# PM17x PRO power quality analyser datasheet: specifications and ordering codes

> PM17x PRO datasheet as a web page: Class A Power Quality Analysis and Class 0.2S Energy Metering. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.1.

Source page: https://satec-global.com.au/support/datasheets/pm17x-pro/

---

PM17x PRO · DATASHEET

# PM17x PRO power quality analyser datasheet

Class A Power Quality Analysis and Class 0.2S Energy Metering.

Transcribed from the SATEC Australia datasheet [TBV1.1, 9 September 2026](https://satec-global.com.au/documentation/PM17x-PRO-Datasheet-0926.pdf) (PDF, 7 pages, 1070 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PM17x PRO Series brings power quality analysis, revenue-grade metering and embedded control together in one panel instrument. It suits substation and industrial automation, utility SCADA and commercial energy management, where one device has to replace several. Class 0.2S accuracy and Class A Ed. 3.1 power quality performance sit in the same enclosure.

Each meter is supplied with a three-row bright LED display or as a transducer version with no display. An extra-wide 10 to 1,000V AC line-to-line input rating and a fourth voltage input (Vref) widen the measurement range. Dual-port Ethernet, RS-485 and USB 2.0 Type C cover communications, with IEC 61850 Ed. 2, DNP3.0 and IEC 60870-5-101/104 support. A fourth current input enables residual and leakage current detection.

PM172 PRO: Power and revenue meter with power quality analysis and data logging

PM174 PRO: Class A Ed. 3.1 analyser reporting to the IEEE 1159 power quality standard

PM175 PRO: Class A Ed. 3.1 analyser reporting to the EN 50160 power quality standard

## Main features

- Class 0.2S four-quadrant active and reactive energy metering to AS/IEC 62053-22 and ANSI C12.20 Class 10
- Class A Ed. 3.1 power quality analyser per IEC 61000-4-30, tested to IEC 62586-1 and IEC 62586-2
- EN 50160 and IEEE 1159 compliance statistics with IEC 61000-4-7 harmonic analysis to the 63rd order
- Extra-wide voltage rating of 10 to 1,000V AC line-to-line plus a fourth voltage input (Vref)
- Four isolated current inputs, the fourth enabling residual and leakage current detection
- Dual-port 10/100 Base-T Ethernet, RS-485 and USB 2.0 Type C with IEC 61850 Ed. 2 support
- 1 µs time synchronisation via IRIG-B or PTP v2 (IEEE 1588)
- 16GB memory for long-term waveform and data recording

## Feature capabilities

### Class A Power Quality Recorder (PM174 and PM175 PRO)

- Class A Ed. 3.1 measurement methods per IEC 61000-4-30
- EN 50160 compliance statistics and event log (PM175 PRO)
- IEEE 1159 power quality reporting (PM174 PRO)
- Power quality event triggering with programmable limits
- Flicker measurement per IEC 61000-4-15

### Harmonic Analyser

- Harmonics to the 63rd order for volts and amps per IEC 61000-4-7
- THD for volts and amps, TDD, K-factor and interharmonics
- Directional power harmonics and harmonic power factor
- IEEE 519 harmonic analysis
- Phasor diagrams and symmetrical components

### Waveform Recording

- 8 fast waveform recorders with 7-channel simultaneous capture (V1–V3, I1–I4)
- Selectable AC sampling rate of 32, 64, 128 or 256 samples per cycle
- 20 pre-fault cycles retained ahead of each trigger
- Synchronised waveforms from multiple devices in a single plot
- COMTRADE and PQDIF export through PAS software

### Event and Data Recording

- 16 data recorders with programmable periodic logs, triggered by any internal or external event
- Event recorder for internal diagnostics, control events and I/O operations
- 32 digital counters for external pulses and internal events
- 16 programmable timers from half a cycle to 24 hours
- 16GB memory for long-term waveform and data recording

### Billing and TOU Energy Meter

- Class 0.2S four-quadrant active and reactive polyphase static meter to AS/IEC 62053-22 and ANSI C12.20 Class 0.2
- Time-of-Use with 16 summary totalisation registers plus TOU energy and demand registers
- Accumulation of energy pulses from external wattmeters
- Block and sliding demand with up to 64 energy sources
- Demand meter for amps, volts and harmonic demands

### Embedded Programmable Controller

- 64 control setpoints with OR/AND logic and extensive trigger options
- Programmable thresholds and delays with relay control
- Event-driven data recording
- Cross-triggering between multiple devices over Ethernet for synchronous event capture, across up to sixteen triggering channels

### AC Measurement

- Fully isolated AC inputs for direct connection to AC feeders
- Four isolated voltage inputs rated 10 to 1,000V AC line-to-line at 50/60 Hz
- Four isolated current inputs with 1A or 5A CT secondary, HACS, LPCT-D or RS5 options
- Three-phase power meter measuring true RMS volts, amps, powers, power factors, unbalance and neutral current
- Fourth voltage input (Vref) rated 0 to 300V AC/DC

### Leakage and Residual Current

- Accurate residual current calculation through a fourth current input monitoring the neutral line
- Alerts and control thresholds configurable in response to detected leakage current

### Built-in I/O

- 2 optically isolated digital inputs, 24V DC dry contact, with programmable debounce from 1 ms to 1 second
- 1 solid state relay output with unlatched, latched and pulse operation plus fail-safe alarm notification
- 1 optically isolated analogue input of configurable range (±1mA, 0–1mA, 0–20mA, 4–20mA)
- IRIG-B time synchronisation input

### Time Synchronisation

- 1 µs satellite-synchronised clock accuracy via IRIG-B or PTP v2 (IEEE 1588)
- SNTP time synchronisation
- 1 pps synchronisation via digital input
- Internal real-time clock with three-year battery retention

### Communications

- RS-485 serial port to 115,200 bps with Modbus RTU/ASCII, DNP3.0 and IEC 60870-5-101
- 2 × Ethernet 10/100 Base-T ports supporting Modbus/TCP, DNP3.0/TCP, IEC 60870-5-104, PTP and IEC 61850
- Up to 10 non-intrusive simultaneous connections per Ethernet port
- USB 2.0 port (Type C)
- TCP notification client reporting to a remote Modbus/TCP server on event or on a time basis

### Software Support and Firmware

- Power Analysis Software (PAS) for configuration, data acquisition, waveforms, phasors and harmonics
- Expertpower™ web platform for energy management with no client software to install
- eXpertConnect™ App for mobile connection to the meter covering configuration, readings and diagnostics
- Expertpower client for Modbus/TCP communication with a remote or local stand-alone Expertpower server
- Firmware upgrade over a serial or Ethernet port

### Display Options

- Three-row, 7-segment bright LED display of two 4-character rows plus one 6-character row
- Transducer version supplied with no display
- Load bar graph indication

### Applications

- Energy management and revenue metering
- SCADA-ready substation automation
- Industrial monitoring
- Renewable energy generation

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Voltage inputs
| Operating range |10–1,000V AC (L-L) @ 50/60 Hz |
| Input impedance |4MΩ |
| Burden @ 400V |≤ 0.04VA |
| Burden @ 120V |< 0.01VA |
| Isolation |4,000V AC @ 1 min |
| Wire size |Up to 14 AWG (≤ 2.5 mm²) |

4th voltage (Vref) and LPVT
| Vref operating range |0–300V AC/DC |
| LPVT nominal voltage (PM172 PRO only) |0.5–5V |
| LPVT input impedance ** |2MΩ / 50 pF |
| LPVT interface ** |RJ45 |

** According to IEC 61869-11.

Current input options
| 1A / 5A from CT secondary (standard) |Continuous 10A RMS · burden < 0.2VA @ In=1A or 5A · overload withstand 15A RMS continuous, 200A (20 × Imax) RMS for ½ second |
| HACS |0–20mA inputs for solid-core or split-core SATEC High Accuracy Current Sensors |
| LPCT-D rating |80A / 150 mV @ 50 Hz · 80A / 180 mV @ 60 Hz · RJ45 interface ** · 2MΩ / 50 pF ** |
| LPCT-D max primary |650A |
| RS5 (5A HACS version) |Nominal input 2.5 mA · maximum current 5 mA at 200% overload · dedicated to HACS CS05S / RS5 (HX0140) |

** According to IEC 61869-11.

Digital inputs (2 DI)
| Type |Dry contacts, internally wetted @ 24V DC |
| Internal power supply |24V DC |
| Galvanic isolation |4,000V AC @ 1 min |
| Scan time |1 ms |
| Connector |Removable, 5 pins · 5 mm terminal pitch |
| Wire size |Up to 14 AWG (≤ 1.5 mm²) |

Digital output and analogue input
| Relay rating |Solid state relay, 0.15A / 250V AC-DC, 1 contact (SPST Form A) |
| Galvanic isolation |4,000V AC @ 1 min |
| Operate / release time |1 ms max / 0.25 ms max |
| Update time |1 cycle |
| Analogue input range |Universal −1mA to 20mA, configurable ±1mA, 0–1mA, 0–20mA, 4–20mA |
| Analogue scan time |1 ms |
| Connector |Removable, 4 pins (DO), 5 pins (AI) |

Power supply
| Rated input |100–277V AC @ 50/60 Hz · 100–290V DC |
| Tolerance |±15% |
| Burden |11VA @ V AC · 6VA @ V DC |
| Isolation |4,000V AC @ 1 min |
| Wire size |Up to 14 AWG (≤ 2.5 mm²) |

Auxiliary power supply (built-in)
| Rated input |9–36V DC (24V) |
| Output |7W |
| Galvanic isolation |4,000V AC @ 1 min · 4kV |
| Terminal pitch |5 mm |
| Wire size |Up to 14 AWG (1.5 mm²) |

Serial communication
| Port |RS-485, optically isolated |
| Baud rate |Up to 115,200 bps |
| Isolation |4,000V AC @ 1 min |
| Protocols |Modbus RTU · DNP3 · IEC 60870-5-101 |

Ethernet ports (dual)
| Type |2 × transformer-isolated 10/100 Base-T, RJ45 |
| Protocols |Modbus/TCP (502) · DNP3/TCP (20000) · IEC 60870-5-104 (2404) · IEC 61850 (102) |
| Simultaneous connections |10 per port (5 Modbus/TCP + 5 DNP3/TCP) |
| Isolation |4,000V AC @ 1 min |

USB port
| Type |USB 2.0, Type C |

IRIG-B
| Port |Optically isolated IRIG-B input for GPS time synchronisation |
| Recommended cable |51Ω low loss RG58A/U (Belden 8219 or equivalent), BNC connector |
| Recommended generator |Masterclock GPS-200A GPS time code generator |

Real-time clock and log memory
| Clock accuracy |Typical error ±15 seconds per month, under 5 minutes per year @ 25°C |
| Battery retention |Three years |
| Log memory |16GB for long-term waveform and data recording |

Display options
| Standard |Three-row 7-segment LED, two 4-character rows plus one 6-character row |
| Transducer version |No display (RPM17x PRO model) |

Environmental conditions
| Operating temperature |−40°C to +70°C (−40°F to 158°F) |
| Display operating temp. |−20°C to +70°C (−4°F to 158°F) |
| Storage temperature |−40°C to +85°C (−40°F to 185°F) |
| Humidity |0 to 95% RH, non-condensing |
| Degree of protection |IP51 |

Construction
| Weight |1.23 kg (2.7 lb) |
| Dimensions [H×W×D] |114 × 127 × 127 mm |
| Panel cutout |Dual installation: 4-inch round or 92 × 92 mm square |

Materials
| Case enclosure |PC/ABS blend plastic |
| Display body |PC/ABS blend plastic |
| Front panel |PC plastic |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Labels |Polyester film (UL94-V0) |

## Standards compliance

### Power Quality

- IEC 61000-4-30 Ed. 3.1: power quality measurement methods, Class A
- IEC 61000-4-7: general guide on harmonics and interharmonics measurement and instrumentation
- IEC 61000-4-15: flickermeter
- IEC 62586-1: product and performance requirements for power quality meters
- IEC 62586-2: detailed testing procedures verifying classification under IEC 61000-4-30
- EN 50160: voltage characteristics of electricity supplied by public networks
- IEEE 1159: recommended practice for monitoring electric power quality

### Accuracy

- Complies with AS/IEC 62053-22:2003, Class 0.2S
- Complies with IEC 62053-24:2014, Class 0.5S
- Meets ANSI C12.20-2015, Class 10 (0.2%)

### Environmental

- IEC 60529: degree of protection
- IEC 60068-2-1: cold
- IEC 60068-2-2: dry heat
- IEC 60068-2-30: damp heat
- IEC 60068-2-5: solar radiation

### Electromagnetic Immunity

- IEC 62052-11 and CLC/TR 50579: conducted disturbances 2 to 150kHz
- IEEE C62.41 and C37.90.1
- IEC 61000-6-2
- IEC 61000-4-2 level 3: electrostatic discharge
- IEC 61000-4-3 level 3: radiated electromagnetic RF fields
- IEC 61000-4-4 level 3: electrical fast transient
- IEC 61000-4-5 level 3: surge
- IEC 61000-4-6 level 3: conducted radio frequency
- IEC 61000-4-8: power frequency magnetic field
- ANSI/IEEE C37.90.1: fast transient SWC

### Electromagnetic Emission

- IEC 61000-6-4: radiated and conducted Class B
- IEC CISPR 22: radiated and conducted Class B
- Emission per EN 55011/22 Class B and FCC Part 15 Class B

### Safety and Construction

- IEC 61010, IEC 62052-11 and IEC 61557-12
- UL 61010-1 Edition 3, safety requirements for electrical equipment for measurement, control and laboratory use
- CSA C22.2 No. 61010-1 Edition 3
- AC impulse insulation meets IEC 62052-11: 4,000V AC for 1 minute, 6kV/500Ω @ 1.2/50 µs impulse
- IEC 60068-2-6: vibration (sinusoidal)
- IEC 60068-2-27: shock test
- IEC 60068-2-75: hammer test

## Ordering information

MODEL – CURRENT – CALIBRATION – PROTOCOL – MODULE – AUX POWER

Model
| PM172 panel-mount power and revenue meter |PRO-PM172 |
| PM174 panel-mount Class A analyser (IEEE 1159) |PRO-PM174 |
| PM175 panel-mount Class A analyser (EN 50160) |PRO-PM175 |
| Transducer version, supplied with no display |PRO-RPM17x |

Current inputs
| 5 Ampere |5A |
| 1 Ampere |1A |
| High Accuracy Current Sensors (HACS), 50/60 Hz. Order 3 × HACS separately |HACS |
| 5A split-core remote HACS, 50/60 Hz only |RS5 |
| LPCT sensor inputs (RJ45) to 650A primary, 80A/150 mV at 50 Hz |LPCT-D |

Calibration frequency
| 50 Hz |50HZ |
| 60 Hz |60HZ |

Communication protocol
| Modbus, DNP3.0 and IEC 60870-5-101/104 (standard) |— |
| IEC 61850 Ed. 2 ‡ |850 |

Optional built-in module (max. 1 per device)
| 4 relay outputs, 250V / 5A AC |EMR4 |
| 4 SSR outputs, 250V / 0.1A AC |SSR4 |
| 4 digital inputs (dry contact 24V DC) plus 2 SSR outputs |4DIOS-DRC |
| 4 digital inputs (dry contact 24V DC) plus 2 EMR outputs |4DIOR-DRC |
| 8 digital inputs, dry contact |DI8-DRC |
| 8 digital inputs, 24 / 48 / 125 / 250V DC |DI8-24, 48, 125, 250V |
| 4 analogue outputs, configurable range |4AO |

Auxiliary power supply
| 9–36V DC (24V) |AUX-24DC |

‡ Confirm the IEC 61850 option code with SATEC Australia when ordering.

## Downloads and related

- [Download the datasheet (PDF, TBV1.1, 1070 KB)](https://satec-global.com.au/documentation/PM17x-PRO-Datasheet-0926.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-26a85b348472/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pm175-pro/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).