# EM132 and EM133 quick start guide

> EM132 and EM133 quick start guide as a web page: Quick Start Guide EM132-133 expertmeter™. Transcribed from SATEC document BG0504 REV.A3; drawings are in the PDF.

Source page: https://satec-global.com.au/support/guides/em132-133-quick-start/

---

EM132 · QUICK START GUIDE

# EM132 and EM133 quick start guide

Quick Start Guide EM132-133 expertmeter™

Transcribed from the SATEC document [EM132-133 Quick Start Guide, BG0504 REV.A3, date not printed](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf) (PDF, 10 pages, 1231 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Mechanical Installation

Figure 1: Instrument Dimensions. Drawing not reproduced on this page. [See page 2 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=2).

Figure 2: Mounting the EM13X on DIN Rail or on flat surface. Drawing not reproduced on this page. [See page 3 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=3).

Use flat screwdriver to disassemble the EM133 from the rail, by inserting the screwdriver to the plastic window to pull down the black plastic DIN RAIL retainer

**Warning**IMPORTANT! Only qualified personnel can perform setup. All incoming power sources must be turned off during installation. During operation of the Powermeter, hazardous voltages are present on the input terminals. Failure to observe precautions can result in serious or even fatal injury, or damage to equipment. Please refer to the installation and operation manual for further information.

## Typical Electrical Installation

Figure 3:Common Wiring Mode: 4LL3 or 4Ln3. Drawing not reproduced on this page. [See page 4 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=4).

Wiring configurations
| Wiring Configuration |Setup Code |
| 3-wire 2-element Direct connection using 2 CTs |3dir2 |
| 4-wire Wye 3-element direct connection using 3 CTs |4Ln3 or 4LL3 |
| 4-wire Wye 3-element connection using 3 PTs, 3 CTs |4Ln3 or 4LL3 |
| 3-wire 2-element Open Delta connection using 2 PTs, 2 CTs |3OP2 |
| 4-wire Wye 2½ -element connection using 2 PTs, 3 CTs |3Ln3 or 3LL3 |
| 3-wire 2½ -element Open Delta connection using 2 PTs, 3 CTs |3OP3 |
| 4-wire 3-element Delta direct connection using 3 CTs |4Ln3 or 4LL3 |
| 3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs |3bLn3 or 3bLL3 |

Refer to the Installation and operation manual for the wiring schematics diagrams

## Electrical Installation

Figure 4: CT Wiring options. Upper drawing: EM133-SE Model, Currents – direct connection with internal CT 50A (100A). Lower drawing: Currents – Transformer connection with External CT 40mA secondary, sensor leads marked RED (+) and ORANGE (-). Drawing not reproduced on this page. [See page 5 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=5).

## Module Installation

This section applies to the I/O and Communication modules.

Figure 5: PM130 PLUS modules (MODULE 4DI/2DO, MODULE ETHERNET, MODULE 4 ANALOG OUT). Drawing not reproduced on this page. [See page 6 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=6).

Figure 6: Mounting module. Drawing not reproduced on this page. [See page 6 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=6).

Module Connector Cover. Remove Module Connector Cover before assembling module

Refer to the Installation and operation manual for the wiring schematics diagrams and setup parameters

**Warning**CAUTION! Before I/O Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.

## Basic Setup

All setups can be performed directly from the display panel or via communication ports using PAS communication software, except for Communications and Display setups, which must be performed directly at the instrument panel.

EM133 front panel with callouts: Alphanumeric LCD display, RS-485 COM1 port Activity LED, Navigation Buttons, IR COM3 port, Phrases presence LED, Wh/varh PULSE LED, Device Label ID. Drawing not reproduced on this page. [See page 7 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=7).

To set the CT Primary current, perform the following steps:

- Press ↵ for 5sec, until password no. blinks:
- Enter Password number using ▲, then press ↵ for 2sec then new display with blinking "Reset"
- Navigate by pressing shortly (less than 1sec) ▲ move to Basic setup
- Press ↵ for 2sec, until "Conf" blinks:
- Navigate by pressing shortly (less than 1sec) ▲ move to CT setup
- Press ↵ for 2sec, until "5000" blinks, then press shortly using ▲ to the desired value
- Press ↵ for 2sec, until "CT" blinks, then press ↵ for 2sec, until "Basic" blinks, then press ↵ for 2sec, until "Reset" blinks, press shortly using ▲ to move to blinking "Exit" and press ↵ for 2sec to return to initial screen

Display screenshots for each step (time and NORM screen, Enter Password, Reset/Basic/Exit, Basic Conf 4Ln3, Basic CT 5000). Drawing not reproduced on this page. [See page 7 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=7).

## Data Display: Navigating in Display Mode

The front panel has a simple interface that allows you to display numerous measurement parameters in up to 38 display pages. For easier reading, the parameters are divided into three groups; each group is accessible by pressing the ↵ key and each group page is accessible by pressing the ▲ key.

The initial display is as described below:

Initial display: time, date, NORM, T1. Drawing not reproduced on this page. [See page 8 of the PDF](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf#page=8).

First push on ↵ will display Energy measurement parameters, by pushing ▲ will navigate to imp., exp. active/reactive, etc …as described below:

- Act. Imp
- Act. Exp
- Rea. Imp
- Rea. Exp
- App.
- App. Imp
- App. Exp
- Rea. Q1
- Rea. Q2
- Rea. Q3
- Rea. Q4

Second push on ↵ will display MAX DMD parameters, by pushing ▲ will navigate to MAX DMD P, Q, S, I, etc …as described below:

- MAX. DMD P Imp
- MAX. DMD P Exp
- MAX. DMD Q Imp
- MAX. DMD Q Exp
- MAX. DMD S
- MAX. DMD I1
- MAX. DMD I2
- MAX. DMD I3
- MAX. DMD In
- MAX. DMD V1
- MAX. DMD V2
- MAX. DMD V3

Third push on ↵ will display Votage/Current measurements, by pushing ▲ will navigate to V (L-N), V (L-L), I, Power, PF, THD, TDD, F, etc …as described below:

- V1 / V2
- V3
- V12 / V23
- V31
- I1 / I2
- I3 / In
- P / Q
- S / PF
- V1 THD / I1 THD
- V2 THD / I2 THD
- V3 THD / I3 THD
- I1 TDD / I2 TDD
- I3 TDD
- V Unb / I Unb
- Freq
- V1 Ang / I1 Ang
- V2 Ang / I2 Ang
- V3 Ang / I3 Ang

## Basic Menu

Basic Menu
| Code |Parameter |Options |Description |
| ConF |Wiring mode |3OP2 |3-wire open delta using 2 CTs |
| | |4Ln3 |4-wire Wye using 3 PTs (default) |
| | |3dir2 |3-wire direct connection using 2 CTs |
| | |4LL3 |4-wire Wye using 3 PTs |
| | |3OP3 |3-wire open delta using 3 CTs |
| | |3Ln3 |4-wire Wye using 2 PTs |
| | |3LL3 |4-wire Wye using 2 PTs |
| | |3bLn3 |3-wire Broken delta using 2 PTs, 3 CTs |
| | |3bLL3 |3-wire Broken delta using 2 PTs, 3 CTs |
| Pt Ratio |PT ratio |1.0∗ - 6,500.0 |The potential transformer ratio |
| Pt Factor | | | |
| Ct |CT primary current |1-50,000A (5*) |The primary rating of the current transformer |
| PowDmdPer |Power demand period |1, 2, 5, 10, 15*, 20, 30, 60, E |The length of the period for power demand calculations, in minutes. E = external synchronization |
| Num.Per. |Number of power demand periods |1-15 (1*) |The number of demand periods to be averaged for sliding window demands 1 = block interval demand calculation |
| ADmdPer. |Ampere/Volt demand period |0-1800 (900*) |The length of the period for volt/ampere demand calculations, in seconds. 0 = measuring peak current |
| Frequency |Nominal frequency |25, 50, 60, 400 (Hz) |The nominal power utility frequency |
| MaxDmdLd | | | |

- Default setup

## Communication Port Menu: COM1 setting

COM1 setting
| Code |Parameter |Options |Description |
| Protocol |Communications protocol |ASCII∗, rtu, dnP3 |ASCII, Modbus RTU (default) or DNP3.0 protocol |
| Interface |Interface standard |485 |RS-485 interface (default) |
| Address |Address |ASCII: 0 (default) - 99, Modbus: 1 (default) -247, DNP3.0: 0 (default) -255 | |
| Baud Rate |Baud rate |110, 300, 600, 1200, 2400, 4800, 9600 (default), up to 115,200 bps | |
| Data/Party |Data format |7E, 8E (7/8 bits, even parity), 8n (default) (8 bits, no parity) | |
| Snd.Delay | | | |

## Input and Output Ratings

Input and Output Ratings
| 3 voltage inputs |57/98-400/690 VAC |DIRECT INPUT - Nominal: 690V line-to-line voltage, 828V maximum; 400V line-to-neutral, 480V maximum - Burden: <0.5 VA. INPUT USING PT - Burden: <0.15 VA |
| 3 voltage inputs |Voltage input terminals |4 x Maximum wire section: 2.5 mm² (12 AWG) |
| 3 current nputs (Galvanic isolation) |/5A(10A) |INPUT VIA CT with 5A secondary output - Burden: <0.2VA, Overload withstands: 20A RMS continuous, 300A RMS for 0.5 second. |
| 3 current nputs (Galvanic isolation) |/1A(2A) |INPUT VIA CT with 1A secondary output - Burden: <0.05VA, Overload withstands: 3A RMS continuous, 80A RMS for 0.5 second. |
| 3 current nputs (Galvanic isolation) |50A(100A) |INPUT VIA CT with 50A direct connection - Burden: < 0.05VA, Overload withstands: 120A RMS continuous, 2000A RMS for 0.5 second. |
| 3 current nputs (Galvanic isolation) |40mA:(optional) |INPUT VIA CT with 40mA secondary output, using external CT – Split Core CT or Solid Core CT – primary 100-1200A maximum rating |
| 3 current nputs (Galvanic isolation) |Current input terminals |3 x Maximum wire section: 16 mm² |
| Communication port COM1 |EIA RS-485 standard |Optically isolated, max. speed 115.2Kb/s |
| Communication port COM1 |COM1 terminals |3 x Maximum wire section: 2.5 mm² |
| Communication port COM3 |IR COM port |Infra Red, max. speed 38.4Kb/s |
| Power Supply (Galvanically isolated) |40-300V AC/DC (standard) |50/60 Hz - 9VA |
| Power Supply (Galvanically isolated) |Power Supply input terminals |3 x Maximum wire section: 2.5 mm² |
| MODULE 2DI/DO |DIGITAL INPUT x 2 optically isolated inputs |Dry contact, internally wetted @ 5VDC |
| MODULE 2DI/DO |DIGITAL OUTPUT x 1 |0.15A/250 VAC - 400 VDC, 1 contact (SPST Form A) |
| MODULE 2DI/DO |2DI/DO terminals |5 x Maximum wire section: 2.5 mm² |
| MODULE 4DI/2DO (Optional) |DIGITAL INPUT x 2 optically isolated inputs |Dry contact, internally wetted @ 24VDC |
| MODULE 4DI/2DO (Optional) |DIGITAL OUTPUT x 2 EMR |5A/250 VAC; 5A/30 VDC, 1 contact (SPST Form A) |
| MODULE 4DI/2DO (Optional) |DIGITAL OUTPUT x 2 SSR |0.15A/250 VAC - 400 VDC, 1 contact (SPST Form A) |
| MODULE 4DI/2DO (Optional) |4DI/2DO terminals |9 x Maximum wire section: 2.5 mm² |
| MODULE 4 AO (Optional) |ANALOG OUT x 4 optically isolated outputs (4 different options) |±1 mA, maximum load 5 kΩ (100% overload) |
| MODULE 4 AO (Optional) |ANALOG OUT x 4 optically isolated outputs (4 different options) |0-20 mA, maximum load 510 Ω |
| MODULE 4 AO (Optional) |ANALOG OUT x 4 optically isolated outputs (4 different options) |4-20 mA, maximum load 510 Ω |
| MODULE 4 AO (Optional) |ANALOG OUT x 4 optically isolated outputs (4 different options) |0-1 mA, maximum load 5 k Ω (100% overload) |
| MODULE 4 AO (Optional) |4 AO terminals |5 x Maximum wire section: 2.5 mm² |
| Communication port COM2 (Optional) |Ethernet |10/100 Base T, auto adaptation speed, Max. speed 100Mb/s |
| Communication port COM2 (Optional) |ETH connector |Shielded RJ45 cable |
| Communication port COM2 (Optional) |Profibus |Max. speed 12 Mb/s |
| Communication port COM2 (Optional) |Profibus terminals |5 x Maximum wire section: 2.5 mm2 (12 AWG) or using terminal to DB9 converter: P/N AC0153 REV.A2 |
| Communication port COM2 (Optional) |EIA RS-232-422/485 standard |Optically isolated, max. speed 115.2Kb/s – to be connected to GPRS modem if ordered |
| Communication port COM2 (Optional) |COM2 terminals |5 x Maximum wire section: 2.5 mm² And DB9 connector |

## Downloads and related

- [Download the PDF (BG0504 REV.A3, 1231 KB)](https://satec-global.com.au/documentation/EM132-133-quick-start-guide.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-7cf34c8c891e/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/em132/)
- [All quick start guides as web pages](https://satec-global.com.au/support/guides/)
- [Does the EM132 have a replaceable clock backup battery?](https://satec-global.com.au/support/articles/em132-clock-backup-battery/)
- [Which EM132 model and input variant do I have?](https://satec-global.com.au/support/articles/em132-identify-model-variant/)
- [What should I record before asking for help with an EM132?](https://satec-global.com.au/support/articles/em132-support-evidence/)

Questions about this document? Use the [contact form](https://satec-global.com.au/contact/).