# PRO Series DC metering datasheet: specifications and ordering codes

> PRO Series DC datasheet as a web page: High accuracy DC power and energy metering. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/pro-series-dc/

---

PRO Series DC · DATASHEET

# PRO Series DC metering datasheet

High accuracy DC power and energy metering.

Transcribed from the SATEC Australia datasheet [TBV1.0, 16 September 2026](https://satec-global.com.au/documentation/PRO-Series-DC-Metering-Datasheet-TBV1-0.pdf) (PDF, 9 pages, 2622 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PRO Series DC power and energy meters are advanced DC meters, fully compliant and tested to the DC metering standard AS/IEC 62053-41. Available as the panel-mounted PRO-PM335 or DIN-rail PRO-EM235, the range suits battery energy storage systems, EV charging, solar and other DC applications that need revenue-grade measurement, alongside substation and industrial monitoring.

The PRO Series DC measurement system operates via Hall Effect sensors or SATEC’s UHACS (Flux Gate) current sensors, for up to three DC channel inputs, with a wide voltage input range from 10–820V DC standard, extendable to 1500V DC with SATEC’s Voltage Ratio Module (VRM). Dual Ethernet ports with daisy-chain Ethernet, RS-485 and an infrared port are built in, supporting Modbus, IEC 61850 and DNP3 protocols.

PRO-PM335-HACS-DC: Panel-mounted DC meter with a 3.5″ TFT colour display, measuring voltage, current, power, energy and demand with data logging capabilities.

PRO-EM235-HACS-DC: DIN-rail mounted DC meter with a 1.77″ TFT colour display, measuring voltage, current, power, energy and demand with data logging capabilities.

## Main features

- DC power and energy metering — volts, amps, power, energy and demand
- Up to three isolated DC channel inputs via Hall Effect or UHACS (Flux Gate) current sensors
- Wide-range voltage inputs — 10–820V DC standard, up to 1500V DC with SATEC’s Voltage Ratio Module (VRM)
- Four isolated DC current inputs up to 2500A DC
- Dual Ethernet ports, daisy-chain Ethernet, RS-485 and infrared port
- Modbus, IEC 61850 and DNP3 protocol support
- Up to 26 external digital triggers, with fault waveform and fast RMS trace capture
- 16GB memory for long-term waveform and data recording

## Feature capabilities

### DC power and energy metering

- Three isolated DC voltage inputs (10–820V DC), extendable up to 1500V DC via VRM
- DC voltage/current accuracy 0.5%
- Four isolated DC current inputs up to 2500A DC (via UHACS or Hall Effect sensors)
- Precise energy & power demand metering: TOU, 16 summary/TOU energy and demand registers, block and sliding demands, up to 64 energy sources
- 32 digital counters for pulses from external sources and internal events

### Event and data recording

- Event recorder for internal diagnostic events, control events and I/O operations
- 16 programmable data recorders, logging on a periodic basis or on any internal/external trigger
- Embedded programmable controller — 64 control setpoints, OR/AND logic, extensive triggers, cross-triggering between devices via Ethernet for synchronous event capture
- Up to sixteen triggering channels
- 16 programmable timers, from ½ cycle to 24 hours

### High precision time synchronisation

- SNTP
- 1 pps via digital input
- IRIG-B time-code input (future release)
- Real-time clock with battery backup and three-year retention
- Backup power supply unit

### Communications (standard)

- Dual Ethernet ports (10/100 Base-T, transformer-isolated), up to 10 simultaneous connections per port
- Daisy-chain Ethernet
- RS-485 optically isolated port, up to 115,200 bps
- Infrared port, front panel access with magnetic head
- USB 2.0 Type-C port

### Expertpower client and notifications

- Expertpower client for Modbus/TCP communication with a remote or local (stand-alone) SATEC Expertpower server
- TCP notification client to a remote Modbus/TCP server, on events or periodically, via any IP-enabled communication port
- Meter security — password protection for meter setups and accumulated data against unauthorised changes

### Optional built-in I/O ports

- 2 optically isolated digital inputs — 24V DC dry contact, 1 ms sampling rate
- 1 solid-state relay output — unlatched, latched and pulse operation, fail-safe for alarm notifications
- 1 optically isolated analogue input — configurable universal range

### Add-on modules (PRO Series modules only)

- 8DI — 8 optically isolated digital inputs, dry contact or 24/48/125/250V AC/DC wet
- 4RO — 4 relays, electromechanical or solid-state, with fail-safe alarm operation
- 4DI + 2RO combination module
- 4AO — 4 isolated universal analogue outputs
- Up to 4 expansion modules side by side; 3 modules requires an auxiliary power supply module

### Software support

- PAS — SATEC’s bundled configuration and data-acquisition tool, including waveforms, phasors and harmonics
- Expertpower — SATEC’s internet-based energy management software, with no client software installation required
- eXpertConnect™ App — mobile connection to the meter for on-site configuration, readings and diagnostics

### Applications

- Energy management and revenue metering
- SCADA-ready industrial automation
- Substation automation and industrial monitoring
- Renewable energy and SATEC data centre solutions

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Voltage inputs
| Operating range |10–820V DC (standard) |
| Extended range |Up to 1500V DC via SATEC Voltage Ratio Module (VRM) |
| Input impedance |4 MΩ |
| Isolation |4000V AC @ 1 min |
| Wire size |Up to 14 AWG (≤2.5 mm²) |

Current inputs — DC Hall Effect sensors
| HCS100-S |100A split-core |
| HCS1000 |1000A solid-core |
| HCS2000-S |2000A split-core |

Current inputs — UHACS (Flux Gate) sensors
| FCS-300 |300A |
| FCS-600 |600A |
| FCS-1000 |1000A |
| FCS-2500-13 |2500A |

Both Hall Effect and UHACS sensors require a separate power supply; the FCS-2500-13 UHACS sensor requires two power supplies connected in parallel.

Digital inputs (2 DI) — built-in, optional
| Contact type |Dry contacts, internally wetted @ 24V DC |
| Galvanic isolation |4000V AC @ 1 min |
| Internal power supply |24V DC |
| Scan time |1 ms |
| Connector type |Removable, 5 pins |
| Wire size |14 AWG (up to 1.5 mm²) |
| Terminal pitch |5 mm |

Digital output (1 DO) — solid-state relay
| Rating |0.15A/250V AC/DC, 1 contact (SPST Form A) |
| Galvanic isolation |4000V AC @ 1 min |
| Operate time |1 ms max. |
| Release time |0.25 ms max. |
| Update time |1 cycle |
| Connector type |Removable, 4 pins |
| Wire size |14 AWG (up to 1.5 mm²) |

Analogue input (1 AI)
| Range |Universal, -1mA to 20mA (configurable: ±1mA, 0–1mA, 0–20mA, 4–20mA, etc.) |
| Galvanic isolation |4000V AC @ 1 min |
| Scan time |1 ms |
| Accuracy |<0.5% FS |
| Connector type |Removable, 5 pins |
| Wire size |14 AWG (up to 1.5 mm²) |
| Terminal pitch |5 mm |

Add-on module — digital inputs (8 DI)
| Contact type |Dry contact @ 24V DC, or wet contact @ 250V DC (8DI only) |
| Sensitivity |Open >100 kΩ, closed <100 Ω |
| Galvanic isolation |4000V AC @ 1 min |
| Internal power supply |24V DC |
| Scan time |1 ms |
| Connector type |Removable, 2×5 pins |
| Wire size |Up to 14 AWG (≤1.5 mm²) |

Add-on module — digital outputs (4 DO)
| Electromechanical (option 1) |4 relays, 5A/250V AC or 5A/30V DC, 1 contact (SPST Form A); isolation 3000V AC (contacts–coil), 750V AC (open contacts) |
| Solid-state (option 2) |4 relays, 100mA/800V AC, 1 contact (SPST Form A); isolation 3000V AC @ 1 min (800V peak open contacts) |
| Operate / release time |5–10 ms max. / 5 ms max. |
| Wire size |14 AWG (up to 1.5 mm²) |

Digital inputs + outputs (4DI + 2RO)
| Combination module |4DI + 2RO, per the digital input and output specifications above |

Analogue outputs (4 AO)
| Ranges |±1mA, 0–20mA, 4–20mA, 0–1mA (max. load 10 kΩ or 510 Ω per range, 100% overload) |
| Accuracy |0.5% FS |
| Scan time |1 ms (manually or remotely programmed) |
| Wire size |Up to 14 AWG (≤1.5 mm²) |
| Terminals pitch |5 mm |

Power supply
| Rated input |57.7–277V AC @ 50/60 Hz, 48–290V DC |
| Tolerance |±15% |
| Burden |11VA @ V AC, 6VA @ V DC |
| Isolation |4000V AC @ 1 min |
| Wire size |Up to 14 AWG (≤1.5 mm²) |

Auxiliary power supply module — AC/DC
| Rated input |88–264V AC / 90–290V DC |
| Output |5W |
| Burden |15VA |
| Withstand |4kV AC @ 1 min |
| Wiring |L/+, N/- |
| Terminals pitch |5 mm |
| Wire size |Up to 12 AWG (≤2.5 mm²) |

Auxiliary power supply module — 24V DC
| Rated input |9–36V DC |
| Output |7W |
| Galvanic isolation |4000V AC @ 1 min |
| Isolation |4 kV |
| Terminals pitch |5 mm |
| Wire size |14 AWG (up to 1.5 mm²) |

Communication — serial
| Port |RS-485, optically isolated, up to 115,200 bps |
| Isolation |4000V AC @ 1 min |
| Supported protocols |Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101 |

Communication — Ethernet (dual / 2 ports)
| Port |Transformer-isolated 10/100 Base-T Ethernet, RJ45 |
| Supported protocols |Modbus/TCP (port 502), DNP3/TCP (port 20000), IEC 60870-5-104 (port 2404), IEC 61850 (port 102, SNTP) |
| Simultaneous connections |10 (5 Modbus/TCP + 5 DNP3/TCP) |
| Isolation |4000V AC @ 1 min |

Communication — infrared (IR)
| Port |Infrared COM port, front panel access with magnetic head |
| Supported protocols |Modbus RTU & DNP3, IEC 62056-21 (for local meter data exchange) |
| Isolation |4000V AC @ 1 min |

Communication — USB
| Port |Full-speed USB 2.0, Type-C connector |
| Isolation |4000V AC @ 1 min |
| Supported protocols |To be confirmed |

Log memory
| Capacity |16GB for long-term waveform and data recording |

Display
| PM335 |3.5″ LCD TFT colour display, 320×480 dots resolution |
| EM235 |1.77″ LCD TFT colour display, 120×160 dots resolution |

Environmental conditions
| Operating temperature |-40°C to +70°C (-40°F to 158°F) |
| Display operating temperature |-25°C to +70°C (-13°F to 158°F) |
| Storage temperature |-40°C to +85°C (-40°F to 185°F) |
| Humidity |0 to 95% RH, non-condensing |
| Degree of protection |IP51 |

Construction
| Weight |0.70kg (1.54 lb) |
| Dimensions (PM335) |108.6×74.7×113.3 mm |
| Dimensions (EM235) |89.5×72×90 mm |

Materials
| Case enclosure |Plastic PC/ABS blend |
| Display body |Plastic PC/ABS blend |
| Front panel |Plastic PC |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Labels |Polyester film (UL94-V0) |

## Standards compliance

### Electromagnetic immunity

- IEC 62052-11, CLC/TR 50579 (conducted disturbances 2–150kHz), IEEE C62.41 and C37.90.1
- IEC 61000-6-2
- IEC 61000-4-2 level 3: Electrostatic Discharge
- IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
- IEC 61000-4-4 level 3: Electrical Fast Transient
- IEC 61000-4-5 level 3: Surge
- IEC 61000-4-6 level 3: Conducted Radio Frequency
- IEC 61000-4-8: Power Frequency Magnetic Field
- ANSI/IEEE C37.90.1: Fast Transient SWC

### Environmental

- IEC 60529: Protection
- IEC 60068-2-1: Cold
- IEC 60068-2-2: Dry Heat
- IEC 60068-2-30: Damp Heat
- IEC 60068-2-5: Solar Radiation

### Accuracy

- AS/IEC 62053-22:2003, Class 0.2S
- IEC 62053-24:2014, Class 0.5S
- ANSI C12.20–2015, Class 10 (0.2%)

### Electromagnetic emission

- IEC 61000-6-4* Radiated/Conducted Class B
- IEC CISPR 22* Radiated/Conducted Class B
- Emission per EN 55011/22 Class B, FCC p.15 Class B

### Safety / construction

- IEC 61010, IEC 62052-11 & IEC 61557-12
- UL61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use – Part 1: General Requirements, Edition 3, Revision Date 07/19/2019
- CSA C22.2 No. 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use – Part 1: General Requirements, Edition 3, Revision Date 11/2018
- AC Impulse Insulation: meets IEC 62052-11 — 4000V AC for 1 minute, 6KV/500Ω @ 1.2/50 µs impulse
- IEC 60068-2-6: Vibration (sinusoidal)
- IEC 60068-2-27: Shock Test
- IEC 60068-2-75: Hammer Test
- AS 62052-11*

### Note

- * Meets standard requirements.

## Ordering information

MODEL – CURRENT – CALIBRATION – POWER – I/O – LANGUAGE – PROTOCOL

Model
| PM335 Panel-Mount |PRO-PM335 |
| EM235 DIN-Rail Mount |PRO-EM235 |
| Transducer Version |PRO-RPM035 |

Current inputs
| High Accuracy Current Sensors (HACS), 50/60Hz only |HACS |

Calibration for DC current (DC)
| DC |DC |

Power supply
| 88–320V AC / 40–290V DC |ACDC |

Built-in I/O
| 2×DI (dry contact) + 1×SSR output + 1×universal AI (-1mA to 20mA) |IOS |

Display language
| English |EN |

Optional protocols
| IEC 61850 Communication Protocol |850 |

### Expansion modules

Optional modules* — maximum of 3 modules
| 4 Relay Outputs – 250V/5A AC |EMR4 |
| 4 SSR Outputs – 250V/0.1A AC |SSR4 |
| 4 Digital Inputs (Dry Contact @ 24V DC) + 2 SSR Outputs |4DIOS-DRC |
| 4 Digital Inputs (Dry Contact @ 24V DC) + 2 EMR Outputs |4DIOR-DRC |
| 8 Digital Inputs – Dry Contact |DI8-DRC |
| 8 Digital Inputs – 24, 48, 125, 250V DC |DI8-24,48,125,250V |
| 4 Analogue Outputs; configurable range |4AO |

* Auxiliary power supply required when configured with 3 modules.

Auxiliary power supply — maximum of 1 module
| AUX. P.S. AC/DC – 88–264V AC / 90–290V DC |AUX-ACDC |
| 24V DC (9–36V DC) |AUX-24DC |

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 2622 KB)](https://satec-global.com.au/documentation/PRO-Series-DC-Metering-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-87fb22ca9cb6/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).