB port

## Installation

The PM335 is designed for 4-inch round / 92x92mm square panel mounting.

Please note to leave room for future expansion: when a basic units (no modules), it is recommended to maintain a minimal gap of 30-100mm to the right (when facing front panel) of the unit, allowing future installation of additional detachable SATEC modules (depending on number of added modules: 17.8mm each).

## Electrical Connections

The following steps correspond with a low-voltage three phase network (figure 2):

- Make sure all power sources are disconnected.
- Make sure that your designated power supply corresponds with the unit's rating.
- Connect the power supply (bottom-left of back panel) via 12 AWG wires and a designated circuit breaker.
- Standard external current transformers: connect the CT's (14 AWG minimum) "+" pole to the device's I1+ current input (unit’s bottom right of rear end, as in figure 2) and the "-" pole to the adjacent I1- current input. Repeat this for the following two phases, I2 and I3. Verify proper polarity in your connections in accordance with the arrow printed on the external CTs. “HACS” CTs: connect the red/white wire to the "+" terminal and the black/orange (colors vary according to the CT model) wire to the "-" terminal.
- Connect the voltage measurement inputs (22-12 AWG; bottom-center of rear end).
- Connect the com wire (26-12 AWG, shielded) to COM1 (RS485, top-left of rear-end).
- Power-on the unit.

Figure 2: Electrical wiring. Drawing not reproduced on this page. [See page 2 of the PDF](https://satec-global.com.au/documentation/PRO-PM335-quickstart.pdf#page=2).

## Basic Configuration and Operation

The PRO PM335 is operated via the LCD display, 2 LEDs and 4 pushbuttons (figure 1: front panel).

When powered on, the device will default to displaying voltages, for basic setup back up (<- button) to the home screen navigate with arrows to “setup” (select with ✓), enter default password (“9”) and select (“apply”). Open “general setup” to reveal “basic setup” for configuration.

Figure 3: Screenshot sequence for basic setup. Drawing not reproduced on this page. [See page 3 of the PDF](https://satec-global.com.au/documentation/PRO-PM335-quickstart.pdf#page=3).

## Connecting Optional SATEC Modules

**Warning**DO NOT HOT-SWAP. When adding modules, make sure the unit is disconnected from power supply

- DO NOT HOT-SWAP. When adding modules, make sure the unit is disconnected from power supply
- Remove cover (sticker on right side of unit) to reveal port
- Attach the module tightly and tighten the clips
- Power on the unit

## General Information and System Defaults

- Default password: 9
- Default IP: 192.168.0.203 (ETH1)
- Default current mode (HACS model): Alternating Current (AC)
- Default serial com settings (RS485): 19,200 Baudrate; address = 1
- For convenient configuration please use SATEC’s PAS engineering software, connecting your PC to the USB port (type C) at the right side of the front panel To download PAS (free): www.satec-global.com/power-analysis-software make sure to update .exe file with the most recent update available on webpage

## Downloads and related

- [Download the PDF (BG0635 REV.A2, 379 KB)](https://satec-global.com.au/documentation/PRO-PM335-quickstart.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-85965487df33/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/em235-pro/)
- [All quick start guides as web pages](https://satec-global.com.au/support/guides/)

Questions about this document? Use the [contact form](https://satec-global.com.au/contact/).