# PTS pole-top MV voltage and current sensor datasheet: specifications and ordering codes

> PTS datasheet as a web page: Pole-top MV voltage and current sensors for Smart Grid monitoring. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/pts-pole-top-sensors/

---

PTS · DATASHEET

# PTS pole-top MV voltage and current sensor datasheet

Pole-top MV voltage and current sensors for Smart Grid monitoring.

Transcribed from the SATEC Australia datasheet [TBV1.0, 29 September 2026](https://satec-global.com.au/documentation/Pole-Top-Sensors-PTS-Datasheet-TBV1-0.pdf) (PDF, 4 pages, 747 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

SATEC Pole-Top Sensors (PTS) are line post insulators with built-in voltage and current sensing for medium voltage distribution networks. They replace existing pole insulators and install without cutting the line. Utilities gain real-time visibility of overhead feeders for distribution automation and Smart Grid programmes.

Each sensor produces a low-level, non-hazardous signal instead of conventional CT and VT secondaries. Paired with the SATEC PM174 or PM175 power quality analyser and calibrated as a system, the sensors deliver Class 0.5S measurements along with waveforms, harmonics and phasors from remote pole locations.

**PTS 15**: Pole-top sensor for 15kV networks. 110kV impulse (BIL) rating.

**PTS 25**: Pole-top sensor for 25kV networks. 150kV impulse (BIL) rating.

**PTS 35**: Pole-top sensor for 35kV networks. 200kV impulse (BIL) rating.

## Main features

- Voltage and current sensing in one line post insulator
- Replaces existing pole insulators
- Installs with no line cutting
- 15kV, 25kV and 35kV insulation classes
- Linear outputs up to fault levels
- Non-hazardous voltage on the signal output
- 600A:10V current signal output ratio
- Class 0.5S system accuracy with PM174 or PM175 calibration
- Completely sealed against moisture
- Anti-tracking polymer concrete construction
- Operating range of -40°C to +65°C
- Suits aluminium and copper conductors

## Feature capabilities

### Sensor design

- Compact, economical power line sensing
- Voltage (PT) and current (CT) sensing combined in the insulator
- Linear outputs up to fault levels
- Native sensor accuracy of 2% for current and 1% for voltage
- Low-level, non-hazardous voltage on the output
- Completely sealed against moisture

### System accuracy and monitoring (with SATEC PM174 or PM175)

- Analyser inputs designed to interface with low-level sensor outputs
- Calibrated as a system to Class 0.5S accuracy
- Precise real-time measurements
- Waveform capture and power quality features
- Phasors and phase rotation
- Directional harmonics and neutral currents
- Local display and on-board memory for data redundancy

### Distribution network management

- Line losses and load balance
- Capacitor controls and voltage regulation
- Outage detection and fault location
- Harmonics monitoring
- Power theft detection
- Demand reduction during peak load times

### Complete cabinet package

- Custom SATEC enclosure for the PM174 or PM175 input connections
- Communications modem for real-time data to SCADA
- Supplied as a complete pole-mounted package
- Expandable as monitoring needs grow

### Communications and integration

- DNP3 protocol for utility SCADA integration
- Real-time data from remote pole locations
- Monitor, coordinate and operate distribution systems in real time
- Waveform, harmonic and power quality data delivered to the control room

### Software support

- Power Analysis Software (PAS) to program and monitor the PM174 or PM175
- Expertpower web platform for energy management and power quality analysis

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Ratings by model: PTS 15
| Insulation class |15kV |
| Impulse (BIL) |110kV |
| Leakage distance |41.6 cm (16.4 in) |
| Dry arc distance |22.3 cm (8.8 in) |
| Corona (extinction) |11kV |
| Low frequency dry flashover |80kV |
| Low frequency wet flashover |60kV |
| Overall height |33.5 cm (13.2 in) |
| Cantilever strength (ultimate) |1270 kg (2800 lb) |
| Weight |17.6 kg (39 lb) |
| Shipping weight |20 kg (44 lb) |

Ratings by model: PTS 25
| Insulation class |25kV |
| Impulse (BIL) |150kV |
| Leakage distance |62.2 cm (24.5 in) |
| Dry arc distance |32 cm (12.6 in) |
| Corona (extinction) |19kV |
| Low frequency dry flashover |110kV |
| Low frequency wet flashover |85kV |
| Overall height |42.4 cm (16.7 in) |
| Cantilever strength (ultimate) |1270 kg (2800 lb) |
| Weight |22.2 kg (49 lb) |
| Shipping weight |24.5 kg (54 lb) |

Ratings by model: PTS 35
| Insulation class |35kV |
| Impulse (BIL) |200kV |
| Leakage distance |89.6 cm (35.3 in) |
| Dry arc distance |41.4 cm (16.3 in) |
| Corona (extinction) |26kV |
| Low frequency dry flashover |125kV |
| Low frequency wet flashover |100kV |
| Overall height |52.8 cm (20.8 in) |
| Cantilever strength (ultimate) |1270 kg (2800 lb) |
| Weight |26.7 kg (59 lb) |
| Shipping weight |29 kg (64 lb) |

Current signal output
| Ratio |600A:10V |
| Output burden/load |Calibrated for a 10 kΩ or greater load |
| Open circuit voltage |10V at 600A line current |

Voltage signal output
| Divider ratio |Depends on network |
| Output impedance |Calibrated for a 1 MΩ load |

Accuracy
| Sensor native accuracy |2% for current, 1% for voltage |
| With SATEC PM174 or PM175 calibration |Class 0.5S |

Operating temperature
| Temperature range |-40°C to +65°C (-40°F to +149°F) |

Conductor diameter range
| Conductor diameter |6.35 mm to 31.75 mm (0.25 in to 1.25 in) |
| Keeper |Two-sided keeper in aluminium (for aluminium conductor) or galvanised ductile iron (for copper conductor) |

Construction and installation
| Body material |Moulded from Polysil, a high dielectric strength, anti-tracking polymer concrete developed under an EPRI contract |
| Mounting |Vertical mounting only |
| Application limit |Not for dead-end use |
| Installation |Replaces an existing pole insulator with no line cutting |

## Ordering information

PTS

Model
| Pole-Top Sensor, line post voltage and current sensor |PTS |

Network voltage class
| For 15kV networks |15 |
| For 25kV networks |25 |
| For 35kV networks |35 |

**Example:** PTS 25 is a Pole-Top Sensor for a 25kV network.

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 747 KB)](https://satec-global.com.au/documentation/Pole-Top-Sensors-PTS-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-efa4e12f4ca7/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).