# PM175 power quality analyser datasheet (TFT display): specifications and ordering codes

> PM175 datasheet as a web page: Power Quality Analyser with 5.7" Touch Screen Colour Display. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/pm175-tft/

---

PM175 · DATASHEET

# PM175 power quality analyser datasheet (TFT display)

Power Quality Analyser with 5.7" Touch Screen Colour Display.

Transcribed from the SATEC Australia datasheet [TBV1.0, 29 September 2026](https://satec-global.com.au/documentation/PM175-TFT-Power-Quality-Analyser-Datasheet-TBV1-0.pdf) (PDF, 6 pages, 2860 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PM175 is a compact multifunction three-phase AC power meter and power quality analyser. It is designed for users ranging from electrical panel builders to substation operators who need revenue-grade energy data and EN 50160 power quality reporting in one instrument.

Users can choose a bright 3-row LED display or a 5.7" colour graphic touch screen. The display module is detachable and can be mounted up to 1000 m from the meter. Two communication ports support local and remote meter reading and setup over serial, Ethernet (TCP/IP) and Profibus.

PM175: Power quality analyser with a bright 3-row LED display.

PM175-TFT: PM175 with a 5.7" colour graphic touch screen display.

RPM075: Transducer version without a local display.

## Main features

- Class 0.2S accuracy per AS/IEC 62053-22
- True RMS multifunction 3-phase metering
- Harmonic spectrum and angles to the 50th order
- EN 50160 power quality recorder and reports
- Time-of-Use metering with 8 tariffs and 4 seasons
- Two waveform recorders at up to 128 samples per cycle
- 16 programmable data recorders
- 1 MB battery-backed log memory
- Embedded controller with 16 setpoints
- Detachable LED or 5.7" colour touch screen display
- Up to 4 digital inputs and 4 relay outputs
- Two communication ports including Ethernet

## Feature capabilities

### Measurements

- 3 voltage and 3 current transformer-isolated AC inputs for direct connection or via PTs and CTs
- True RMS volts, amps, power, power factor and frequency
- Neutral current plus voltage and current unbalance
- Ampere, volt, THD and TDD demand meter
- Class 0.2S accuracy (1A and 5A versions)

### Energy and Time-of-Use

- 8 tariff energy/demand registers x 8 tariffs
- 4 seasons x 4 types of day with 8 tariff changes per day
- Easily programmable tariff schedule
- Automatic daily profile of energy and maximum demand readings for total and tariff registers

### Power quality recorder

- EN 50160 power quality recorder (GOST 13109 or GOST 54149 also selectable)
- Compliance statistics and EN 50160 harmonics survey statistics
- Onboard power quality analyser with programmable thresholds and hysteresis
- Ready-to-use reports

### Harmonic analyser

- Embedded harmonic analyser
- Voltage and current THD, current TDD and K-factor
- Voltage and current harmonic spectrum and angles up to the 50th order
- Inter-harmonics THD

### Waveform recording

- Two waveform recorders with simultaneous 6-channel AC recording in a single plot
- Sampling rates of 32, 64 and 128 samples per cycle
- 20 pre-fault cycles
- Up to 30 seconds of continuous recording at 32 samples per cycle
- Real-time waveform capture and monitoring: 6 channels, 4 cycles at 128 samples per cycle

### Logging and memory

- Event recorder for internal diagnostics, control events and I/O operations
- 16 data recorders with programmable logs on a periodic basis or on any internal or external trigger
- 1 MB RAM with battery backup for long-term data and waveform recording
- Precise internal clock with battery backup

### Embedded controller

- 16 control setpoints
- Programmable thresholds and delays
- Relay output control
- 1/2-cycle response time

### Inputs and outputs

- 2 standard plus 2 optional digital inputs for external contacts and pulses from energy, water and gas meters
- 2 standard plus 2 optional relay outputs for alarms, control and energy pulses
- 2 optional optically isolated analogue outputs with internal power supply
- 2 optional optically isolated analogue inputs with internal power supply
- Optional analogue expander with an additional 2 x 8 analogue outputs

### Display options: one or two displays per meter

- Detachable display module with a 3-wire RS-485 interface, up to 1000 m from the meter
- LED: bright 3-row display (2 x 4 characters + 1 x 6 characters) with adjustable update time, auto-scroll, auto-return to a default page and a percent-load LED bar graph
- TFT: 5.7" colour graphic touch screen with easy-to-read screens for monitoring complex information at a glance
- Touch screen operation keeps setup and configuration simple

### Communications

- Two independent communication ports
- COM1: RS-232/RS-422/RS-485, Ethernet 10/100BaseT (Expertpower enabled) or Profibus DP
- COM2: RS-422/RS-485
- Modbus RTU, Modbus ASCII and Modbus/TCP
- DNP3 and DNP3/TCP (Level 1 Rev. 2.3)
- Full speed USB port on the PM175-TFT display

### Security and firmware

- Password security for setup parameters and resets via the front panel and communications
- Tampering attempts recorded to the device event log
- Easy field upgrade of device firmware through any communication port

### Software support

- PAS Power Analysis Software for setup, data retrieval and analysis
- Expertpower web platform via the Ethernet port
- eXpertConnect™ App for mobile access to energy data
- MV90xi compatible

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Environmental conditions
| Operating temperature |-20°C to +60°C (-4°F to 140°F) |
| Storage temperature |-25°C to +80°C (-13°F to 176°F) |
| Humidity |0 to 95% RH non-condensing |

Construction
| Weight |1.23 kg (2.7 lb) |
| Dimensions (HxWxD) |127 x 127 x 143 mm (5 x 5 x 5.6") |

Power supply
| 120/230V AC, 110/220V DC option |Rated input 85-264V AC 50/60 Hz, 88-290V DC, burden 10W |
| Isolation |Input to output 3000V AC, input to ground 2000V AC |
| 12V DC option |Rated input 9.6-19V DC |
| 24V DC option |Rated input 19-37V DC |
| 48V DC option |Rated input 37-72V DC |
| Wire size |Up to 12 AWG (up to 3.5 mm²) |

Materials
| Case enclosure |Plastic PC/ABS blend |
| Display body |Plastic PC/ABS blend |
| Front panel |Plastic PC |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Packaging case |Carton and Stratocell® (polyethylene foam) brackets |
| Labels |Polyester film (UL94-V0) |

Real-time clock
| Accuracy |Typical error 30 seconds per month at 25°C |

Log memory
| Onboard memory |1 MB with battery backup |

Voltage inputs
| Operating range |690V AC L-L, 400V AC L-N |
| Direct input and input via PT |Up to 828V AC line-to-line, up to 480V AC line-to-neutral |
| Input impedance |1 MΩ |
| Burden for 400V |<0.4 VA |
| Burden for 120V |<0.04 VA |
| Overvoltage withstand |1kV AC continuous, 2kV AC for 1 second |
| Galvanic isolation |3500V AC |
| Wire size |Up to 12 AWG (up to 3.5 mm²) |

Current inputs
| Operating range |5A: continuous 10A RMS, burden <0.1 VA; 1A: continuous 2A RMS, burden <0.02 VA |
| Overload withstand |5A: continuous 15A RMS, 300A for 1 second; 1A: continuous 6A RMS, 80A for 1 second |
| Galvanic isolation |3500V AC |
| Wire size |12 AWG (up to 3.5 mm²) |

Relay outputs
| Relays |2 relays rated 3A/250V AC and 3A/30V DC, 2 contacts (SPST Form A) |
| Galvanic isolation |Between contacts and coil 2000V AC for 1 minute, between open contacts 1000V AC |
| Operate time |10 ms max. |
| Release time |5 ms max. |
| Update time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

Digital inputs
| Inputs |2 digital inputs, dry contacts |
| Galvanic isolation |2000V RMS |
| Internal power supply |15V |
| Scan time |1 ms |
| Wire size |14 AWG (up to 1.5 mm²) |

Optional analogue inputs
| Inputs |2 analogue inputs (optically isolated) |
| Ranges (upon order) |±1 mA (100% overload), 0-1 mA (100% overload), 0-20 mA, 4-20 mA |
| Isolation |2000V RMS |
| Accuracy |0.5% FS |
| Scan time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

Optional analogue outputs
| Outputs |2 analogue outputs (optically isolated) |
| Ranges (upon order) |0-20 mA and 4-20 mA, max. load 510 Ω; ±1 mA and 0-1 mA, max. load 5 kΩ (100% overload); ±5 mA and 0-5 mA, max. load 5 kΩ |
| Isolation |2000V RMS |
| Power supply |Internal |
| Accuracy |0.5% FS |
| Update time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

LED display module
| Display |High-brightness seven-segment digital LEDs, two 4-digit and one 6-digit windows |
| Keypad |6 push buttons |
| Communication |EIA RS-485 port with 12V supply voltage |
| Connector type |DB15, 15 pins |
| Wire size |Up to 14 AWG (up to 1.5 mm²) |
| Distance |Up to 1000 m (3200 ft) |

COM1: RS-232 port (optional module)
| Port |Serial EIA RS-232, optically isolated |
| Isolation |2000V RMS |
| Connector type |DB9 female |
| Baud rate |Up to 115.2 kbps |
| Supported protocols |Modbus RTU, Modbus ASCII, DNP3 (firmware V25.2.01 and later) |

COM1: RS-422/RS-485 port (optional module)
| Port |RS-422/RS-485, optically isolated |
| Isolation |2000V RMS |
| Connector type |DB9 female |
| Baud rate |Up to 115.2 kbps |
| Supported protocols |Modbus RTU, Modbus ASCII, DNP3 (firmware V25.2.01 and later) |

COM1: Ethernet port (optional module)
| Port |Transformer-isolated 10/100BaseT Ethernet |
| Connector type |RJ45 modular |
| Supported protocols |Modbus/TCP on port 502, DNP3/TCP on port 20000 (firmware V25.2.01 and later) |
| Simultaneous connections |4 (4 Modbus/TCP or 2 Modbus/TCP + 2 DNP3/TCP) |

COM2
| Port |RS-422/RS-485, optically isolated |
| Isolation |2000V RMS |
| Connector type |Removable, 5 pins |
| Wire size |Up to 14 AWG (up to 1.5 mm²) |
| Baud rate |Up to 115.2 kbps |
| Supported protocols |Modbus RTU, Modbus ASCII, DNP3 (firmware V25.2.01 and later) |

TFT display module
| Display |5.7" colour graphic touch screen |
| USB |Full speed USB port |
| Distance |Up to 1000 m from the meter |

## Standards compliance

### Accuracy

- Class 0.2S per AS/IEC 62053-22 (1A and 5A versions)

### Emission

- EN 55011:1991
- EN 55022:1994 Class A
- EN 50081-2 Generic Emission Standard, Industrial Environment

### Immunity

- EN 50082-1:1992
- EN 50082-2 Generic Immunity Standard, Industrial Environment
- EN 61000-4-2, EN 61000-4-4:1995, EN 61000-4-8:1993
- ENV 50140:1983, ENV 50141:1993, ENV 50204:1995 (900 MHz)

### Safety

- EN 61010-1:1993/A2:1995

### Directives

- EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
- LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC

## Ordering information

MODEL – VOLTAGE – CURRENT – CAL. FREQ. – POWER – I/O MODULE – COMMS

Model
| PM175 power quality analyser |PM175 |
| PM175 with 5.7" touch screen colour graphic display |PM175-TFT |
| Transducer version |RPM075 |

Voltage inputs
| 690V AC nominal voltage input |- |
| 120V AC nominal voltage input |U |

Current inputs
| 5 Ampere |5 |
| 1 Ampere |1 |
| 5A split core remote high accuracy current sensor |RS5 |
| High Accuracy Current Sensors (HACS), requires ordering of 3 HACS |HACS |

Calibration at frequency
| 50 Hz |50Hz |
| 60 Hz |60Hz |

Power supply
| 85-265V AC and 88-290V DC |ACDC |
| 9.6-19V DC |1DC |
| 19-37V DC |2DC |
| 37-72V DC |3DC |

I/O module
| 2 digital inputs/2 digital outputs (standard) |- |
| Additional 2 DI/2 DO (total 4 DI/4 DO) |DIO |
| 2 analogue outputs: ±1 mA |AO1 |
| 2 analogue outputs: 0-20 mA |AO2 |
| 2 analogue outputs: 0-1 mA |AO3 |
| 2 analogue outputs: 4-20 mA |AO4 |
| 2 analogue outputs: 0-5 mA |AO5 |
| 2 analogue outputs: ±5 mA |AO6 |
| 2 analogue inputs: ±1 mA |AI1 |
| 2 analogue inputs: 0-20 mA |AI2 |
| 2 analogue inputs: 0-1 mA |AI3 |
| 2 analogue inputs: 4-20 mA |AI4 |

Communication
| Standard communications RS-232/422/485 |- |
| Ethernet (TCP/IP) |ETH |
| Profibus |PRO |

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 2860 KB)](https://satec-global.com.au/documentation/PM175-TFT-Power-Quality-Analyser-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-84013b5fd81f/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pm175/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [Which PM175 display drawing applies to my panel?](https://satec-global.com.au/support/articles/pm175-display-drawing/)
- [What does the PM175 LED display's CT primary setting mean?](https://satec-global.com.au/support/articles/pm175-led-ct-primary-setting/)
- [Is the PM175 PRO a suitable replacement for my legacy PM175?](https://satec-global.com.au/support/articles/pm175-to-pm175-pro-replacement-checks/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).