# PM335 and EM235 PRO Series power quality analyser datasheet: specifications and ordering codes

> PM335 and EM235 datasheet as a web page: Advanced power meter and power quality analyser. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/pm335-em235-pro/

---

PM335 and EM235 · DATASHEET

# PM335 and EM235 PRO Series power quality analyser datasheet

Advanced power meter and power quality analyser.

Transcribed from the SATEC Australia datasheet [TBV1.0, 24 September 2026](https://satec-global.com.au/documentation/PRO-Series-PM335-EM235-Power-Quality-Analyser-Datasheet-TBV1-0.pdf) (PDF, 8 pages, 2734 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PRO Series is a modular family of advanced power meters and power quality analysers for substations, utilities, data centres, renewable energy sites and industrial networks. Each model is available as a Class S analyser or as a full IEC 61000-4-30 Class A Ed. 3.1 power quality analyser. It brings together capabilities usually spread across several separate devices.

Every unit delivers Class 0.2S revenue accuracy with AC and DC measurement on wide range inputs. Leakage current detection uses a fourth current input. Dual port Ethernet with IEC 61850 Ed. 2, 16GB of recording memory and up to four add-on modules make it ready for demanding monitoring and control projects.

## Main features

- Class 0.2S four-quadrant energy metering to AS/IEC 62053-22 and ANSI C12.20 Class 0.2
- IEC 61000-4-30 Class A Ed. 3.1 power quality analysis on PQ-A models
- EN 50160 statistics and reports plus IEEE 519 harmonic analysis
- AC inputs to 1,000V AC (L-L) and direct DC voltage from 10 to 820V DC
- Harmonics to the 63rd per IEC 61000-4-7 and flicker per IEC 61000-4-15
- Leakage and residual current detection via a fourth current input
- Flexible current inputs for 1A/5A CTs, HACS, DC sensors, LPCT and Rogowski clamps
- Eight fast waveform recorders at up to 256 samples per cycle
- 16 programmable data recorders with 16GB of onboard memory
- Dual Ethernet, RS-485, infrared and USB-C with Modbus, DNP3, IEC 60870-5-101/104 and IEC 61850
- Embedded programmable controller with 64 control setpoints
- Up to four add-on I/O, analogue output and auxiliary power modules side by side

## Feature capabilities

### Models

- PRO-PM335: Panel-mount analyser with a 3.5″ TFT colour display. Class S or Class A.
- PRO-EM235: DIN-rail analyser with a 1.77″ TFT colour display. Class S or Class A.
- PRO-RPM035: Transducer version of the PRO Series analyser. Class S or Class A.

### Billing and energy metering

- Four-quadrant active and reactive energy polyphase meter: Class 0.2S AS/IEC 62053-22 and Class 0.2 ANSI C12.20
- Time-of-Use (TOU) with 16 summary (totalisation) and TOU energy and demand registers for substation energy management
- Accumulation of energy pulses from external watt-meters
- Block and sliding demands for up to 64 energy sources
- Demand meter for amps, volts and harmonic demands

### Multi-functional power meter

- Three-phase true RMS volts, amps, powers, power factors, unbalance and neutral current
- Phasors and symmetrical components
- Frequency readings with three and four decimal resolution
- 32 digital counters for pulses from external sources and internal events
- 16 programmable timers from ½ cycle to 24 hours for periodic recording and triggering

### Harmonic analyser

- Per IEC 61000-4-7, up to the 63rd harmonic for volts and amps
- THD for volts and amps, TDD and K-factor
- Interharmonics for volts and amps
- Directional power harmonics (load or source) and harmonic power factor

### Time synchronisation and clock

- High precision time synchronisation via SNTP or 1 pps through a digital input
- IRIG-B time-code input (future release)
- Real-time clock with battery backup and three-year retention

### Power quality: PQ-A models (Class A Ed. 3.1)

- Power quality analysis in full compliance with IEC 61000-4-30 Class A, Edition 3.1
- Built-in statistics and reports per EN 50160
- IEEE 519 harmonic analysis

### Power quality: all models

- Sags and swells (dips and overvoltages), interruptions, frequency and voltage variations
- Flicker per IEC 61000-4-15 and voltage unbalance
- V-I angle, current TDD coefficients and K-factors
- Programmable thresholds and hysteresis
- Power quality event recorder with waveform and data recording
- Selectable sampling rate up to 256 samples per cycle
- Redundant auxiliary power supply for recording major dips and interruptions

### Fault recorder

- Up to 26 external digital triggers from protection relays
- Onboard zero-sequence currents and volts plus current and voltage unbalance
- Fault waveforms and fast RMS trace
- Cross triggering between devices via digital inputs for synchronous event capture

### Waveform and data recorders

- Eight fast waveform recorders with seven-channel (V1-V3, I1-I4) simultaneous recording
- Selectable AC sampling rate of 32, 64, 128 or 256 samples per cycle with 20 pre-fault cycles
- Synchronised waveforms from multiple devices in a single plot
- Export to COMTRADE and PQDIF formats via PAS software
- 16 programmable data recorders, periodic or on any internal or external trigger
- Event recorder for internal diagnostics, control events and I/O operations

### AC measurements

- Three fully isolated AC voltage inputs rated 10-1,000V AC (L-L) at 50/60Hz
- Four isolated AC current inputs (see Current Inputs in Specifications)
- Leakage current detection: residual current calculated via the fourth current input monitoring the neutral line, with configurable alerts and control thresholds

### DC measurements

- Three isolated DC voltage inputs from 10 to 820V DC, or up to 1,500V DC via an optional adapter
- DC voltage accuracy: 0.2%
- Four isolated DC current inputs up to 3,000A DC using SATEC U-HACS or Hall Effect sensors
- DC current accuracy: 0.2%
- DC power calculated from measured voltage and current

### Embedded programmable controller

- 64 control setpoints with OR/AND logic and extensive triggers
- Programmable thresholds and delays with relay control
- Event-driven data recording with up to 16 triggering channels
- Cross triggering between devices via Ethernet for synchronous event capture

### Software support

- Power Analysis Software (PAS) for configuration, data retrieval and waveform analysis
- Expertpower client over Modbus/TCP to a remote or local (stand-alone) Expertpower server
- eXpertConnect™ App for mobile configuration, readings and diagnostics

### Communications

- RS-485 serial port up to 115,200 bps: Modbus RTU/ASCII, DNP3.0, SNTP and IEC 60870-5-101
- Two 10/100 Base-T Ethernet ports: Modbus/TCP, DNP3/TCP, IEC 60870-5-104 and IEC 61850, with up to 10 non-intrusive simultaneous connections per port
- Infrared port (19,200 bps) with Modbus and DNP3 for local data exchange
- USB 2.0 port (type C)
- TCP notification client to a remote Modbus/TCP server, on events or periodically

### Expansion modules and I/O: up to four modules side by side

- Up to two expansion modules are self-energised
- Three I/O modules require the auxiliary power supply module
- Three daisy-chain slots for plug-in I/O and communication modules

### Expansion modules and I/O: optional built-in I/O

- Two optically isolated 24V DC dry contact inputs with 1 ms sampling and 1 pps time synchronisation
- One solid state relay output for alarms, pulses and remote control
- One universal analogue input (±1mA, 0-1mA, 0-20mA, 4-20mA)

### Expansion modules and I/O: add-on modules

- 8 DI: dry contact or 24/48/125/250V wet inputs
- 4 RO: electromechanical (EMR) or solid state (SSR) relays
- 4 DI + 2 RO combination module
- 4 AO: isolated universal analogue outputs
- Auxiliary power supply: 88-264V AC / 90-290V DC or 24V DC (9-36V DC)

### Applications

- Energy management and revenue metering
- SCADA and substation automation
- Industrial monitoring and power quality
- Renewable energy

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Voltage inputs
| Operating range1 |0-600V AC (L-N); 0-1,000V AC (L-L) |
| Direct DC voltage range2 |10-820V DC |
| Input impedance |4MΩ |
| Burden at 400V |≤ 0.04VA |
| Burden at 120V |< 0.01VA |
| Isolation |4,000V AC for 1 min |
| Wire size |Up to 14 AWG (≤ 2.5 mm²) |

1 Minimum value for accurate detection is 6V L-N and 10V L-L. 2 Measuring up to 1,500V DC is possible via an adapter.

Current inputs: 1A or 5A from CT secondary (standard)
| Operating range |Continuous 10A RMS |
| Burden |< 0.2VA at In = 1A or 5A |
| Overload withstand |15A RMS continuous, 200A (20 × Imax) RMS for ½ second |

Current inputs: optional inputs
| DC |0-20mA input for DC Hall Effect sensors |
| HACS |0-20mA inputs for solid or split core SATEC High Accuracy Current Sensors |

LPCT sensor interface (V/I)
| Voltage input |(3.25/√3) V |
| Voltage input burden |200kΩ ±1% |
| Current input |225mV |
| Current input burden |> 20kΩ |
| Connector type |2 wires |

Power supply
| Rated input |57.7-277V AC at 50/60Hz; 48-290V DC |
| Tolerance |±15% |
| Burden |11VA AC, 6VA DC |
| Isolation |4,000V AC for 1 min |
| Wire size |Up to 14 AWG (≤ 1.5 mm²) |

Built-in I/O (optional): digital inputs (2 DI)
| Type |Dry contacts, internally wetted at 24V DC |
| Galvanic isolation |4,000V AC for 1 min |
| Internal power supply |24V DC |
| Scan time |1 ms |
| Connector type |Removable, 5 pins |
| Wire size |14 AWG (up to 1.5 mm²) |
| Terminal pitch |5 mm |

Built-in I/O (optional): digital output (1 DO)
| Type |Solid state relay rated 0.15A / 250V AC/DC, 1 contact (SPST Form A) |
| Galvanic isolation |4,000V AC for 1 min |
| Operate time |1 ms max. |
| Release time |0.25 ms max. |
| Update time |1 cycle |
| Connector type |Removable, 4 pins |
| Wire size |14 AWG (up to 1.5 mm²) |

Built-in I/O (optional): analogue input (1 AI)
| Type |Universal, -1mA to 20mA (configurable: ±1mA, 0-1mA, 0-20mA, 4-20mA) |
| Galvanic isolation |4,000V AC for 1 min |
| Scan time |1 ms |
| Accuracy |< 0.5% FS |
| Connector type |Removable, 5 pins |
| Wire size |14 AWG (up to 1.5 mm²) |
| Terminal pitch |5 mm |

Add-on modules, digital I/O: digital inputs (8 DI)
| Type |Dry contacts, internally wetted at 24V DC, or wet contact up to 250V DC |
| Sensitivity |Open: input resistance > 100kΩ; Closed: input resistance < 100Ω |
| Galvanic isolation |4,000V AC for 1 min |
| Internal power supply |24V DC |
| Scan time |1 ms |
| Connector type |Removable, 2 × 5 pins |
| Wire size |14 AWG (up to 1.5 mm²) |

Add-on modules, digital I/O: digital outputs (4 DO), electromechanical relay
| Rating |4 relays, 5A / 250V AC and 5A / 30V DC, 1 contact (SPST Form A) |
| Isolation, contacts to coil |3,000V AC for 1 min |
| Isolation, open contacts |750V AC |
| Operate time |10 ms max. |
| Release time |5 ms max. |

Add-on modules, digital I/O: digital outputs (4 DO), solid state relay
| Rating |4 relays, 100mA / 800V AC, 1 contact (SPST Form A) |
| Isolation, contacts to coil |3,000V AC for 1 min |
| Isolation, open contacts |800V peak |
| Operate time |5 ms max. |
| Release time |5 ms max. |
| Update time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

Add-on modules, digital I/O: combination module (4 DI + 2 RO)
| Combination module (4 DI + 2 RO) |Four digital inputs and two relay outputs, per the specifications above |

Add-on modules: analogue outputs (4 AO)
| Type |Universal (configurable) isolated analogue outputs |
| Scan time |1 ms |
| Ranges (manually or remotely programmed) |±1mA, max. load 10kΩ (100% overload); 0-20mA, max. load 510Ω; 4-20mA, max. load 510Ω; 0-1mA, max. load 10kΩ (100% overload) |
| Accuracy |0.5% FS |
| Wire size |Up to 14 AWG (≤ 1.5 mm²) |
| Terminal pitch |5 mm |

Auxiliary power supply (module): AC/DC module
| Rated input |88-264V AC / 90-290V DC |
| Output |5W |
| Burden |15VA |
| Withstand |4kV AC for 1 min |
| Wiring |L/+, N/- |
| Terminal pitch |5 mm |
| Wire size |Up to 12 AWG (≤ 2.5 mm²) |

Auxiliary power supply (module): 24V DC module
| Rated input |9-36V DC |
| Output |7W |
| Galvanic isolation |4,000V AC for 1 min |
| Terminal pitch |5 mm |
| Wire size |14 AWG (up to 1.5 mm²) |

Communication ports: serial
| Type |RS-485 optically isolated, up to 115,200 bps |
| Supported protocols |Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101 |
| Isolation |4,000V AC for 1 min |

Communication ports: Ethernet (dual, 2 ports)
| Type |Transformer-isolated 10/100 Base-T, RJ45 |
| Supported protocols |Modbus/TCP (port 502); DNP3/TCP (port 20000); IEC 60870-5-104 (port 2404); IEC 61850 (port 102); SNTP |
| Simultaneous connections |10 (5 Modbus/TCP + 5 DNP3/TCP) |
| Isolation |4,000V AC for 1 min |

Communication ports: infrared (IR)
| Type |Front panel IR port with magnetic head |
| Supported protocols |Modbus RTU, DNP3 and IEC 62056-21 for local meter data exchange |
| Isolation |4,000V AC for 1 min |

Communication ports: USB
| Type |Full speed USB 2.0 |
| Connector type |USB Type C |
| Supported protocols |Modbus |
| Isolation |4,000V AC for 1 min |

Real-time clock
| Accuracy |Typical error ±15 seconds per month, < 5 minutes per year at 25°C |
| Retention |Battery backup, three years |

Log memory
| Capacity |16GB for long-term waveform and data recording |

Display
| PM335 |3.5″ TFT colour LCD, 320 × 480 dots |
| EM235 |1.77″ TFT colour LCD, 120 × 160 dots |

Environmental conditions
| Operating temperature |-40°C to +70°C (-40°F to 158°F) |
| Display operating temperature |-25°C to +70°C (-13°F to 158°F) |
| Storage temperature |-40°C to +85°C (-40°F to 185°F) |
| Humidity |0 to 95% RH non-condensing |
| Degree of protection |IP51 |

Construction
| Weight |0.70kg (1.54 lb) |
| Dimensions (PM335) |108.6 × 74.7 × 113.3 mm |
| Dimensions (EM235) |89.5 × 72 × 90 mm |
| Mounting (PM335) |Panel mount, 4″ round or 92 × 92 mm square cutout, 50 mm deep |
| Mounting (EM235) |DIN-rail |
| Enclosure |Anti-tamper sealed; power connections at bottom, communications and I/O at top |

Materials
| Case enclosure |Plastic PC/ABS blend |
| Display body |Plastic PC/ABS blend |
| Front panel |Plastic PC |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Labels |Polyester film (UL94-V0) |

## Standards compliance

### Electromagnetic immunity

- AS/IEC 62052-11, CLC/TR 50579 (conducted disturbances 2-150kHz), IEEE C62.41 and C37.90.1
- IEC 61000-6-2
- IEC 61000-4-2 level 3: Electrostatic Discharge
- IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
- IEC 61000-4-4 level 3: Electric Fast Transient
- IEC 61000-4-5 level 3: Surge
- IEC 61000-4-6 level 3: Conducted Radio Frequency
- IEC 61000-4-8: Power Frequency Magnetic Field
- ANSI/IEEE C37.90.1: Fast Transient SWC

### Electromagnetic emission

- IEC 61000-6-4*: Radiated/Conducted Class B
- IEC CISPR 22*: Radiated/Conducted Class B
- Emission per EN 55011/22 Class B and FCC Part 15 Class B

### Environmental

- IEC 60529: Protection
- IEC 60068-2-1: Cold
- IEC 60068-2-2: Dry Heat
- IEC 60068-2-30: Damp Heat
- IEC 60068-2-5: Solar Radiation

### Accuracy

- AS/IEC 62053-22:2003, Class 0.2S
- IEC 62053-24:2014, Class 0.5S
- ANSI C12.20-2015, Class 10 (0.2%)

### Power quality

- Designed to comply with EN 50160: Power Quality in European Electricity Supply Networks
- IEC 61000-4-7: Harmonics and interharmonics measurement
- IEC 61000-4-15: Flicker measurement
- IEC 61000-4-30 Class A (Ed. 3.1): Power quality measurement methods

### Safety and construction

- IEC 61010, AS/IEC 62052-11* and IEC 61557-12
- UL 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General Requirements, Edition 3, revision date 07/19/2019
- CSA C22.2 No. 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General Requirements, Edition 3, revision date 11/2018
- AC impulse insulation: meets AS/IEC 62052-11, 4,000V AC for 1 minute and 6kV/500Ω at 1.2/50 µs impulse
- IEC 60068-2-6: Vibration (sinusoidal)
- IEC 60068-2-27: Shock Test
- IEC 60068-2-75: Hammer Test
- * Meets standard requirements.

## Ordering information

MODEL – CURRENT – CAL. FREQ. – POWER – BUILT-IN I/O – LANGUAGE – PROTOCOL

Model
| PM335 panel-mount PQ analyser, Class S |PRO-PM335-PQ-S |
| EM235 DIN-rail PQ analyser, Class S |PRO-EM235-PQ-S |
| Transducer version PQ analyser, Class S |PRO-RPM035-PQ-S |
| PM335 panel-mount PQ analyser, Class A (Ed. 3.1) |PRO-PM335-PQ-A |
| EM235 DIN-rail PQ analyser, Class A (Ed. 3.1) |PRO-EM235-PQ-A |
| Transducer version PQ analyser, Class A (Ed. 3.1) |PRO-RPM035-PQ-A |

Current inputs
| 5 Ampere |5A |
| 1 Ampere |1A |
| 5A split core remote HACS, 50/60Hz only |RS5 |
| High Accuracy Current Sensors (HACS), 50/60Hz only |HACS |
| Pole top sensor interface, 0-10V (voltage and current) |PTS |
| Pole top sensor interface, 0-10V (voltage), current 5A |PTS-5 |
| LPCT: dedicated low voltage interface for MV sensors |LPCT |
| 3V AC inputs for Rogowski current clamps |FLEX |

Calibration at frequency
| 50Hz |50HZ |
| 60Hz |60HZ |

Power supply
| 88-320V AC / 40-290V DC |ACDC |

Built-in I/O
| 2 × DI (dry contact) + 1 × SSR output + 1 × universal AI (-1mA to 20mA) |IOS |

Display language
| English |EN |

Optional protocols
| IEC 61850 communication protocol |850 |

### Expansion modules

Maximum of three I/O modules and one auxiliary power supply module per device.

I/O modules
| 4 relay outputs, 250V / 5A AC |EMR4 |
| 4 SSR outputs, 250V / 0.1A AC |SSR4 |
| 4 digital inputs (dry contact at 24V DC) + 2 SSR outputs |4DIOS-DRC |
| 4 digital inputs (dry contact at 24V DC) + 2 EMR outputs |4DIOR-DRC |
| 8 digital inputs, dry contact |DI8-DRC |
| 8 digital inputs, 24, 48, 125 or 250V DC |DI8-24 / 48 / 125 / 250 |
| 4 analogue outputs, configurable range |4AO |

Auxiliary power supply
| AC/DC, 88-264V AC / 90-290V DC |AUX-ACDC |
| 24V DC (9-36V DC) |AUX-24DC |

An auxiliary power supply module is required when three I/O modules are fitted.

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 2734 KB)](https://satec-global.com.au/documentation/PRO-Series-PM335-EM235-Power-Quality-Analyser-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-37991131aa0e/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pm335-pro/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).