# PM172 power and revenue meter datasheet: specifications and ordering codes

> PM172 datasheet as a web page: PM172 Series: advanced high accuracy power and revenue meter. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/pm172/

---

PM172 · DATASHEET

# PM172 power and revenue meter datasheet

PM172 Series: advanced high accuracy power and revenue meter.

Transcribed from the SATEC Australia datasheet [TBV1.0, 28 September 2026](https://satec-global.com.au/documentation/PM172-Power-Revenue-Meter-Datasheet-TBV1-0.pdf) (PDF, 7 pages, 585 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PM172 is a compact, multi-function, three-phase AC power meter and Class 0.2S revenue meter. It is designed for users ranging from electrical panel builders to substation operators, with more than 100 measured parameters for feeder monitoring, utility substations, industrial SCADA and distribution automation.

A bright three-row LED display with a load bar graph sits on a detachable display module that can be located up to 1000 m from the meter. Built-in Time of Use tariffs, event and data recorders, harmonic analysis and waveform capture sit alongside two independent communication ports supporting Modbus, DNP3 and Profibus DP, with an Ethernet option for Expertpower.

PM172P: Multi-functional three-phase power meter with harmonic analysis, setpoint control and digital I/O.

PM172E: Adds a Class 0.2S TOU revenue meter, an event recorder and multi-channel data recorders.

PM172EH: Adds extended harmonic analysis, fast waveform recorders and voltage disturbance monitoring.

## Main features

- Class 0.2S four-quadrant energy metering to AS/IEC 62053-22 (PM172E and PM172EH)
- Accuracy per ANSI C12.20
- Time of Use metering with 8 registers x 8 tariffs, 4 seasons x 4 types of days
- Voltage and current THD, current TDD and K-Factor up to the 40th harmonic
- Waveform recording at up to 128 samples per cycle (PM172EH)
- 16 control setpoints with a 1-cycle response time
- 2 relay outputs and 2 digital inputs, with optional analogue inputs or outputs
- 1 Mbyte battery-backed memory for long-term data and waveform recording
- Two communication ports: RS-232/422/485, Ethernet and Profibus DP options
- Detachable three-row LED display module, mountable up to 1000 m away
- Expertpower enabled Ethernet with Modbus/TCP and DNP3/TCP
- Panel mounting in an ANSI 4" round or DIN 92 x 92 mm cutout, or 35 mm DIN rail

## Feature capabilities

### Multi-functional three-phase power meter

- 3 voltage and 3 current transformer-isolated AC inputs for direct connection to the power line or via potential and current transformers
- True RMS volts, amps, power, power factor, neutral current, voltage and current unbalance and frequency
- Ampere, volt, THD and TDD demand meter
- 1-cycle real-time and 1-second average measurements
- 25, 50, 60 and 400Hz operation

### Harmonic analysis

- Embedded harmonic analyser: voltage and current THD, current TDD and K-Factor up to the 40th order
- Voltage and current harmonic spectrum and angles up to the 40th order (PM172EH)
- Harmonic power and energy (PM172EH)

### Programmable controller and alarms

- Embedded programmable controller with 16 control setpoints
- Programmable thresholds and delays with relay output control
- 1-cycle response time
- Four six-digit counters for counting pulses or events

### Billing and TOU revenue meter (PM172E and PM172EH only)

- Class 0.2S four-quadrant active, reactive and apparent energy, import and export, to AS/IEC 62053-22
- Time of Use with 8 totalisation and tariff energy/demand registers x 8 tariffs
- 4 seasons x 4 types of days and 8 tariff changes per day, with an easy programmable tariff schedule
- Automatic daily profile for energy and maximum demand readings (total and tariff registers)
- MV90xi compatible

### Waveform and disturbance recording (PM172EH only)

- Two waveform recorders with simultaneous 6-channel AC recording in a single plot
- Sampling rates of 32 and 128 samples per cycle, with 20 pre-fault cycles
- Up to 30 seconds of continuous recording at 32 samples per cycle
- Real-time waveform capture and monitoring: simultaneous 6-channel 4-cycle capture at 128 samples per cycle
- Voltage disturbance monitor with setpoint triggering

### Event and data recording (PM172E and PM172EH only)

- Event recorder for logging internal diagnostic events, control events and I/O operations
- Eight data recorders with programmable data logs on a periodic basis and on any internal or external trigger
- Real-time stamped logging of more than 100 parameters
- 1 Mbyte onboard memory with battery backup

### Display

- Easy to read 3-row (2 x 4 characters + 1 x 6 characters) bright LED display
- Adjustable update time, auto-scroll with adjustable page exposition time and auto-return to a default page
- LED bar graph showing percent load against a user-definable nominal load current
- Detachable display module with a 3-wire RS-485 interface, operating up to 1000 m from the meter
- Optional colour touch screen graphical display

### Inputs and outputs

- 2 digital inputs for monitoring external contacts and receiving pulses from energy, water and gas meters
- 2 relay outputs for alarms, controls and energy pulse output
- Optional DIO module adds 2 digital inputs and 2 digital outputs (4 DI / 4 DO in total)
- 2 optional optically isolated analogue outputs or analogue inputs with an internal power supply
- Optional analogue expander providing an additional 2 x 8 analogue outputs

### Current input options

- 5A or 1A secondary inputs for standard CTs
- Optional High Accuracy Current Sensors (HACS)
- 5A split core remote HACS option for retrofit installations

### Communications

- Two independent communication ports for local and remote meter reading and setup
- COM1 options: RS-232/422/485, Ethernet 10/100BaseT or Profibus DP
- COM2: RS-422/485
- Modbus RTU and ASCII, Modbus/TCP, DNP3, DNP3/TCP, GE EGD producer, Profibus DP and SATEC ASCII protocols
- Ethernet port is Expertpower enabled, with a TCP notification client

### Real-time clock and firmware

- Precise internal clock and calendar with battery backup
- Time synchronisation via a communication port or digital input
- Easy field upgrading of device firmware through any communication port

### Software support

- Power Analysis Software (PAS) for meter setup, data retrieval and analysis
- Expertpower web platform for energy monitoring and management reports
- eXpertConnect™ App for mobile connection to the meter for configuration, readings and diagnostics

### Applications

- Utility substations
- Feeder monitoring
- Industrial SCADA
- Distribution automation
- Revenue and tariff metering
- Electrical panel builders

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Environmental conditions
| Operating temperature |-20°C to 60°C (-4°F to 140°F) |
| Storage temperature |-25°C to 80°C (-13°F to 176°F) |
| Humidity |0 to 95% non-condensing |

Construction
| Display module |127 x 127 mm (max.) |
| Meter body |114 x 114 mm |
| Panel mounting |ANSI 4" round or DIN 92 x 92 mm square cutout |
| DIN rail mounting |35 mm DIN rail |
| Weight |1.23 kg (2.7 lb) |
| Case enclosure |Plastic PC/ABS blend |
| Front panel |Plastic PC |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |

Power supply
| 120/230V AC, 110/220V DC option |85 to 264V AC 50/60Hz, 88 to 290V DC |
| Burden |10W |
| 12V DC option |9.6 to 19V DC |
| 24V DC option |19 to 37V DC |
| 48V DC option |37 to 72V DC |
| Isolation |Input to output 3000V AC; input to ground 2000V AC |
| Wire size |Up to 12 AWG (3.5 mm²) |

Voltage inputs
| Operating range |690V AC line-to-line, 400V AC line-to-neutral |
| Direct input and via PT |Up to 828V AC line-to-line, up to 480V AC line-to-neutral |
| Input impedance |500 kΩ |
| Burden |< 0.4VA at 400V; < 0.04VA at 120V |
| Overvoltage withstand |1000V AC continuous; 2000V AC for 1 second |
| Galvanic isolation |3500V AC |
| Wire size |Up to 12 AWG (3.5 mm²) |

Current inputs
| Galvanic isolation |3500V AC |
| Wire size |12 AWG (up to 3.5 mm²) |

Current inputs: 5A secondary
| Operating range |10A RMS continuous |
| Burden |< 0.1VA |
| Overload withstand |15A RMS continuous; 300A RMS for 1 second |

Current inputs: 1A secondary
| Operating range |2A RMS continuous |
| Burden |< 0.02VA |
| Overload withstand |6A RMS continuous; 80A RMS for 1 second |

Frequency
| Measurement range |15Hz to 480Hz |
| Calibration frequency |25, 50, 60 or 400Hz (upon order) |

Relay outputs
| Relays |2 relays rated at 3A/250V AC; 3A/30V DC |
| Contacts |2 contacts (SPST Form A) |
| Isolation |Contacts to coil 2000V AC for 1 minute; open contacts 1000V AC |
| Operate / release time |10 ms max. / 5 ms max. |
| Update time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

Communication ports: COM1 RS-232 or RS-422/485 (optional module)
| Port |Optically isolated, 2000V RMS, DB9 female |
| Baud rate |Up to 115.2 kbps |
| Protocols |Modbus RTU, DNP3 and SATEC ASCII |

Communication ports: COM1 Ethernet (optional module)
| Port |Transformer-isolated 10/100BaseT, RJ45 |
| Protocols |Modbus/TCP (port 502), DNP3/TCP (port 20000), GE EGD producer |
| Connections |4 simultaneous (4 Modbus/TCP, or 2 Modbus/TCP + 2 DNP3/TCP) |

Communication ports: COM1 Profibus DP, IEC 61158 (optional module)
| Port |RS-485 optically isolated, DB9 female |
| Baud rate |9600 bit/s to 12 Mbit/s (auto detection) |
| Data |32 bytes input, 32 bytes output |

Communication ports: COM2 RS-422/485
| Port |Optically isolated, 2000V RMS, removable 5-pin connector |
| Baud rate |Up to 115.2 kbps |
| Protocols |Modbus RTU, DNP3 and SATEC ASCII |
| RS-485 network |Up to 32 devices |
| Wire size |Up to 14 AWG (1.5 mm²) |

Real-time clock and memory
| Clock accuracy |Typical error 30 seconds per month at 25°C |
| Log memory |1 Mbyte onboard memory with battery backup |

Warranty
| Product warranty |3 years |
| Warranty of accuracy |10 years |

Digital inputs
| Inputs |2 dry contact inputs |
| Sensitivity |Open at input resistance > 100 kΩ; closed at < 100 Ω |
| Galvanic isolation |2000V RMS |
| Internal power supply |15V |
| Scan time |1 ms |
| Wire size |14 AWG (up to 1.5 mm²) |

Optional analogue inputs
| Inputs |2 optically isolated analogue inputs |
| Ranges (upon order) |±1 mA (1.2 kΩ); 0-1 mA (2.4 kΩ); 0-20 mA (250 Ω); 4-20 mA (250 Ω) |
| Isolation |2000V RMS |
| Accuracy |0.5% FS |
| Scan time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

Optional analogue outputs
| Outputs |2 optically isolated analogue outputs, internal power supply |
| Ranges (upon order) |±1 mA and 0-1 mA (max. load 5 kΩ); 0-20 mA and 4-20 mA (max. load 510 Ω) |
| Isolation |2000V RMS |
| Accuracy |0.5% FS |
| Update time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

Display module
| Display |High-brightness seven-segment LEDs, two 4-digit and one 6-digit windows |
| Keypad |6 push buttons |
| Communication |EIA RS-485 port with 12V supply voltage |
| Connector |DB15, 15 pins |
| Distance |Up to 1000 m (3200 ft) |
| Supply / consumption |12V DC ±10% / 2W |
| Wire size |Up to 14 AWG (1.5 mm²) |

Measurement accuracy
| Voltage |Full scale at input range: 120V x PT at 120V; 400V x PT at 690V. Accuracy: 0.2% reading, 0.01% FS. Conditions: 10% to 120% FS. Range: 0 to 1,150,000V |
| Line current |Full scale at input range: CT. Accuracy: 0.2% reading, 0.02% FS. Conditions: 1% to 200% FS. Range: 0 to 40,000A |
| Neutral current |Accuracy: 0.4% reading |
| Active power |Full scale at input range: 0.36 x PT x CT at 120V; 1.2 x PT x CT at 690V. Accuracy: 0.2% reading, 0.02% FS. Conditions: |PF| ≥ 0.5 (note 1). Range: -10,000,000 kW to +10,000,000 kW |
| Reactive power |Full scale at input range: 0.36 x PT x CT at 120V; 1.2 x PT x CT at 690V. Accuracy: 0.3% reading, 0.04% FS. Conditions: |PF| ≤ 0.9 (note 1). Range: -10,000,000 kvar to +10,000,000 kvar |
| Apparent power |Full scale at input range: 0.36 x PT x CT at 120V; 1.2 x PT x CT at 690V. Accuracy: 0.2% reading, 0.02% FS. Conditions: |PF| ≥ 0.5 (note 1). Range: 0 to 10,000,000 kVA |
| Power factor |Full scale at input range: 1.000. Accuracy: 0.2% FS. Conditions: |PF| ≥ 0.5, I ≥ 2% FSI. Range: -0.999 to +1.000 |
| Frequency |Accuracy: 0.02% reading. Range: 15Hz to 480Hz |
| Total harmonic distortion, THD V (I), %Vf (%If) |Full scale at input range: 999.9. Accuracy: 1.5% reading, 0.1% FS. Conditions: THD ≥ 1%, V (I) ≥ 10% FSV (FSI). Range: 0 to 999.9 |
| Total demand distortion, TDD, % |Full scale at input range: 100. Accuracy: 1.5% FS. Conditions: TDD ≥ 1%, I ≥ 10% FSI. Range: 0 to 100 |
| Active energy, import and export |Class 0.2S under conditions as per AS/IEC 62053-22:2003. Range: 0 to 999,999.999 MWh |
| Reactive energy, import and export |Class 0.2S under conditions as per AS/IEC 62053-22:2003, |PF| ≤ 0.9. Range: 0 to 999,999.999 Mvarh |
| Apparent energy |Class 0.2S under conditions as per AS/IEC 62053-22:2003. Range: 0 to 999,999.999 MVAh |

Note 1: at 80% to 120% of voltage FS, 1% to 200% of current FS and frequency 50/60Hz. PT: external potential transformer ratio. CT: primary current rating of external current transformer. FSV: voltage full scale. FSI: current full scale. Vf: fundamental voltage. If: fundamental current. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not include inaccuracies introduced by the user's potential and current transformers. Accuracy is calculated at a 1-second average. Specifications assume voltage and current waveforms with THD ≤ 5% for kvar, kVA and PF, and a reference operating temperature of 20°C to 26°C. Temperature coefficient: 0.008% / °C. Measurement error is typically less than the maximum error indicated.

## Standards compliance

### Accuracy

- AS/IEC 62053-22 Class 0.2S (1A and 5A versions)
- Accuracy per ANSI C12.20-1998

### Electromagnetic immunity

- EN 50082-1:1992
- EN 50082-2 Generic Immunity Standard, Industrial Environment
- EN 61000-4-2
- ENV 50140:1983
- ENV 50204:1995 (900MHz)
- ENV 50141:1993
- EN 61000-4-4:1995
- EN 61000-4-8:1993

### Electromagnetic emission

- EN 55011:1991
- EN 50081-2 Generic Emission Standard, Industrial Environment
- EN 55022:1994 Class A

### Safety

- EN 61010-1:1993, A2/1995

### Directives complied with

- EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
- LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC

### Communication protocols

- Modbus RTU, Modbus ASCII and Modbus/TCP
- DNP3 and DNP3/TCP
- Profibus DP (IEC 61158)
- GE EGD producer

## Ordering information

MODEL – VOLTAGE – CURRENT – CAL. FREQ. – POWER – I/O MODULE – COMMUNICATION

Model
| Power meter |PM172P-N |
| Power meter including revenue meter |PM172E-N |
| Power meter including revenue meter, harmonic analysis and waveform capture |PM172EH-N |
| PM172E-N transducer version, no display |RPM072 |

Voltage input
| 690V AC nominal voltage input (standard) |No code |
| 120V AC nominal voltage input |U |

Current input
| 5 ampere |5 |
| 1 ampere |1 |
| 5A split core remote high accuracy current sensor |RS5 |
| High Accuracy Current Sensors (order 3 HACS separately) |HACS |

Calibration frequency
| 25Hz |25HZ |
| 50Hz |50HZ |
| 60Hz |60HZ |
| 400Hz |400HZ |

Power supply
| 85 to 264V AC and 88 to 290V DC |ACDC |
| 9.6 to 19V DC |1DC |
| 19 to 37V DC |2DC |
| 37 to 72V DC |3DC |

I/O module
| 2 digital inputs / 2 digital outputs (standard) |No code |
| Additional 2 DI / 2 DO (4 DI / 4 DO in total) |DIO |
| 2 analogue outputs, ±1 mA |AO1 |
| 2 analogue outputs, 0-20 mA |AO2 |
| 2 analogue outputs, 0-1 mA |AO3 |
| 2 analogue outputs, 4-20 mA |AO4 |
| 2 analogue inputs, ±1 mA |AI1 |
| 2 analogue inputs, 0-20 mA |AI2 |
| 2 analogue inputs, 0-1 mA |AI3 |
| 2 analogue inputs, 4-20 mA |AI4 |

Communication
| RS-232/422/485 (standard) |No code |
| Ethernet (TCP/IP) |ETH |
| Profibus DP |PRO |

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 585 KB)](https://satec-global.com.au/documentation/PM172-Power-Revenue-Meter-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-86f7d8a24dcd/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pm172/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)