# SCT-DP split core current transformers datasheet: specifications and ordering codes

> SCT-DP datasheet as a web page: Split core current transformers for retrofit energy metering. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/sct-dp-split-core-ct/

---

SCT-DP · DATASHEET

# SCT-DP split core current transformers datasheet

Split core current transformers for retrofit energy metering.

Transcribed from the SATEC Australia datasheet [TBV1.0, 30 September 2026](https://satec-global.com.au/documentation/SATEC-SCT-DP-Split-Core-Current-Transformers-Datasheet-TBV1-0.pdf) (PDF, 6 pages, 1256 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

SCT-DP split core current transformers are designed for fast installation in new and existing low voltage networks. The core opens so the transformer can be fitted around an existing cable or busbar without disconnecting the primary conductor. This suits retrofit energy metering, sub-metering and power monitoring projects where a shutdown is costly or impractical.

Five window sizes cover primary currents from 100A to 5000A with a 5A or 1A secondary. Accuracy Class 0.5, 1.0 and 3.0 are available depending on ratio and burden, with rated outputs from 1.5VA to 30VA. Busbar centring devices hold the conductor in position and the range is designed to IEC 61869-2 and AS 61869.2.

## Main features

- Split core design fits around existing cables and busbars
- No need to disconnect the primary conductor to install
- Primary currents from 100A to 5000A
- 5A or 1A secondary output
- Accuracy Class 0.5, 1.0 or 3.0 (subject to burden)
- Rated output from 1.5VA to 30VA
- Five window sizes from 20 × 30mm to 80 × 160mm
- Busbar centring devices for secure positioning
- Insulation level 0.72/3kV
- Short time thermal current Ith = 100 × In
- Instrument security factor FS < 5
- Suitable for 50Hz and 60Hz networks
- Designed to IEC 61869-2 and AS 61869.2

## Feature capabilities

### SCT-DP-23

- Compact 20 × 30mm window for cables. Ratios 100/5A to 400/5A.

### SCT-DP-58 and SCT-DP-88

- 50 × 80mm and 80 × 80mm windows. Ratios 250/5A to 1000/5A.

### SCT-DP-812 and SCT-DP-816

- 80 × 120mm and 80 × 160mm windows for busbars. Ratios 500/5A to 5000/5A.

### Split Core Retrofit Installation

- Core opens and closes around the existing conductor
- No need to disconnect cables or busbars to fit the CT
- Avoids the primary circuit interruption that conventional CTs require
- Saves installation time and cost on switchboard upgrades
- Ideal for adding metering to sites already in service

### Wide Window Range

- SCT-DP-23: 20 × 30mm window
- SCT-DP-58: 50 × 80mm window
- SCT-DP-88: 80 × 80mm window
- SCT-DP-812: 80 × 120mm window
- SCT-DP-816: 80 × 160mm window for large busbars

### Metering Accuracy

- Accuracy Class 0.5, 1.0 and 3.0 depending on ratio and burden
- Rated output from 1.5VA to 30VA
- Higher ratios support higher burdens for longer secondary runs
- Select ratio, class and VA from the ratings tables on page 5

### Busbar Centring and Mounting

- Centring devices hold the busbar in the middle of the window
- Removable core section secured with fixing screws
- Base fixing holes for secure mounting
- Suits both cable and busbar installations

### Safety and Protection

- Insulation level 0.72/3kV
- Short time thermal current Ith = 100 × In
- Instrument security factor FS < 5 helps protect connected meters during faults
- Never open circuit the secondary while the primary is energised
- Installation by a qualified electrician to site safety procedures

### Typical Applications

- Retrofit sub-metering in commercial buildings
- Energy monitoring upgrades in industrial plants
- Data centre and critical power monitoring
- Water, wastewater and council infrastructure
- Sites where a shutdown is not practical

### Complete SATEC Metering System

- Pairs with SATEC power meters and energy meters
- Meter data can be viewed and managed in the Expertpower platform
- New installations: CT-MES solid core CTs
- High accuracy options: HACS current sensors

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Electrical
| Primary current |100A to 5000A |
| Secondary current |5A or 1A |
| Frequency |50Hz / 60Hz |
| Insulation level |0.72/3kV |
| Short time thermal current |Ith = 100 × In |

Accuracy and output
| Accuracy class |0.5, 1.0, 3.0 (subject to burden) |
| Rated output |1.5VA to 30VA |
| Instrument security factor |FS < 5 |
| Design standard |IEC 61869-2, AS 61869.2 |

Construction
| Core type |Split core |
| Window sizes |20 × 30mm to 80 × 160mm |
| Overall size |89 × 111mm to 184 × 245mm |
| Weight |0.75kg to 4.30kg |
| Busbar centring |Centring devices included |

Installation
| Installation |Around existing cable or busbar |
| Fixing |Base fixing holes |
| Primary disconnection |Not required |

Model overview: SCT-DP-23
| Window A × B (mm) |20 × 30 |
| Ratio range (A) |100/5 to 400/5 |
| Accuracy classes |0.5, 1.0, 3.0 |
| Rated output (VA) |1.5 to 5 |
| Overall D × E (mm) |89 × 111 |
| Weight (kg) |0.75 |

Model overview: SCT-DP-58
| Window A × B (mm) |50 × 80 |
| Ratio range (A) |250/5 to 1000/5 |
| Accuracy classes |0.5, 1.0 |
| Rated output (VA) |2.5 to 5 |
| Overall D × E (mm) |114 × 145 |
| Weight (kg) |0.90 |

Model overview: SCT-DP-88
| Window A × B (mm) |80 × 80 |
| Ratio range (A) |250/5 to 1000/5 |
| Accuracy classes |0.5, 1.0 |
| Rated output (VA) |2.5 to 10 |
| Overall D × E (mm) |144 × 145 |
| Weight (kg) |1.05 |

Model overview: SCT-DP-812
| Window A × B (mm) |80 × 120 |
| Ratio range (A) |500/5 to 3000/5 |
| Accuracy classes |0.5, 1.0 |
| Rated output (VA) |2.5 to 20 |
| Overall D × E (mm) |144 × 185 |
| Weight (kg) |1.25 |

Model overview: SCT-DP-816
| Window A × B (mm) |80 × 160 |
| Ratio range (A) |1000/5 to 5000/5 |
| Accuracy classes |0.5, 1.0 |
| Rated output (VA) |10 to 30 |
| Overall D × E (mm) |184 × 245 |
| Weight (kg) |4.30 |

Ratio ranges shown for 5A secondary. For 1A secondary ratings please contact SATEC. Dimensions in mm.

Dimensions: SCT-DP-23
| A |20 |
| B |30 |
| C |51 |
| D |89 |
| E |111 |
| F |34 |
| G |47 |
| H |40 |
| I |32 |
| Weight (kg) |0.75 |

All SCT-DP models share the same construction. Window A × B sets the largest cable or busbar the transformer will accept. Dimensions are in millimetres.

Dimensions: SCT-DP-58
| A |50 |
| B |80 |
| C |78 |
| D |114 |
| E |145 |
| F |32 |
| G |32 |
| H |32 |
| I |33 |
| Weight (kg) |0.90 |

Dimensions: SCT-DP-88
| A |80 |
| B |80 |
| C |108 |
| D |144 |
| E |145 |
| F |32 |
| G |32 |
| H |32 |
| I |33 |
| Weight (kg) |1.05 |

Dimensions: SCT-DP-812
| A |80 |
| B |120 |
| C |108 |
| D |144 |
| E |185 |
| F |32 |
| G |32 |
| H |32 |
| I |33 |
| Weight (kg) |1.25 |

Dimensions: SCT-DP-816
| A |80 |
| B |160 |
| C |120 |
| D |184 |
| E |245 |
| F |52 |
| G |47 |
| H |52 |
| I |38 |
| Weight (kg) |4.30 |

A × B = window (aperture). D × E = overall width and height. Side and top view dimensions H, I, 32, 50 and 65 as per drawing.

Ratings: SCT-DP-23, rated output (VA) by accuracy class and ratio (A)
| 100/5 |Class 0.5: n/a · Class 1.0: n/a · Class 3.0: 2.5 |
| 150/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 200/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 250/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 300/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |
| 400/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |

Ratings: SCT-DP-58, rated output (VA) by accuracy class and ratio (A)
| 250/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 300/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 400/5 |Class 0.5: 2.5 · Class 1.0: n/a · Class 3.0: n/a |
| 500/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |
| 600/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |
| 750/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |
| 800/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |
| 1000/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |

Ratings: SCT-DP-88, rated output (VA) by accuracy class and ratio (A)
| 250/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 300/5 |Class 0.5: 2.5 · Class 1.0: n/a · Class 3.0: n/a |
| 400/5 |Class 0.5: 2.5 · Class 1.0: n/a · Class 3.0: n/a |
| 500/5 |Class 0.5: 2.5 · Class 1.0: n/a · Class 3.0: n/a |
| 600/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |
| 750/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |
| 800/5 |Class 0.5: 5 · Class 1.0: n/a · Class 3.0: n/a |
| 1000/5 |Class 0.5: 5 · Class 1.0: 10 · Class 3.0: n/a |

Ratings: SCT-DP-812, rated output (VA) by accuracy class and ratio (A)
| 500/5 |Class 0.5: 2.5 · Class 1.0: 10 · Class 3.0: n/a |
| 600/5 |Class 0.5: 2.5 · Class 1.0: 10 · Class 3.0: n/a |
| 750/5 |Class 0.5: 2.5 · Class 1.0: 10 · Class 3.0: n/a |
| 800/5 |Class 0.5: 2.5 · Class 1.0: 10 · Class 3.0: n/a |
| 1000/5 |Class 0.5: 5 · Class 1.0: 15 · Class 3.0: n/a |
| 1200/5 |Class 0.5: 7.5 · Class 1.0: 20 · Class 3.0: n/a |
| 1250/5 |Class 0.5: 7.5 · Class 1.0: 20 · Class 3.0: n/a |
| 1500/5 |Class 0.5: 10 · Class 1.0: 20 · Class 3.0: n/a |
| 1600/5 |Class 0.5: 10 · Class 1.0: 20 · Class 3.0: n/a |
| 2000/5 |Class 0.5: 10 · Class 1.0: 20 · Class 3.0: n/a |
| 2500/5 |Class 0.5: 15 · Class 1.0: 20 · Class 3.0: n/a |
| 3000/5 |Class 0.5: 20 · Class 1.0: 20 · Class 3.0: n/a |

Ratings: SCT-DP-816, rated output (VA) by accuracy class and ratio (A)
| 1000/5 |Class 0.5: 10 · Class 1.0: 20 · Class 3.0: n/a |
| 1500/5 |Class 0.5: 15 · Class 1.0: 25 · Class 3.0: n/a |
| 2000/5 |Class 0.5: 15 · Class 1.0: 25 · Class 3.0: n/a |
| 2500/5 |Class 0.5: 15 · Class 1.0: 25 · Class 3.0: n/a |
| 3000/5 |Class 0.5: 20 · Class 1.0: 30 · Class 3.0: n/a |
| 4000/5 |Class 0.5: 20 · Class 1.0: 30 · Class 3.0: n/a |
| 5000/5 |Class 0.5: 20 · Class 1.0: 30 · Class 3.0: n/a |

Rated output in VA for each ratio and accuracy class with a 5A secondary. n/a means the class is not offered at that ratio. Accuracy class subject to rated burden (p. 6).

## Standards compliance

### Instrument Transformers

- IEC 61869-2: Additional requirements for current transformers
- AS 61869.2: Australian adoption of IEC 61869-2

### Legacy Standards

- IEC 60044-1: Instrument transformers, current transformers
- AS 60044.1: Current transformers
- BS 7626: Specification for current transformers

### Insulation and Thermal

- Insulation level 0.72/3kV
- Short time thermal current Ith = 100 × In
- Instrument security factor FS < 5

## Ordering information

MODEL · RATIO · CLASS · RATED OUTPUT · OPTIONS

Model
| 20 × 30mm window |SCT-DP-23 |
| 50 × 80mm window |SCT-DP-58 |
| 80 × 80mm window |SCT-DP-88 |
| 80 × 120mm window |SCT-DP-812 |
| 80 × 160mm window |SCT-DP-816 |

Ratio
| Primary 100A to 5000A |e.g. 600 |
| Secondary 5A |/5 |
| Secondary 1A (contact SATEC) |/1 |

Accuracy class
| Class 0.5 |0.5 |
| Class 1.0 |1.0 |
| Class 3.0 (SCT-DP-23 only) |3.0 |

Rated output
| Per ratings table, page 5 |1.5VA to 30VA |

Ordering example: SCT-DP-58 · 600/5 · Class 0.5 · 5VA

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 1256 KB)](https://satec-global.com.au/documentation/SATEC-SCT-DP-Split-Core-Current-Transformers-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-c3b086f17420/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).