# PM135 power meter datasheet: specifications and ordering codes

> PM135 datasheet as a web page: Compact Multi-function Power Meter with Modular I/O and Open Protocols. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/pm135/

---

PM135 · DATASHEET

# PM135 power meter datasheet

Compact Multi-function Power Meter with Modular I/O and Open Protocols.

Transcribed from the SATEC Australia datasheet [TBV1.0, 28 September 2026](https://satec-global.com.au/documentation/PM135-Multi-Function-Power-Meter-Datasheet-TBV1-0.pdf) (PDF, 9 pages, 1385 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PM135 is a compact multi-function power meter designed for metering three-phase AC current circuits. With versatile I/O options, communication ports and open protocols, it is suited to integration in utility substation and industrial SCADA systems as well as commercial energy management.

A built-in RS-485 port, optional Ethernet, Profibus or RS-232/422/485 modules and up to 16 digital and analogue I/O points let one meter grow with the site. A backlit LCD with an LED load bar-graph, 25–400 Hz frequency measurement options and dual 4″ round or 92×92 mm square mounting make it a flexible retrofit or new-build choice.

PM135P — Power version offering voltage, current, power and frequency measurements.

PM135E — All PM135P features plus energy measurements, Time-of-Use tariffs and data logging.

PM135EH — All PM135E features plus harmonic analysis to the 40th order.

## Main features

- Accuracy: Class 0.5S per AS/IEC 62053-22 and ANSI C12.20
- Built-in communication: standard RS-485 port
- Optional ports: Ethernet, Profibus DP, RS-232/422/485
- Open protocols: Modbus RTU, DNP3.0, IEC 60870-5-101/104
- Digital and analogue I/O modules: up to 16 I/O
- Dual mounting: 4″ round and 92×92 mm square cutouts
- Broad frequency range: 25–400 Hz measurement options
- LED bar-graph: load shown as a percentage of nominal current
- Embedded logic controller: 16 setpoints with 1-cycle response
- Software: free PAS configuration software and Expertpower cloud platform

## Feature capabilities

### Multi-functional 3-phase power meter

- True RMS volts, amps, power, power factor, neutral current, angles and unbalance for voltage and current, frequency, symmetrical components and more
- Ampere and volt demand meter
- 25, 50, 60 and 400 Hz measurements with 3 decimal digit values
- 128 samples per cycle

### Harmonic analyser (PM135EH only)

- Individual voltage and current harmonic spectrum and harmonic angles up to the 40th order
- Voltage and current THD, TDD and K-Factor

### Real-time waveform capture

- Real-time “scope mode” waveform monitoring via PAS software

### Programmable logic controller

- Embedded programmable controller
- 16 control setpoints with programmable thresholds and delays
- Relay output control
- 1-cycle response time

### Billing / TOU energy meter (PM135E and PM135EH only)

- Accuracy Class 0.5S per AS/IEC 62053-22 and Class 0.2 per IEC 61557-12
- Four-quadrant active and reactive energy polyphase static meter
- Three-phase total and per-phase energy measurements; active, reactive and apparent energy counters
- Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 types of days, 8 tariff changes per day
- Easily programmable tariff calendar schedule
- Automatic daily energy and maximum demand profile log for total energy and tariff registers

### Event and data recording (PM135E and PM135EH only)

- Non-volatile memory for timestamped event and data recording: 48 days for 2 daily TOU records, half-hourly writing of 4 parameters and more than 100 events over the whole period
- Event recorder logging internal diagnostic events and setup changes
- Two data recorders with programmable periodic data logs, automatic daily energy log and maximum demand profile

### Current input options

- 1A or 5A inputs from CT secondary
- 40mA input designed for SATEC HACS current sensors (100–3000A options)
- RS5: dedicated input for 5A rated split-core HACS

### Voltage inputs

- Direct measurement: 0–690V AC

### I/O options

- 4DIOR: 4 digital inputs and 2 relay outputs with 1-cycle update time; unlatched, latched, pulse and KYZ operation; energy pulses; choice of solid state or electromechanical relays
- 12DIOR: 12 digital inputs and 4 relay outputs (with optional Ethernet or additional RS-485 port)
- 4AO: four optically isolated analogue outputs with internal power supply; 0–20mA, 4–20mA, 0–1mA, ±1mA, 0–5mA or ±5mA output; 1-cycle update time
- 8DI: eight digital inputs with 1 ms scan time

### Communication: on-board interface

- Standard 2-wire RS-485

### Communication: optional interfaces

- Ethernet (10/100BaseT)
- Multipurpose RS-232/422/485
- PROFIBUS DP

### Communication: client functions

- Modbus/TCP client over Ethernet
- TCP notification client for sending events or periodic reports to a remote server
- Expertpower client (subscription)

### Communication: protocols

- Modbus RTU and Modbus/TCP
- SATEC ASCII
- DNP3.0 (Level 2)
- IEC 60870-5-101 and IEC 60870-5-104 (optional)

### Applications

- Energy management
- Utility substation and industrial SCADA
- Tariff and TOU energy monitoring
- Renewable energy systems

### Display

- 3×2″ / 76×49 mm backlit LCD
- Adjustable display brightness and update rate
- Auto-scroll with adjustable page and auto-return to a default page
- LED bar-graph showing load as a percentage of nominal (user-definable) load current

### Software support and firmware

- SATEC Power Analysis Software (PAS) for full configuration and data acquisition, free to download
- Expertpower web-based energy management platform (subscription)
- eXpertConnect™ App for convenient mobile access to energy data
- Any third-party software supporting the open protocols
- Firmware easily upgraded through the serial or Ethernet port

### Meter security

- Password protection of meter setups and accumulated data against unauthorised changes

### Real-time clock

- Internal battery-backed clock with typical retention of 36 months

### Unique design

- Pass-through CT connection
- Built-in auxiliary terminal for loose CT wires
- Dual panel mounting: 92×92 mm square or 4″ round cutout

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Voltage inputs
| Installation |Category III |
| Nominal voltage (L-N/L-L) |100/400V AC; 230/400V AC; 400/690V AC |
| Operating range (L-N/L-L) |Nominal voltage +25% tolerance |
| Burden for 120V |< 0.04 VA |
| Over-voltage withstand |1000V AC continuous, 2000V AC for 1 second |
| Input impedance |1 MΩ |
| Wire size |Up to 12 AWG (up to 3.5 mm²) |

Current inputs (via CT)
| Wire size |12 AWG (up to 3.5 mm²) |
| Galvanic isolation |2,500V |

Current inputs: 5A secondary
| Operating range |Continuous 10A RMS |
| Burden |< 0.2 VA @ In = 5A (12 AWG wire, 1 m long) |
| Overload withstand |15A RMS continuous, 300A RMS for 1 second (12 AWG wire) |

Current inputs: 1A secondary
| Operating range |Continuous 2A RMS |
| Burden |< 0.02 VA @ In = 1A (12 AWG wire, 1 m long) |
| Overload withstand |3A RMS continuous, 80A RMS for 1 second (12 AWG wire) |

Current inputs: HACS / RS5 remote sensors
| |Depends on sensor rating. See the HACS datasheet. |

Sampling
| Sampling rate |Up to 256 samples per cycle |
| Waveforms |128 samples per cycle (via communications) |

Power supply: 120/230V AC-DC option
| Rated input |85–265V AC @ 50/60 Hz; 88–290V DC |
| Burden |9 VA |
| Isolation |1500V DC |
| Input to ground |2500V AC |

Power supply: 12V DC option
| Rated input |9.5–18V DC |
| Burden |4 VA |
| Isolation |1500V DC |

Power supply: 24/48V DC option
| Rated input |18.5–58V DC |
| Burden |4 VA |
| Isolation |1500V DC |

Power supply
| Wire size |Up to 12 AWG (up to 3.5 mm²) |

Real-time clock
| Type |Battery-backed clock |
| Accuracy |Typical error 7 seconds per month @ 25°C (±2.5 ppm) |
| Retention time |Typically 36 months |

Display
| Screen |3×2″ / 76×49 mm backlit LCD |
| Load bar-graph |3-colour LED (40–110%) |
| Keypad |6 push buttons |

Electromechanical relay (optional)
| Contact |Dry contact, 1 contact (SPST Form A) |
| Rating |5A/250V AC; 5A/30V DC |
| Isolation, contacts to coil |3000V AC @ 1 min |
| Isolation, open contacts |750V AC |
| Operate time |10 ms max |
| Release time |5 ms max |
| Update time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

Solid state relay (optional)
| Contact |Dry contact, 1 contact (SPST Form A) |
| Rating |0.15A/250V AC/DC |
| Galvanic isolation |3750V AC @ 1 min |
| Operate time |1 ms max |
| Release time |0.25 ms max |
| Update time |1 cycle |
| Connector type |Removable, 4 pins |
| Wire size |14 AWG (up to 1.5 mm²) |

Analogue outputs (optional)
| Ranges (upon order) |±1 mA, max. load 5 kΩ (100% overload); 0–20 mA, max. load 510 Ω; 4–20 mA, max. load 510 Ω; 0–1 mA, max. load 5 kΩ (100% overload) |
| Isolation |2500V AC @ 1 min |
| Power supply |Internal |
| Accuracy |0.5% FS |
| Update time |1 cycle |
| Connector type |Removable, 5 pins |
| Wire size |14 AWG (up to 1.5 mm²) |

Digital inputs (optional)
| Type |Dry contacts internally wetted @ 24V DC, or wet contact @ 250V DC (12DI/4DO only) |
| Sensitivity |Open @ input resistance > 100 kΩ; closed @ input resistance < 100 Ω |
| Galvanic isolation |3750V AC @ 1 min |
| Internal power supply |24V DC (4DI/2DO or 12DI/4DO) |
| External power supply |250V DC (12DI/4DO only) |
| Scan time |1 ms |
| Connector type |Removable, 5 pins |
| Wire size |14 AWG (up to 1.5 mm²) |

COM1: RS-485 (built in)
| Type |RS-485 optically isolated port |
| Isolation |3000V AC @ 1 min |
| Baud rate |Up to 115.2 kbps |
| Supported protocols |Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101 |
| Connector type |Removable, 3 pins |
| Wire size |Up to 14 AWG (up to 1.5 mm²) |

COM2: Ethernet (optional module)
| Type |Transformer-isolated 10/100BaseT Ethernet port |
| Supported protocols |Modbus/TCP (port 502), IEC 60870-5-104, DNP3/TCP (port 20000) |
| Simultaneous connections |4 (2 Modbus/TCP + 2 DNP3/TCP) |
| Connector type |RJ45 modular |
| Isolation |1,500V DC @ 1 min |

Independent module or add-on to the 12DIOR module

Environmental conditions
| Operating range, unit stand-alone |−30°C to 70°C (−22°F to 158°F) |
| Operating range, with add-on modules |−30°C to 60°C (−22°F to 140°F) |
| Storage temperature |−40°C to 85°C (−40°F to 185°F) |
| Humidity |0 to 95% non-condensing |

COM2: PROFIBUS DP, IEC 61158 (optional)
| Type |RS-485 optically isolated Profibus interface |
| Connector type |Removable, 5 pins |
| Baud rate |9600 bit/s to 12 Mbit/s (auto detection) |
| Data |32 bytes input, 32 bytes output |
| Supported protocols |PROFIBUS DP |

COM2: RS-232/422/485 (optional)
| Type |RS-232 or RS-422/485 optically isolated port |
| Isolation |3000V AC @ 1 min |
| Baud rate |Up to 115.2 kbps |
| Supported protocols |Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101 |
| Connector type |Removable 5 pins (RS-422/485); DB9 (RS-232) |
| Wire size |Up to 14 AWG (up to 1.5 mm²) |

Construction
| Weight |0.70 kg (1.54 lb) |
| Dimensions (H×W×D) |114×114×109 mm (4.5×4.5×4.3″) |
| Panel cutout |92×92 mm square or 4″ round |

Construction: materials
| Case enclosure |PC/ABS plastic blend |
| Front panel |PC plastic |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Labels |Polyester film (UL94-V0) |
| Packaging |Carton and Stratocell® (polyethylene foam) brackets |

## Standards compliance

### Accuracy

- Complies with AS/IEC 62053-22, Class 0.5S
- Meets ANSI C12.20-1998, Class 10 0.5%

### Accuracy: complies with IEC 61557-12 (PMD)

- Total apparent power: 0.2%
- Total active energy: 0.5/0.2%
- Total reactive energy: 0.5%
- Frequency: 0.05%
- Current: 0.2%
- Neutral current: 0.2%
- Voltage: 0.2%
- Power factor: 0.2%
- THDV, THDI: 1%

### Electromagnetic immunity: complies with IEC 61000-6-2

- IEC 61000-4-2 level 3: Electrostatic Discharge
- IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
- IEC 61000-4-4 level 3: Electric Fast Transient
- IEC 61000-4-5 level 3: Surge
- IEC 61000-4-6 level 3: Conducted Radio Frequency
- IEC 61000-4-8: Power Frequency Magnetic Field

### Electromagnetic immunity

- Meets ANSI/IEEE C37.90.1: Fast Transient SWC

### Electromagnetic emission

- Complies with IEC 61000-6-4: Radiated/Conducted Class A
- Complies with IEC CISPR 22: Radiated/Conducted Class A

### Safety

- Meets IEC 61010-1:2006

### AC and impulse insulation

- Complies with IEC 62052-11: 2500V AC for 1 minute
- 6 kV/500 Ω @ 1.2/50 µs impulse

## Ordering information

MODEL – CURRENT – CAL. FREQ. – RESOLUTION – POWER – PROTOCOL – MOUNTING

Models
| Power version |PM135P |
| Energy version |PM135E |
| Energy and harmonic version |PM135EH |

Current inputs
| 5 Ampere |5 |
| 1 Ampere |1 |
| 5A split-core remote high accuracy current sensor (HACS), 50/60 Hz only |RS5 |
| High Accuracy Current Sensors (HACS), 50/60 Hz only; requires ordering of 3 HACS |HACS |

Calibration at frequency
| 25 Hz* |25HZ |
| 50 Hz |50HZ |
| 60 Hz |60HZ |
| 400 Hz* |400HZ |

Display resolution
| Low resolution 1A, 1V |– |
| High resolution 0.01A, 0.1V |H |

Power supply
| 85–265V AC and 85–290V DC |ACDC |
| 9.5–18V DC |1DC |
| 18.5–58V DC (24V DC, 48V DC) |23DC |

Communication protocol
| Modbus and DNP3.0 |– |
| Modbus and IEC 60870-5-101/104** |870 |

Mounting
| Panel mount (standard) |– |
| DIN rail mounting |DIN |

* Supported by 1A and 5A models only. ** IEC 60870-5-104 requires Ethernet.

### Expansion modules

Maximum of 1 expansion module per instrument. Modules can be ordered separately.

Expansion module: analogue outputs
| 4 analogue outputs: ±1mA |AO1 |
| 4 analogue outputs: 0–20mA |AO2 |
| 4 analogue outputs: 0–1mA |AO3 |
| 4 analogue outputs: 4–20mA |AO4 |
| 4 analogue outputs: 0–5mA |AO7 |
| 4 analogue outputs: ±5mA |AO8 |

Expansion module: communication ports
| Ethernet (TCP/IP) |ETH |
| PROFIBUS |PRO |
| RS-232/422/485 |RS232 |

Expansion module: digital I/O
| 4 digital inputs (dry contact) / 2 relay outputs 250V/5A AC |DIOR |
| 4 digital inputs (dry contact) / 2 SSR outputs 250V/0.1A AC |DIOS |
| 8 digital inputs (dry contact) |8DI |
| 12 digital inputs / 4 relay outputs 250V/5A AC |12DIOR |

12DIOR: digital input rating
| Dry contact |DRC |
| 48V |48V |
| 125V |125V |
| 250V |250V |

12DIOR: communication port
| None |– |
| RS-485 |485 |
| Ethernet |ETH |

12DIOR order string example: 12DIOR-DRC-ETH.

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 1385 KB)](https://satec-global.com.au/documentation/PM135-Multi-Function-Power-Meter-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-3c2f9c4a5618/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pm135/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [PM135 clock backup and the TOU module battery](https://satec-global.com.au/support/articles/pm135-clock-backup-tou-module-battery/)
- [Identifying your PM135: model, options, clock and wiring drawing](https://satec-global.com.au/support/articles/pm135-identify-model-options-wiring/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).