# PM130E DC energy meter datasheet: specifications and ordering codes

> PM130E DC datasheet as a web page: Multi-function direct current (DC) energy meter for substations, data centres and renewables. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.1.

Source page: https://satec-global.com.au/support/datasheets/pm130e-dc/

---

PM130E DC · DATASHEET

# PM130E DC energy meter datasheet

Multi-function direct current (DC) energy meter for substations, data centres and renewables.

Transcribed from the SATEC Australia datasheet [TBV1.1, 17 September 2026](https://satec-global.com.au/documentation/PM130E-DC-metering-datasheet-TBV1-1.pdf) (PDF, 8 pages, 391 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PM130E DC is a multi-function direct current (DC) energy meter designed for single channel DC metering. Measuring DC volts, amps, power, energy and demand to Class 0.5/1.0 accuracy per AS/IEC 62053-41, it is built for utility substations, data centres, renewable energy systems, SCADA integration and building management systems.

Current is measured via a DC shunt (single-channel), with direct voltage measurement to 670 V DC and extended ranges to 1500 V DC — or higher on application — using the SATEC Voltage Ratio Module (VRM). Every unit ships with a standard RS-485 port, with optional Ethernet, 4G modem and PROFIBUS interfaces, up to 16 digital/analogue I/O, dual 92×92 mm / 4-inch round panel mounting and an optional DIN-rail mounting kit.

## Current input options

- 

### PM130E-DCC-RS5

DC shunt input — single-channel metering via a 50, 60, 75 or 100 mV shunt (shunt dependent)

- 

### + SATEC VRM

Optional Voltage Ratio Module extends direct voltage measurement beyond 670 V to 1500 V DC

## Main features

- Accuracy: Class 0.5/1.0 per AS/IEC 62053-41
- Communication: built-in RS-485; optional Ethernet, 4G modem, PROFIBUS
- Open protocols: Modbus RTU, DNP3.0, IEC 60870-5-101/104
- Digital and analogue I/O modules: up to 16 I/O
- Dual mounting: suitable for 4-inch round and 92×92 mm square cutouts
- DIN-rail mounting option
- LED bar-graph: displays load as a percentage of nominal current
- Non-volatile event and data recording (48 days)

## Feature capabilities

### DC energy metering

- DC volts
- DC amps
- DC power
- DC energy
- DC ampere demand
- DC volt demand

### Billing / TOU energy meter (PM130E-DCC only)

- Total and per-channel energy measurements
- Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 day types, 8 tariff changes per day
- Easy programmable tariff calendar schedule
- Automatic daily energy and maximum demand profile log for total and tariff registers

### Programmable logical controller

- Embedded programmable controller
- 16 control setpoints — programmable thresholds and delays
- Optional relay output control and alarming (load control)
- 1-cycle response time (20 ms @ 50 Hz)

### Event and data recording

- Non-volatile memory: 48 days for 2 daily TOU records, half-hourly writing of 4 parameters, over 100 events recorded during the period
- Event recorder for internal diagnostic events and setup changes
- Two data recorders — periodic data logs plus automatic daily energy and max-demand profile log

### Display

- 3-row (2×4 characters + 1×5 characters) bright LED display, adjustable brightness and update rate
- Auto-scroll with adjustable page exposition time; auto-return to a default page
- LED bar graph showing percent load against a user-definable nominal load current

### Real-time clock

- Standard meter clock: non-backed, ~1 min/month error @ 25°C, 30-second retention
- TOU module clock: battery-backed, ~7 s/month error @ 25°C (±2.5 ppm), 36-month retention

### Voltage input options

- Direct measurement: 0–670 V DC
- Extended range to 1500 V DC via the SATEC Voltage Ratio Module (VRM)
- Ranges above 1500 V DC on application — measuring up to 3000 V DC

### Current options

- DC shunts — 50, 60, 75 or 100 mV (shunt dependent)

### Digital and analogue I/O

- TOD (TOU+4DI) — 4 digital inputs, 1 ms scan, battery-backed RTC; last 5 input-change events with timestamps
- DIOR — 4 digital inputs, 2 relay outputs, 1-cycle update; unlatched, latched, pulse and KYZ; solid-state or electromechanical
- 12DIOR — 12 digital inputs, 4 relay outputs, optional Ethernet or additional RS-485 port
- 4AO — 4 optically isolated analogue outputs (0–20 mA / 4–20 mA / 0–1 mA / ±1 mA), 1-cycle update
- 8DI — 8 digital inputs, 1 ms scan time

### Communication

- On-board: standard 2-wire RS-485
- Optional: Ethernet (10/100Base-T), 4G modem, multipurpose RS-232/422/485, PROFIBUS
- Client (Modbus/TCP over Ethernet or 4G): TCP notification client for event/periodic reports to a remote server; Expertpower client on a subscription basis
- Protocols: Modbus RTU, SATEC ASCII, DNP 3.0 (Level 2), IEC 60870-5-101 (standard), IEC 60870-5-104 (requires Ethernet)

### Unique design and meter security

- Pass-through CT connection for minimal burden
- Built-in auxiliary terminal for loose CT wires
- Dual panel mounting — 92×92 mm square or 4-inch round cutout
- Password security protecting meter setups and accumulated data from unauthorised changes

### Software support and firmware

- Power Analysis Software (PAS) — SATEC’s free configuration and data-acquisition tool
- Expertpower — SATEC’s internet-based energy management platform (subscription)
- eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics
- Firmware upgrade via a serial or Ethernet port

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Environmental conditions
| Operating temperature |−30°C to 60°C (−22°F to 140°F) |
| Storage temperature |−40°C to 85°C (−40°F to 185°F) |
| Humidity |0–95% RH, non-condensing |

Construction and materials
| Weight |0.70 kg (1.54 lb) |
| Dimensions [H×W×D] |114×114×109 mm (4.5×4.5×4.3″) |
| Case enclosure |PC/ABS blend plastic |
| Front panel |PC plastic |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Packaging case |Carton & Stratocell® (PE foam) brackets |
| Labels |Polyester film (UL94-V0) |

Display
| Type |High-brightness 7-segment LED, two 4-digit + one 5-digit window |
| Bar graph |3-colour LED, 40–110% load |
| Keypad |6 push buttons |

Voltage inputs
| Nominal voltage (L-N) |0–670 V DC · use VRM above 670 V DC* |
| Over-voltage withstand |1000VAC continuous, 2000VAC for 1 s |
| Input impedance |1 MΩ |
| Wire size |Up to 12 AWG (3.5 mm²) |

* Measuring up to 3000 V DC on application.

Current inputs
| Type |DC shunts |
| Wire size |12 AWG (3.5 mm²) |
| Galvanic isolation |3500VAC |

Power supply
| 120/230V AC-DC option |85–265V AC 50/60/400 Hz, 88–290VDC · 9VA burden · 2500VAC isolation (input to ground) |
| 12VDC option |9.5–18V DC · 4VA burden · 1500VDC isolation |
| 24/48VDC option |18.5–58VDC · 4VA burden · 1500VDC isolation · up to 12 AWG (3.5 mm²) wire |

Real-time clock
| Standard meter clock |Non-backed · ~1 min/month error @ 25°C · 30 s retention |
| TOU module clock |Battery-backed · ~7 s/month error @ 25°C (±2.5 ppm) · 36-month retention |

Optional relay outputs
| Electromechanical (4DI/DO or 12DI/DO) |2 or 4 relays, 5A/250VAC or 5A/30VDC, 1 contact (SPST Form A) |
| Galvanic isolation |3000VAC (contacts–coil) · 750VAC (open contacts) |
| Operate / release time |10 ms max / 5 ms max |
| Wire size |14 AWG (1.5 mm²) |
| Solid-state (4DI/2DO) |2 relays, 0.15A/250V AC/DC, 1 contact (SPST Form A) |
| Galvanic isolation |3750VAC 1 min |
| Operate / release time |1 ms max / 0.25 ms max |

Optional digital inputs
| Type |4 or 12 inputs (4DI/2DO or 12DI/4DO module); dry contact, internally wetted @ 24VDC, or wet contact @ 250VDC (12DI/4DO only) |
| Sensitivity |Open >100 kΩ · closed <100 Ω |
| Galvanic isolation |3750VAC 1 min |
| Scan time |1 ms |

Optional analogue outputs
| Ranges (on order) |±1 mA · 0–20 mA · 4–20 mA · 0–1 mA |
| Isolation |2500VAC 1 min |
| Accuracy |0.5% FS |
| Update time |1 cycle |

Communication ports
| COM1 — RS-485 (built-in) |Optically isolated |
| Isolation / baud |3000VAC 1 min · up to 115.2 kbps |
| Protocols |Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101 |
| COM2 (optional module): Ethernet |Transformer-isolated 10/100BaseT · Modbus/TCP (502), IEC 60870-5-104, DNP3/TCP (20000) · 4 simultaneous connections |
| COM2 (optional module): Cellular port |Modbus/TCP (502), DNP3/TCP (20000) · SMA connector |
| COM2 (optional module): PROFIBUS DP (IEC 61158) |RS-485 isolated · 9600 bit/s–12 Mbit/s auto-detect · 32 bytes in/out |
| COM2 (optional module): RS-232/422/485 |Isolated · up to 115.2 kbps · Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101 |

The printed sub-heading row 'COM2 (optional module)' is joined into the labels of the four rows under it.

## Standards compliance

### Accuracy

- Complies with AS/IEC 62053-41, Class 0.5/1.0 — accuracy subject to DC shunt input
- Meets ANSI C12.20-1998, Class 10, 0.5%
- Complies with IEC 61557-12 (PMD): Total DC Power 0.5 · Total DC Energy 0.5 · DC Current 0.05 · DC Voltage 0.05

### Electromagnetic immunity

- Complies with IEC 61000-6-2
- IEC 61000-4-2 level 3 — electrostatic discharge
- IEC 61000-4-3 level 3 — radiated electromagnetic RF fields
- IEC 61000-4-4 level 3 — electrical fast transient
- IEC 61000-4-5 level 3 — surge
- IEC 61000-4-6 level 3 — conducted radio frequency
- IEC 61000-4-8 — power-frequency magnetic field
- Meets ANSI/IEEE C37.90.1 — fast transient SWC

### Electromagnetic emission

- Complies with IEC 61000-6-4 — radiated/conducted Class A
- Complies with IEC CISPR 22 — radiated/conducted Class A

### Safety and construction

- Meets IEC 61010-1:2006

### AC and impulse insulation

- Complies with IEC 62052-11 — 2500VAC for 1 minute
- 6kV/500Ω @ 1.2/50 μs impulse

## Ordering information

MODEL – CURRENT – DISPLAY – POWER – PROTOCOL – MOUNTING – TEST/CERT

Model
| DC energy power version |PM130E-DCC |

Current inputs
| DC shunt |RS5 |

Display resolution
| Low resolution — 1A, 1V |— |
| High resolution — 0.01A, 0.1V |H |

Power supply
| 85–265V AC & 85–290V DC |ACDC |
| 9.5–18V DC |1DC |
| 18.5–58V DC (24VDC, 48VDC) |23DC |

Communication protocol
| Modbus and DNP 3.0 |— |
| Modbus and IEC 60870-5-101/104† |870 |

Mounting
| Panel mount (standard) |— |
| DIN rail mounting |DIN |

Testing
| Full functional test, calibration at various work loads & detailed test report |— |

† –104 requires Ethernet — does not work over a cellular network.

### Expansion modules

Max. 1 per instrument, order separately.

Expansion module
| 4 Analogue Outputs: ±1mA / 0–20mA / 0–1mA / 4–20mA / 0–3mA / ±3mA / 0–5mA / ±5mA |AO1–AO8 |
| Ethernet (TCP/IP) |ETH |
| PROFIBUS |PRO |
| RS232/422/485 |RS232 |
| 4G Modem** — G=Europe, V=Verizon (US), A=AT&T (US), T=Telstra (AUS) |T4x |
| 4 Digital Inputs / 2 Relay Outputs, 250V/5A AC |DIOR |
| 4 Digital Inputs / 2 SSR Outputs, 250V/0.1A AC |DIOS |
| TOU + 4 Digital Inputs (RTC battery) |TOD |
| 8 Digital Inputs (dry contact) |8DI |
| 12 Digital Inputs / 4 Relay Outputs, 250V/5A AC |12DIOR |
| 12DIOR digital input rating — DRC, 48V, 125V or 250V |DRC / 48V / 125V / 250V |
| 12DIOR communication port — none, RS-485 or Ethernet |— / 485 / ETH |

** Does not support the 870 protocol; supplied with a bendable antenna.

## Downloads and related

- [Download the datasheet (PDF, TBV1.1, 391 KB)](https://satec-global.com.au/documentation/PM130E-DC-metering-datasheet-TBV1-1.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-48ad5200ac3c/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).