Advanced P-Class and M-Class phasor measurement unit for wide area monitoring.

Transcribed from the SATEC Australia datasheet [TBV1.0, 28 September 2026](https://satec-global.com.au/documentation/PMU-PRO-Phasor-Measurement-Unit-Datasheet-TBV1-0.pdf) (PDF, 8 pages, 938 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PMU PRO is an advanced phasor measurement unit built for distribution network operators, utilities, substations and renewable generators that need precise, time-aligned visibility of their grid. It measures synchronised voltage and current phasors, frequency and rate of change of frequency to IEEE C37.118.1 P-Class and M-Class performance, then streams that data over Ethernet via IEEE C37.118.2 or IEC 61850-9-2 sampled values.

Based on the familiar PRO Series look and feel, it combines 1 to 240 frames per second reporting and 1µs time stamp accuracy with IRIG-B or IEEE 1588 PTPv2 time synchronisation. Dual port Ethernet, RS-485, USB-C, a 1.77" colour display, 16GB of log memory and up to four side-by-side expansion modules complete a compact DIN rail package.

## Current input options

- 

### PMU PRO 5A

5A nominal current inputs for connection to standard secondary CTs.

- 

### PMU PRO 1A

1A nominal current inputs for 1A CT secondary circuits.

## Main features

- IEEE C37.118.1-2011, C37.118.1a-2014 and IEC/IEEE 60255-118-1:2018 P-Class and M-Class compliance
- Synchronised three-phase voltage, current and sequence phasors
- Synchronous frequency and ROCOF measurements
- Advanced IEEE C37.118.2 data streaming over UDP and TCP
- IEC 61850-9-2 multicast sampled value streaming
- Reporting rates from 1 to 200/240 frames per second at 50/60Hz
- Expected steady-state TVE below 0.05% and 1µs time stamp accuracy
- IRIG-B and IEEE 1588 PTPv2 time synchronisation
- Dual port Ethernet, RS-485 and USB-C communications
- Up to four expansion modules and 16GB log memory

## Feature capabilities

### Phasor measurement (P-Class and M-Class)

- IEEE C37.118.1-2011, IEEE C37.118.1a-2014 and IEC/IEEE 60255-118-1:2018 P-Class and M-Class performance compliance
- Three-phase voltage, current, and positive and negative sequence phasor measurements synchronised to a common UTC time reference
- IEEE C37.118.1 synchronous frequency and rate of change of frequency (ROCOF) measurements
- Expected steady-state total vector error (TVE) below 0.05%
- Time-stamped measurements including phasor estimates, frequency deviation from nominal or actual frequency, and ROCOF, sent in synchrophasor data frames

### IEC 61850-9-2 sampled values

- Streaming of phasor data over Ethernet using the IEC 61850-9-2 multicast sampled value (SV) service
- IEEE C37.118.2 compliant mapping of synchrophasor data, based on IEC 61850-9-2 and IEC 61850-9-5 guidelines
- IEC 61850 supported on both Ethernet ports alongside Modbus/TCP, DNP3/TCP and IEC 60870-5-104

### Time synchronisation

- Clock synchronisation to a UTC time reference using an IRIG-B timecode source or an IEEE 1588 PTPv2 master clock
- 1µs time stamp accuracy
- Optically isolated IRIG-B port with B004/B005 timecode format
- 1pps time synchronisation available via the digital inputs
- Built-in real-time clock with battery backup

### IEEE C37.118.2 data streaming (advanced protocol support)

- Commanded client-server UDP and TCP data transmission, plus spontaneous UDP data transmission over IP
- Reporting rates from 1 to 200 or 240 frames per second at 50 or 60Hz respectively
- Five data streaming slots for continuous synchrophasor streaming via unicast UDP and/or TCP connections
- 32-bit IEEE floating point or 16-bit scaled integer format, with conversion factors provided in configuration frames
- Optional frame extensions with analogue data (total fundamental active, reactive and apparent power and displacement power factor) and digital status data for up to 32 inputs
- Support for CFG-1, CFG-2 and CFG-3 configuration frames
- In spontaneous UDP mode, CFG-2 or CFG-3 frames can be sent every 30 seconds without an explicit user command

### Logging, recording and programming

- Programmable controller with up to 32 control setpoints and half-cycle scan time
- OR, AND and arithmetical logic functions, extensive triggers, programmable thresholds and delays, relay control and event-driven data recording
- Event recorder for internal diagnostic events, power faults and operation of the logic controller and digital I/O
- Eight data recorders with programmable datasets, logging periodically or on any internal or external trigger
- 32 digital counters for internal events and external pulses
- 16 interval timers from half a cycle to 24 hours for periodic recording and timed operations
- 16GB memory for long-term data recording

### Measurement inputs

- Voltage inputs: measurement category CAT III, operating range up to 277/480V AC +25%
- Variable current inputs: 5A or 1A nominal, selected at order
- Built-in power supply: 57.7 to 277V AC / 48 to 290V DC

### Display

- High contrast 1.77" TFT colour graphics display with configurable backlight
- Multilanguage support
- Two diagnostic LEDs and four push buttons

### Built-in I/O

- Two optically isolated digital inputs: 24V DC dry contact, programmable de-bounce from 1ms to 1s, control setpoints and 1pps time synchronisation, 1ms sampling
- One solid state relay output: unlatched, latched and pulse operation, fail-safe alarm operation, programmable pulse width and direct remote control through communications
- One optically isolated analogue input for 1mA to 20mA signals

### Communications

- RS-485 serial port up to 115,200 bps with Modbus RTU/ASCII and DNP3
- Dual 10/100Base-T Ethernet ports supporting Modbus/TCP, DNP3/TCP, IEC 60870-5-104, IEC 61850, IEEE C37.118.2 and IEEE 1588 PTPv2
- Up to 10 simultaneous non-intrusive Ethernet connections
- USB 2.0 port (Type C)

### Expansion modules (optional, ordered separately)

- Up to four expansion modules fitted side by side
- Up to two I/O modules are self-energised; a third I/O module requires an auxiliary power supply module
- 8 DI: eight optically isolated digital inputs, dry contact or 24/48/125/250V DC wet inputs, 1ms sampling, pulse counting and 1pps time synchronisation
- 4 RO: four electromechanical (EMR) or solid state (SSR) relay outputs with unlatched, latched, pulse and fail-safe operation
- 4 DI + 2 RO combo module
- 4 AO: four isolated universal analogue outputs configurable for ±1mA, 0 to 1mA, 0 to 5mA, ±5mA, 0 to 20mA or 4 to 20mA
- Auxiliary power supply modules (88 to 264V AC / 90 to 290V DC, or 24V DC) power the whole device including up to three extra I/O modules

### Software support

- Power Analysis Software (PAS): free configuration and data acquisition tool for remote configuration and monitoring
- Expertpower: SATEC web platform for energy data, alarms and reporting through the built-in Expertpower client
- eXpertConnect™ App: mobile connection to the meter for configuration, readings and diagnostics

### Applications

- Suited to a wide range of grid and site monitoring applications.
- Wide area monitoring
- Power quality
- Substation automation
- Renewable energy
- Energy management
- Industrial monitoring
- SCADA ready

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Voltage inputs
| Measurement category |CAT III |
| Operating range |277/480V AC +25% |
| Input impedance |4MΩ |
| Over-voltage withstand |1,000V AC continuous; 2,000V AC for 1 second |
| Burden |< 0.01VA at 120V; < 0.04VA at 400V |
| Isolation |4,000V AC for 1 minute |
| Wire size |Up to 10 AWG (4.5mm²) |
| Connector type |4 pin, plug-in |

Current inputs
| Measurement category |CAT III |
| Galvanic isolation |4,000V AC for 1 minute |
| Wire size |Up to 10 AWG (4.5mm²) |

Current inputs: 5A input
| Operating range |10A RMS continuous |
| Burden |< 0.2VA at 5A (10 AWG wire, 1m long) |
| Overload withstand |15A RMS continuous; 200A RMS for ½ second (10 AWG wire) |

Current inputs: 1A input
| Operating range |2A RMS continuous |
| Burden |< 0.2VA at 1A (10 AWG wire, 1m long) |
| Overload withstand |3A RMS continuous; 40A RMS for ½ second (10 AWG wire) |

Power supply
| Rated input |57.7 to 277V AC at 50/60Hz; 48 to 290V DC |
| Tolerance |±15% |
| Burden |11VA AC; 6VA DC |
| Isolation |4,000V AC for 1 minute |
| Wire size |Up to 14 AWG (1.5mm²) |

Auxiliary power supply (optional module): AC/DC module
| Rated input |88 to 264V AC / 90 to 290V DC |
| Output |5W |
| Burden |15VA |
| Withstand |4kV AC for 1 minute |
| Wiring |L/+, N/- |
| Terminal pitch |5mm |
| Wire size |Up to 12 AWG (2.5mm²) |

Auxiliary power supply (optional module): 24V DC module
| Rated input |9 to 36V DC |
| Output |7W |
| Galvanic isolation |4,000V AC for 1 minute |
| Terminal pitch |5mm |
| Wire size |14 AWG (up to 1.5mm²) |

Built-in digital inputs (2 DI)
| Type |Dry contacts, internally wetted at 24V DC |
| Galvanic isolation |4,000V AC for 1 minute |
| Internal power supply |24V DC |
| Scan time |1ms |
| Connector type |Removable, 5 pin |
| Wire size |14 AWG (up to 1.5mm²) |
| Terminal pitch |5mm |

Built-in digital output (1 DO)
| Type |Solid state relay, 1 contact (SPST Form A) |
| Rating |0.15A / 250V AC/DC |
| Galvanic isolation |4,000V AC for 1 minute |
| Operate time |1ms max. |
| Release time |0.25ms max. |
| Update time |1 cycle |
| Connector type |Removable, 4 pin |
| Wire size |14 AWG (up to 1.5mm²) |

Built-in analogue input (1 AI)
| Type |Universal, -1mA to 20mA |
| Configurable ranges |±1mA, 0 to 1mA, 0 to 20mA, 4 to 20mA |
| Accuracy |< 0.5% FS |
| Galvanic isolation |4,000V AC for 1 minute |
| Scan time |1ms |
| Connector type |Removable, 5 pin |
| Wire size |14 AWG (up to 1.5mm²) |
| Terminal pitch |5mm |

Add-on digital inputs (8 DI)
| Type |Dry contacts, internally wetted at 24V DC, or wet contacts up to 250V DC |
| Sensitivity |Open: input resistance > 100kΩ; Closed: input resistance < 100Ω |
| Galvanic isolation |4,000V AC for 1 minute |
| Internal power supply |24V DC |
| Scan time |1ms |
| Connector type |Removable, 2 × 5 pin |
| Wire size |14 AWG (up to 1.5mm²) |

Add-on digital outputs (4 DO): option 1, electromechanical relay, dry contact
| Rating |4 relays, 5A / 250V AC; 5A / 30V DC, 1 contact (SPST Form A) |
| Isolation, contacts to coil |3,000V AC for 1 minute |
| Isolation, open contacts |750V AC |
| Operate time |10ms max. |
| Release time |5ms max. |
| Wire size |14 AWG (up to 1.5mm²) |

Add-on digital outputs (4 DO): option 2, solid state relay, dry contact
| Rating |4 relays, 100mA / 800V AC, 1 contact (SPST Form A) |
| Isolation, contacts to coil |5,000V AC for 1 minute |
| Isolation, open contacts |800V peak |
| Operate time |5ms max. |
| Release time |5ms max. |
| Update time |1 cycle |
| Wire size |14 AWG (up to 1.5mm²) |

Add-on combo module (4 DI + 2 RO)
| Specification |Four digital inputs and two relay outputs, as per the 8 DI and 4 DO modules above |

Add-on analogue outputs (4 AO)
| Type |Universal (configurable) isolated analogue outputs |
| Scan time |1ms |
| Ranges (manually or remotely programmed) |±1mA, max. load 10kΩ (100% overload); 0 to 20mA, max. load 510Ω; 4 to 20mA, max. load 510Ω; 0 to 1mA, max. load 10kΩ (100% overload) |
| Accuracy |0.5% FS |
| Wire size |14 AWG (up to 1.5mm²) |
| Terminal pitch |5mm |

Communication ports: COM1 RS-485
| Type |Optically isolated RS-485 port |
| Baud rate |2,400 to 115,200 bps |
| Isolation |4,000V AC for 1 minute |
| Supported protocols |Modbus RTU, Modbus ASCII, DNP3 |
| Connector type |2 pin, plug-in |
| Wire size |Up to 14 AWG (1.5mm²) |

Communication ports: Ethernet (dual, 2 ports)
| Type |Transformer-isolated 10/100Base-T, RJ45 |
| Supported protocols |Modbus/TCP (port 502), DNP3/TCP (port 20000), IEC 60870-5-104 (port 2404), IEC 61850 (port 102), IEEE C37.118.2, PTPv2 (IEEE 1588) time sync |
| Simultaneous connections |10 (5 Modbus/TCP + 5 DNP3/TCP) |
| Isolation |4,000V AC for 1 minute |

Communication ports: USB port
| Type |Full speed USB 2.0, Type C |
| Isolation |4,000V AC for 1 minute |
| Supported protocols |Modbus |

Communication ports: IRIG-B port
| Type |Optically isolated IRIG-B port |
| Timecode signal |Unmodulated (pulse-width coded), 100pps |
| Signal level |5V unbalanced |
| Timecode format |B004/B005 |
| Isolation |4,000V AC for 1 minute |
| Connector type |Plug-in |
| Recommended cable |50Ω low loss RG58A/U (Belden 8219 or equivalent) |

Real-time clock
| Type |Built-in real-time clock with battery backup |
| Accuracy, calibrated |< 5ppm at 23°C |
| Battery type |CR1632 3V lithium button cell |
| Time retention |5 years (typical) |

Log memory and display
| Log memory |16GB for long-term data recording |
| Display |1.77" colour TFT LCD, 128 × 160 pixels |
| Indicators |2 diagnostic LEDs |
| Keypad |4 push buttons |

Environmental conditions
| Operating temperature |-25°C to +55°C (-13°F to 131°F) |
| No hardware failure |-40°C to +70°C (-40°F to 158°F) |
| No display failure |-20°C to +70°C (-4°F to 158°F) |
| Storage temperature |-30°C to +85°C (-22°F to 185°F) |
| Humidity |0 to 95% RH non-condensing |
| Altitude |Up to 2,000m above sea level |
| Degree of protection |IP51 |

Construction
| Mounting |DIN rail |
| Dimensions (without expansion modules) |89.5 × 72 × 90mm |
| Weight |0.70kg (1.54lb) |
| Case enclosure |PC/ABS plastic blend |
| Display body |PC/ABS plastic blend |
| Front panel |PC plastic |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Labels |Polyester film (UL94-V0) |

## Standards compliance

### Accuracy

- IEEE C37.118.1-2011 and IEEE C37.118.1a-2014 P-Class and M-Class performance
- IEC/IEEE 60255-118-1:2018 P-Class and M-Class performance

### Electromagnetic immunity

- Complies with IEC 61000-6-2
- IEC 61000-4-2 level 3: electrostatic discharge
- IEC 61000-4-3 level 3: radiated electromagnetic RF fields
- IEC 61000-4-4 level 3: electric fast transient
- IEC 61000-4-5 level 3: surge
- IEC 61000-4-6 level 3: conducted radio frequency
- IEC 61000-4-8: power frequency magnetic field
- Meets ANSI/IEEE C37.90.1: fast transient SWC

### Communication protocols

- IEEE C37.118.2 synchrophasor data transfer
- IEC 61850-9-2 sampled values, with mapping based on IEC 61850-9-5 guidelines
- IEEE 1588 PTPv2 and IRIG-B time synchronisation

### Electromagnetic emission

- Complies with IEC 61000-6-4: radiated and conducted, class A
- Complies with CISPR 22: radiated and conducted, class A

### Safety

- Meets IEC 61010-1:2006

### AC and impulse insulation

- Meets AS/IEC 62052-11: 4,000V AC for 1 minute
- 6kV / 500Ω at 1.2/50µs impulse
- Degree of protection: IP51

## Ordering information

MODEL – CURRENT – CAL. FREQ. – POWER – I/O MODULES – AUX. POWER

Model
| PMU PRO DIN rail mount phasor measurement unit |PMU PRO |

Current inputs
| 5 ampere |5A |
| 1 ampere |1A |

Calibration frequency
| 50Hz |50HZ |
| 60Hz |60HZ |

Power supply
| 88 to 320V AC / 40 to 290V DC |ACDC |

Optional I/O modules (max. 3 per device) and the auxiliary power supply module (max. 1 per device) complete the order string — see Expansion modules below.

### Expansion modules

Optional I/O modules: max. 3 per device. Auxiliary power supply: max. 1 per device.

Optional I/O modules (max. 3 per device)
| 4 relay outputs, 250V / 5A AC |EMR4 |
| 4 SSR outputs, 250V / 0.1A AC |SSR4 |
| 4 digital inputs (dry contact at 24V DC) + 2 SSR outputs |4DIOS-DRC |
| 4 digital inputs (dry contact at 24V DC) + 2 EMR outputs |4DIOR-DRC |
| 8 digital inputs, dry contact |DI8-DRC |
| 8 digital inputs, 24, 48, 125 or 250V DC wet |DI8-24/48/125/250 |
| 4 analogue outputs, configurable range |4AO |

Auxiliary power supply (max. 1 per device)
| AC/DC, 88 to 264V AC / 90 to 290V DC |AUX-ACDC |
| 24V DC (9 to 36V DC) |AUX-24DC |

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 938 KB)](https://satec-global.com.au/documentation/PMU-PRO-Phasor-Measurement-Unit-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-c0e6638047d6/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pmu-pro/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [What should I identify before selecting or installing a PMU PRO?](https://satec-global.com.au/support/articles/pmu-pro-identify-options/)
- [What PMU PRO status and recorded data should I collect for support?](https://satec-global.com.au/support/articles/pmu-pro-status-records-for-support/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).