# PM180 power quality analyser datasheet: specifications and ordering codes

> PM180 datasheet as a web page: High Performance Power Quality Analyser with PMU and Fault Recording. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/pm180/

---

PM180 · DATASHEET

# PM180 power quality analyser datasheet

High Performance Power Quality Analyser with PMU and Fault Recording.

Transcribed from the SATEC Australia datasheet [TBV1.0, 29 September 2026](https://satec-global.com.au/documentation/PM180-Power-Quality-Analyser-Datasheet-TBV1-0.pdf) (PDF, 8 pages, 2518 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PM180 is a multi-microprocessor power quality analyser that combines a Class A power quality analyser, a Class 0.2S energy meter, a digital fault recorder, a phasor measurement unit and a programmable bay controller in one instrument. It is designed for substation and industrial automation, where one IED can replace several separate devices and save cost, panel space and wiring.

Four voltage inputs (the fourth AC/DC) and four current inputs are standard. Three hot-swap expansion slots take transient recorder, fault recorder, PMU, digital input, relay, analogue I/O, communication and auxiliary power supply modules. Built-in RS-485, Ethernet, USB and IRIG-B ports support Modbus, DNP3, IEC 60870-5-101/104 and optional IEC 61850.

## Main features

- Power quality to IEC 61000-4-30 Class A, Edition 3
- Active energy Class 0.2S per AS/IEC 62053-22
- Harmonics and interharmonics to the 63rd order
- EN 50160 and IEEE 1159 statistics and reports
- Disturbance direction detection for sags and swells
- Fast transient recorder up to 2 kV at 1024 samples per cycle
- Digital fault recorder for currents up to 200 A (40 x In)
- Distance to fault calculation
- IEEE C37.118.1 M-Class and P-Class PMU
- IEC 61850 Edition 2 with GOOSE messaging
- Bay controller for 2 circuit breakers and 14 switches
- 256 MB memory with 3.5 min of continuous waveform recording

## Feature capabilities

### Versions

- PM180-X: Transducer version with no display. Includes a DIN rail mounting kit.
- PM180-G: PM180 with a 5.7" colour graphic touch screen display (RGM180).
- PM180-D: PM180 with a 3-line ultra-bright LED display (RDM180).

### Multi-function power and energy meter

- Real-time cycle-by-cycle true RMS voltage, current, power, power factor, demand and energy
- Class 0.2S active energy per AS/IEC 62053-22 and Class 0.2 per ANSI C12.20
- Class 0.5S reactive energy per IEC 62053-24
- Time of Use with 16 energy sources including external pulse inputs, 4 seasons, 4 daily profiles and 8 tariff changes per day
- KYZ or KY pulse output and a calibration LED (via the optional display)

### Power quality

- Analysis in full compliance with IEC 61000-4-30 Class A, Edition 3 (2015)
- Sags, swells, interruptions, frequency and voltage variations
- Flicker per IEC 61000-4-15 and voltage unbalance
- Individual voltage and current harmonics per IEC 61000-4-7, interharmonics and directional power harmonics (load or source) to the 63rd
- Voltage and current THD, current TDD, K-factors and V-I angles
- Vector diagram and symmetrical components; frequency to 3 decimal places
- Built-in statistics and reports per EN 50160 and IEEE 1159
- Disturbance direction detection showing whether sags and swells come from upstream or downstream
- Programmable thresholds and hysteresis
- Optional redundant auxiliary power supply to capture major dips and interruptions

### Distance to fault calculation

- Compensation for CT and PT errors, for an average accuracy of 0.5%
- Single lines, parallel lines, partially parallel lines and lines with a branch
- Detects three-phase, two-phase, two-phase to ground and single-phase to ground short circuits, and single-phase open wire
- Reports fault classification, distance to fault (km) and fault duration

### Digital fault recorder (DFR module for 200 A fault currents)

- Direct reading of fault currents up to 200 A (40 x In from the CT secondary)
- Dual current inputs for separate metering and protection CT connections (optional)
- Programmable fault threshold and hysteresis
- Zero-sequence currents and voltages, unbalance, undervoltage and neutral current
- Ready-to-use fault reports with fault current magnitude and duration, coincident voltage magnitude, waveforms and RMS trace
- Selectable pre-fault and post-fault recording length, triggered by any internal or external condition
- Disturbance capture and waveforms from multiple locations
- View faults and receive alerts in Expertpower

### Phasor measurement unit (PMU module)

- IEEE C37.118.1 M-Class and P-Class
- Three-phase voltage and current phasors synchronised to a common UTC time reference
- Synchronous frequency and rate of change of frequency (ROCOF)
- Expected steady-state total vector error (TVE) below 0.5%
- Streaming from 1 to 50 or 60 frames per second at 50 or 60 Hz
- IEEE C37.118.2 commanded client-server UDP and TCP and spontaneous UDP transmission
- Optional frame extensions with total power, power factor and digital status data
- Phasor streaming via the IEC 61850-9-2 sampled value (SV) service
- PTP (IEEE 1588) time synchronisation; includes the transient recorder

### Fast transient recorder (TRM-180 or PMU module)

- Records voltage transients up to 2 kV (line to ground) at 1024 samples per cycle per channel
- Four voltage channels with 10 MΩ high-impedance inputs

### Bay controller (BCU)

- Monitoring and control of 2 circuit breakers and 14 circuit switches
- One-pole and three-pole switch position monitoring using two or six contacts
- Select-close and select-open outputs for secure switching, with configurable command pulse duration
- Supervision of command execution and reporting on operation termination
- Interlocking logic with secure timed-out interlocking bypass
- Indication of non-controllable breaker trips and switch position substitution
- Counting and logging of breaker and switch operations
- PLC configurator based on IEC 61131-3 using Function Block Diagram or Ladder Diagram

### IEC 61850 substation communications (order code 850)

- IEC 61850 implemented per Edition 2
- Remote switch control and monitoring
- Inter-device GOOSE messaging for remote interlocking
- GOOSE publisher and subscriber setup and report dead-bands
- Configurable IED properties, datasets and reports

### Data logging, waveforms and PLC

- 256 MB memory for data logging
- 8 fast waveform recorders: 8 AC channels plus one DC channel and up to 48 digital inputs in a single plot
- Waveform sampling at 32, 64, 128 or 256 samples per cycle with up to 20 pre-fault cycles
- 3.5 min of continuous waveform recording
- 16 fast data recorders (16 parameters each) from ½-cycle to 2-hour RMS envelopes
- Power quality, event and diagnostic recorders; 1 ms resolution for digital inputs
- Up to 64 control setpoints with OR, AND and arithmetic logic
- 32 internal counters and 16 programmable timers (½ cycle to 24 hours)
- COMTRADE and PQDIF file export

### Time synchronisation

- Real-time clock with a maximum drift of 5 seconds per month at 25°C
- 1 ms time resolution from an IRIG-B time code input or satellite clock
- Periodic synchronisation from an SNTP server as an SNTP client
- Time sync from a digital input with 1 ms accuracy
- PTP (IEEE 1588) with the PMU module

### Communications

- Built-in RS-485, Ethernet, USB and IRIG-B
- Optional fibre optic Ethernet (TXFX), redundant 2nd Ethernet and 2nd RS-422/485 port
- Modbus RTU, Modbus TCP, DNP3, DNP3/TCP and IEC 60870-5-101/104 as standard
- Optional IEC 61850 (SISCO) with MMS and GOOSE
- IEEE C37.118.2 synchrophasor streaming with the PMU module
- Cross triggering between multiple devices via Ethernet

### Modular hardware and displays

- Three hot-swap expansion slots for plug-in I/O and function modules
- Up to 48 digital inputs, 24 relay outputs and 12 analogue inputs and outputs
- Optional redundant power supply and Ethernet port
- Compact half 19" 3U form factor for DIN rail, panel or 19" rack installation
- Choice of 5.7" colour touch screen or 3-line LED remote display

### Software support

- Power Analysis Software (PAS) for setup, real-time monitoring, waveform and event analysis and data retrieval
- Expertpower web platform for dashboards, fault alerts and energy reporting
- eXpertConnect™ App for mobile connection to the meter for configuration, readings and diagnostics

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Environmental conditions
| Operating temperature |-25°C to +60°C |
| Storage temperature |-30°C to +85°C |
| Humidity |0 to 95% non-condensing; long-term damp heat withstand per IEC 68-2-3 <95%, +40°C |
| Altitude |Up to 2000 m |

Construction
| Dimensions (W x H x D) |220 x 152 x 210 mm |
| Weight |2.5 kg |
| Mounting |DIN rail, panel mount or 19" rack installation; complies with EN 50022 |
| Enclosure and panels |Polycarbonate |
| PCB and terminals |FR4 (UL94-V0); PBT terminals (UL94-V0) |
| Protection |Panel display IP54, instrument IP30 per IEC 60529 |

Power supply (main)
| Rated input |50-290V AC (50/60 Hz), 90-290V DC |
| Maximum power |10W (burden <20VA) |
| Insulation |4kV AC @ 1 min |
| Wire size |Up to 10 AWG (up to 6 mm²) |

Auxiliary power supply (module)
| AC/DC module |50-290V AC (50/60 Hz), 40-290V DC, maximum power 20W |
| Low DC module (12/24V) |9.6-35V DC, maximum power 20W |

Voltage inputs (V1, V2, V3, VN)
| Nominal voltage (L-N/L-L) |57/100V AC, 277/480V AC, 400/690V AC |
| Operating range |Direct input or via PT, up to 828V AC |
| Input impedance |1 MΩ |
| Burden |480V L-N: 0.3VA; 277V L-N: 0.1VA; 120V L-N: 0.02VA |
| Overvoltage withstand |1000V AC continuous, 2500V AC for 1 second |
| Galvanic isolation |4kV AC @ 1 min; impulse dielectric withstand 6kV |
| Wire size |Up to 10 AWG (up to 6 mm²) |

AC/DC voltage input (V4, VREF)
| Operating range |400V AC; DC voltage measurement up to 290V DC |
| Input impedance |>10 MΩ |

Current inputs (I1, I2, I3, I4)
| Current ratings |1A or 5A input |
| Guaranteed accuracy |Per AS/IEC 62053-22 and ANSI: Class 0.2S up to 2 x In, Class 0.2 up to 4 x In |
| 5A input |Fault currents up to 50A RMS (10 x In); burden <0.15VA; overload 50A RMS continuous, 250A for 1 second |
| 1A input |Continuous 4A RMS; fault currents up to 10A RMS; burden <0.02VA; overload 10A RMS continuous, 50A for 1 second |
| HACS inputs |40mA inputs for SATEC High Accuracy Current Sensors (100-3000A) |
| HACS 100A (CS1S) |Nominal 5A RMS; fault currents up to 100A RMS (20 x In) |

Digital fault recorder module
| Channels |4 current channels via 4 HACS |
| Fault currents measured |Up to 200A RMS @ In = 5A (40 x In) |
| Accuracy |Class 1 |
| Burden |<0.15VA |
| Overload |200A RMS continuous, 1000A for 1 second |

Fast transient recorder
| Measuring range |Up to 2kV AC, 4 voltage channels |
| Sampling |1024 samples per cycle |
| Input |High impedance 10 MΩ; insulation withstand 4kV AC @ 1 min |

Phasor measurement unit
| Compliance |IEEE C37.118.1 M-Class and P-Class |
| Total vector error |Expected steady-state TVE less than 0.5% |
| Streaming rate |1 to 50 or 60 frames per second @ 50 or 60 Hz |
| Data transfer |IEEE C37.118.2 over UDP and TCP; IEC 61850-9-2 sampled values |
| Time reference |PTP (IEEE 1588) or IRIG-B |

Digital inputs (16 per module)
| Inputs |16 optically isolated inputs per module, up to 48 per unit |
| Sensitivity |Open @ input resistance >16 kΩ, closed @ input resistance <10 kΩ |
| Galvanic isolation |4kV RMS @ 1 min |
| Scan time |1 ms @ 60 Hz, 1.25 ms @ 50 Hz |
| Wire size |12 AWG (up to 2.5 mm²) |

Relay outputs (8 per module)
| Relays |8 SPST Form A relays per module, up to 24 per unit |
| Contact rating |8A @ 250V AC, 5A @ 30V DC, 0.25A @ 250V DC, 5A @ 24V DC |
| Operate and release time |10 ms max. operate, 5 ms max. release |
| Update time |½ cycle |

Analogue I/O (4 AI + 4 AO per module)
| Ranges (upon order) |±1 mA (100% overload), 0-20 mA, 4-20 mA, 0-1 mA |
| Maximum load |±1 mA: 10 kΩ; 0-20 mA: 510 Ω |
| Accuracy |0.5% FS |
| Scan and update time |2 cycles |
| Voltage input module |4 analogue inputs, ±10V |

Communication ports
| COM1 |RS-485 (RS-232 selectable), optically isolated 4kV AC @ 1 min, up to 115.2 kb/s, max. cable length 1000 m; Modbus RTU/ASCII, DNP3 |
| Ethernet |Transformer-isolated 10/100Base-T, 4kV AC @ 1 min; Modbus TCP (port 502), DNP3/TCP (port 20000); 5 simultaneous connections |
| USB |Isolated USB 1.1 port, 4kV AC @ 1 min; Modbus RTU |
| COM2 (module) |RS-422/485 optically isolated, up to 115.2 kb/s |
| ETH2 (module) |10/100Base-T or 100Base-FX fibre optic |

Time and clock
| IRIG-B |Optically isolated port, unbalanced 5V level; 1 ms time resolution |
| Real-time clock |Maximum drift 5 seconds per month @ 25°C |
| SNTP / digital input |SNTP client; digital input sync with 1 ms accuracy |

Display modules
| Graphic display (G) |5.7" touch panel TFT colour display, 320 x 240; operating -20°C to +70°C |
| LED display (D) |High-brightness seven-segment LEDs, two 4-digit windows and one 6-digit window |
| Distance |3 m cable, up to 500 m with an external 12V DC supply |

Measurement accuracy
| Voltage V1-V3, VN |% reading 0.05; % FS 0.01; conditions 10% to 120% FS; range 0 to 99,999,999 V |
| Line current I1-I4 |% reading 0.05; % FS 0.01; conditions 1% to 120% FS; range 0 to 29,999 A |
| Fault current (standard inputs) |% reading 2.0; conditions 400% to 1000% FS; range 0 to 29,999 A |
| Fault current (DFR module) |% reading 2.0; conditions 400% to 4000% FS; range 0 to 29,999 A |
| DC voltage |% reading 0.3; conditions 10% to 120% FS; range 0 to 290V DC |
| Active power |% reading 0.2; % FS 0.002; conditions |PF| ≥ 0.5; range ±2,000,000 kW |
| Reactive power |% reading 0.3; % FS 0.002; conditions |PF| ≤ 0.9; range ±2,000,000 kvar |
| Apparent power |% reading 0.2; % FS 0.002; conditions |PF| ≥ 0.5; range 0 to 2,000,000 kVA |
| Power factor |% reading 0.35; conditions |PF| ≥ 0.5, I ≥ 2% FSI; range -0.999 to +1.000 |
| Frequency |% reading 0.002; conditions 40 to 70 Hz; range 40.000 to 70.000 Hz |
| Voltage and current THD |% reading 1.5; % FS 0.2; conditions THD ≥ 1% FS; range 0 to 999.9% |
| Active energy |Class 0.2S per AS/IEC 62053-22; range 0 to 999,999.999 MWh |
| Reactive energy |Class 0.5S per IEC 62053-24; range 0 to 999,999.999 Mvarh |

Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit, calculated at 1 second average. It does not include errors introduced by external potential and current transformers. Printed as a five-column table (parameter, % reading, % FS, conditions, range); blank cells are left out.

## Standards compliance

### Accuracy

- Active energy: Class 0.2S per AS/IEC 62053-22
- Active energy: Class 0.2 per ANSI C12.20
- Reactive energy: Class 0.5S under conditions per IEC 62053-24:2014 @ 0 ≤ |PF| ≤ 0.9

### Power quality

- IEC 61000-4-30 Class A, Edition 3: power quality measurement methods
- IEC 61000-4-7: harmonics and interharmonics measurement
- IEC 61000-4-15: flicker measurement
- EN 50160: power quality in European electricity supply networks
- IEEE 1159: power quality recording
- GOST 13109 and GOST R 54149-2010 (order option G)
- IEC 62054-21: real-time clock backup, RTC accuracy ±2 ppm @ 23°C

### Phasor measurement

- IEEE C37.118.1: M-Class and P-Class synchrophasor measurement
- IEEE C37.118.2: synchrophasor data transfer
- IEEE 1588: Precision Time Protocol

### Communications

- IEC 61850 Edition 2 (optional)
- IEC 60870-5-101 and IEC 60870-5-104
- DNP3 and Modbus

### Safety and insulation

- Meets IEC/UL 61010-1 and UL94 V-0
- AS/IEC 62052-11: insulation impulse 6kV/500 Ω @ 1.2/50 µs
- AS/IEC 62052-11, IEC 61010-1: AC voltage tests related to ground, 4kV AC @ 1 min

### EMC immunity

- IEC 61000-4-2, IEC 60255-22-2: electrostatic discharge, 15kV/8kV air/contact
- IEC 61000-4-3, IEC 60255-22-3: radiated immunity, 10V/m and 30V/m @ 80 MHz to 1000 MHz
- IEC 61000-4-4, IEC 60255-22-4: fast transient burst, 4kV on current and voltage circuits, 2kV on auxiliary circuits
- IEC 61000-4-5, IEC 60255-22-5: surge 6kV on current and voltage circuits and power supply
- IEEE C62.41.2-2002: 100 kHz ring wave 6kV @ 0.5kA; 1.2/50 µs and 8/20 µs combination wave 6kV @ 3kA
- IEC 61000-4-6, AS/IEC 62052-11: conducted radio frequency, 10V @ 0.15 MHz to 80 MHz
- IEC 61000-4-8: magnetic field
- IEC 61000-4-12, AS/IEC 62052-11, IEEE C37.90.1-2002: oscillatory waves, CMM 2.5kV and DFM 1kV @ 100 kHz and 1 MHz
- ANSI C37.90.1: surge withstand capability (SWC)
- IEC 61000-6-2, IEC 60255-5, IEC 60255-22

### Emission

- EN 55022, IEC 60255-22: Class A (radiated and conducted)
- IEC 61000-6-4

### Environmental and mechanical

- IEC 68-2-3: long-term damp heat withstand <95%, +40°C
- IEC 60255-21-1: vibration response Table I Class 2; vibration endurance Table II Class 1
- IEC 60255-21-2: shock Table II Class 1; bump Table III Class 1
- IEC 60255-21-3: seismic, Class 1

### Ingress protection

- IEC 60529: panel display IP54 (NEMA type 13)
- IEC 60529: instrument IP30

## Ordering information

MODEL – DISPLAY – VOLTAGE – CURRENT – FREQ. – STANDARD – POWER – COMMS – MODULES

Model
| PM180 power quality analyser |PM180 |

Display
| Transducer version, no display. Includes DIN rail mounting kit |X |
| Graphic colour display, 5.7" touch screen |G |
| Graphic colour display, 5.7" touch screen with DIN rail mounting kit and 3 m remote cable |G-DIN |
| 3-line ultra-bright LED display |D |
| 3-line ultra-bright LED display with DIN rail mounting kit and 3 m remote cable |D-DIN |

Voltage inputs
| 690V AC nominal voltage input |- |
| 120V AC nominal voltage input |U |

Current inputs
| 50A, calibrated to 5A (Class 0.2S accuracy) |5 |
| 10A, calibrated to 1A (Class 0.2S accuracy) |1 |
| 100A split core HACS (set of 4), calibrated to 5A (Class 1 accuracy) |CS1S |
| 100A split core handheld clamp HACS (set of 4), Ø13 mm opening, calibrated to 5A (Class 1 accuracy) |CS1H |
| Any High Accuracy Current Sensors (HACS), without overcurrent. Requires ordering of 4 HACS |HACS |
| 3V AC current clamps (purchased locally) |FLEX |

Calibration frequency
| 50 Hz |50Hz |
| 60 Hz |60Hz |

Accuracy and power quality standard
| AS/IEC 62053-22 with EN 50160 full power quality |E |
| ANSI C12.20 with IEEE 1159 full power quality |A |
| GOST 13109 / GOST 54149 |G |

Power supply (main)
| 85-265V AC and 88-290V DC (default) |ACDC |

Communication standard
| Modbus RTU, Modbus TCP, DNP3, DNP3/TCP, IEC 60870-5-101 and -104 (default) |- |
| Default communication plus IEC 61850 (SISCO) |850 |

Optional plug-in modules are listed below. A maximum of three modules can be fitted to each PM180.

### Expansion modules

Optional plug-in modules. Maximum of three modules per unit.

Phasor measurement unit (max. 1)
| PMU with transient recorder, including PTP (IEEE 1588) |PMU |

Transient recorder (max. 1)
| 4 voltage channels, up to 2kV and 1024 samples per cycle |TRM-180 |

Fault recorder (max. 1)
| 4 current channels up to 200A via 4 x solid core CTs (Ø23 mm aperture) |DFR-CS2-180 |
| 4 current channels up to 200A via 4 x split core CTs (Ø23 mm aperture) |DFR-CS2S-180 |
| 4 current channels up to 200A via 4 x split core CTs (Ø33 mm aperture) |DFR-CS2SL-180 |

Digital inputs (max. 48 per unit)
| 16 digital inputs, dry contacts |DI16-DRC-180 |
| 16 digital inputs, 24V DC |DI16-24V-180 |
| 16 digital inputs, 125V DC |DI16-125V-180 |
| 16 digital inputs, 250V DC |DI16-250V-180 |

Communication
| BNC IRIG-B and 2nd RS-422/485 port |IRIG-180 |
| Fibre optic Ethernet (TXFX), redundant Ethernet and 2nd RS-422/485 port |TXFX-180 |

Relay outputs (max. 24 per unit)
| 8 relays |RLY8-180 |
| 8 DI / 4 RO, electromechanical relays, dry contact inputs |8DIOR-DRC |
| 8 DI / 4 RO, solid state relays, dry contact inputs |8DIOS-DRC |
| 8 DI / 4 RO, electromechanical relays, 24V inputs |8DIOR-24 |
| 8 DI / 4 RO, solid state relays, 24V inputs |8DIOS-24 |
| 8 DI / 4 RO, electromechanical relays, 125V inputs |8DIOR-125 |
| 8 DI / 4 RO, solid state relays, 125V inputs |8DIOS-125 |
| 8 DI / 4 RO, electromechanical relays, 250V inputs |8DIOR-250 |
| 8 DI / 4 RO, solid state relays, 250V inputs |8DIOS-250 |

Analogue I/O (max. 12 AI / 12 AO per unit)
| 4 AI / 4 AO, ±1 mA |4AIO1-180 |
| 4 AI / 4 AO, 0-20 mA |4AIO2-180 |
| 4 AI / 4 AO, 0-1 mA |4AIO3-180 |
| 4 AI / 4 AO, 4-20 mA |4AIO4-180 |
| 4 analogue inputs, ±10V |4AIV-180 |

Auxiliary power supply (max. 1)
| Auxiliary power supply, 85-265V AC and 40-300V DC |BACDC-180 |
| Auxiliary power supply, 9.5-36V DC |B21DC-180 |

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 2518 KB)](https://satec-global.com.au/documentation/PM180-Power-Quality-Analyser-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-e1ae59da3da2/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pm180/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [How do I replace the backup battery in a PM180?](https://satec-global.com.au/support/articles/pm180-battery-replacement/)
- [Which PM180 display and options are fitted or required?](https://satec-global.com.au/support/articles/pm180-display-and-options/)
- [What information and records should I preserve before a PM180 service or change?](https://satec-global.com.au/support/articles/pm180-preserve-before-service-or-change/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).