# PM130 PLUS power meter datasheet: specifications and ordering codes

> PM130 PLUS datasheet as a web page: High Performance Multi-function Power Meter. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/pm130-plus/

---

PM130 PLUS · DATASHEET

# PM130 PLUS power meter datasheet

High Performance Multi-function Power Meter.

Transcribed from the SATEC Australia datasheet [TBV1.0, 2 September 2026](https://satec-global.com.au/documentation/PM130E-PLUS-Datasheet.pdf) (PDF, 7 pages, 849 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The PM130 PLUS is a compact multi-function, three-phase AC power meter designed to meet the requirements of users ranging from electrical panel builders to substation operators. Measurement inputs and power supply comply with Measuring Category II.

The series offers a bright multi-row LED display, a standard RS-485 port with an optional plug-in second communications module, and a selection of digital I/O and analogue output modules — with all models suited to both 4-inch round and 92×92 mm square panel cutouts.

PM130P: Base model — voltage, current, power & frequency measurement and control.

PM130E: Adds energy measurement & data logging.

PM130EH: Adds harmonic analysis to the PM130E feature set.

## Main features

- 3 voltage inputs and 3 current-transformer-isolated AC inputs for direct connection to the power line or via potential and current transformers
- True RMS volts, amps, power, power factor, neutral current, voltage and current unbalance, frequency
- Ampere/Volt demand meter
- 25/50/60/400 Hz measurement capability
- Selection of I/O plug-in modules from 4DI/2DO up to 12DI/4RO, with communications
- Standard RS-485 port plus an optional plug-in RS-232/422/485, Ethernet or Profibus module
- Dual panel mounting — 92×92 mm square or 4-inch round cutout

## Feature capabilities

### Billing / TOU energy meter (PM130E and PM130EH only)

- Class 0.5S IEC 62053-22 four-quadrant active and reactive energy polyphase static meter
- Three-phase total and per-phase energy measurement — active, reactive and apparent energy counters
- Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 day types, 8 tariff changes per day
- One-time programmable tariff calendar schedule
- Automatic daily energy and maximum demand profile log for total and tariff registers

### Harmonic analyser (PM130EH only)

- Voltage and current THD, current TDD and K-Factor, up to the 40th order harmonic
- Voltage and current harmonic spectrum and angles

### Real-time waveform capture

- Real-time "scope mode" waveform monitoring
- Simultaneous 6-channel, one-cycle waveform capture at 64 samples per cycle
- Accessed via Power Analysis Software (PAS), Expertpower or the eXpertConnect™ App

### Programmable logical controller

- Embedded programmable controller
- 16 control setpoints — programmable thresholds and delays
- Relay output control
- 1-cycle response time

### Event and data recording (PM130E and PM130EH only)

- Non-volatile memory for long-term event and data recording
- Event recorder for internal diagnostic events and setup changes
- Two data recorders — periodic data logs plus automatic daily energy and max-demand profile log

### Display

- 3-row (2×4 characters + 1×5 characters) bright LED display, adjustable update time and brightness
- Auto-scroll with adjustable page exposition time; auto-return to a default page
- LED bar graph showing percent load against a user-definable nominal load current

### Real-time clock

- Internal clock with 20-second retention time
- Optional battery backup via the TOU+4DI module

### I/O options

- TOU+4DI — 4 digital inputs, 1 ms scan time, battery-backed real-time clock, records the last five input-change events with timestamps
- 4DIO — 4 digital inputs and 2 relay outputs, 1-cycle update; unlatched, latched, pulse and KYZ operation; solid-state or electromechanical relay option
- 12DIO — 12 digital inputs, 4 relay outputs, optional Ethernet or RS-485 port
- 4AO — 4 optically isolated analogue outputs, internal power supply; 0–20 mA / 4–20 mA / 0–1 mA / ±1 mA, 1-cycle update

### Communications

- Standard 2-wire RS-485 port
- Protocols: Modbus RTU, ASCII, DNP3.0; optional IEC 60870-5-101; with Ethernet: Modbus/TCP, DNP3/TCP; optional IEC 60870-5-104
- Expertpower client for SATEC's Expertpower internet services (via Ethernet)
- TCP notification client to a remote Modbus/TCP server, on event or on a time basis (via Ethernet)
- eXpertConnect™ App — connects directly to the meter for on-site setup and readings

### Measurement

- Direct voltage measurement up to 690 V
- 5A — up to 10A via conventional 5A CTs (see the solid-core and split-core current transformer ranges)
- 1A — up to 2A via conventional 1A CTs (see the solid-core and split-core current transformer ranges)
- HACS — remote sensors from 100 A up to 3000 A with built-in shorting circuit; Class 0.5S system accuracy (meter plus sensor); requires 3× HACS ordered separately
- RS5 — a separate connection scheme underneath HACS: remote split-core sensor for straightforward retrofit onto a 5A conventional CT circuit; requires 3× RS5 HACS ordered separately

### Unique design

- Pass-through CT connection for minimal burden
- Auxiliary CT connection terminal for simple installation
- Dual panel mounting — 92×92 mm square or 4-inch round cutout
- Add-on modular design for a second communications port, digital I/O or analogue outputs

### Meter security

- Password security protecting meter setups and accumulated data from unauthorised changes

### Upgradeable firmware

- Firmware upgrade via a serial or Ethernet port

### Software support

- PAS — SATEC's bundled configuration and data-acquisition tool, including waveforms, phasors and harmonics
- Expertpower — SATEC's internet-based energy management software, with no client software installation required
- eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Environmental conditions
| Operating temperature |−30°C to 60°C (−22°F to 140°F) |
| Storage temperature |−40°C to 85°C (−40°F to 185°F) |
| Humidity |0–95% RH, non-condensing |

Construction and materials
| Weight |0.70 kg (1.54 lb) |
| Dimensions [H×W×D] |114×114×109 mm (4.5×4.5×4.3") |
| Case enclosure |PC/ABS blend plastic |
| Front panel |PC plastic |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Labels |Polyester film (UL94-V0) |

Power supply
| 120/230V AC-DC option |85–265V AC 50/60/400 Hz, 88–290VDC · 9VA burden · 2500V AC isolation (input to ground) |
| 12VDC option |9.5–18V DC · 4VA burden · 1500V DC isolation |
| 24/48VDC option |18.5–58VDC · 4VA burden · 1500VDC isolation · up to 12 AWG (3.5 mm²) wire |

Voltage inputs
| Operating range |690VAC line-to-line, 400VAC line-to-neutral |
| Direct / via PT |Up to 790VAC L-L, up to 460VAC L-N |
| Input impedance |1000 kΩ |
| Burden @ 400V / 120V |<0.4 VA / <0.04 VA |
| Over-voltage withstand |1000VAC continuous, 2000VAC for 1 s |
| Wire size |Up to 12 AWG (3.5 mm²) |

Current inputs (via CT)
| Wire size |12 AWG (3.5 mm²) |
| Galvanic isolation |3500VAC |
| 5A secondary / RS5 |Continuous 10A RMS · <0.2VA burden @ In=5A · overload 15A RMS continuous, 300A RMS 1 s |
| 1A secondary |Continuous 2A RMS · <0.02VA burden @ In=1A · overload 3A RMS continuous, 80A RMS 1 s |
| Standard CT range |Solid-core and split-core current transformers, 5A-3000A primary |
| HACS remote sensors |100–3000 A per sensor rating — see the HACS datasheet |

Sampling and resolution
| Sampling rate |128 samples/cycle |
| Display/measurement resolution |Low (1A, 1V) or high (0.01A, 0.1V) — field-programmable in the meter; no factory order code required |

Optional relay outputs: electromechanical (4DI/DO or 12DI/DO module)
| Rating |2 or 4 relays, 5A/250VAC or 5A/30VDC, 1 contact (SPST Form A) |
| Galvanic isolation |3000VAC (contacts–coil) · 750VAC (open contacts) |
| Operate / release time |10 ms max / 5 ms max |
| Wire size |14 AWG (1.5 mm²) |

Optional relay outputs: solid-state (4DI/2DO module)
| Rating |2 relays, 0.15A/250V AC/DC, 1 contact (SPST Form A) |
| Galvanic isolation |3750VAC 1 min |
| Operate / release time |1 ms max / 0.25 ms max |

Optional digital inputs
| Type |4 or 12 inputs (4DI/2DO or 12DI/4DO module); dry contact, internally wetted @ 24VDC, or wet contact @ 250VDC (12DI/4DO only) |
| Sensitivity |Open >100 kΩ · closed <100 Ω |
| Galvanic isolation |3750VAC 1 min |
| Scan time |1 ms |

Optional analogue outputs
| Ranges (on order) |±1 mA · 0–20 mA · 4–20 mA · 0–1 mA |
| Isolation |2500VAC 1 min |
| Accuracy |0.5% FS |
| Update time |1 cycle |

Communication ports: COM1 — RS-485
| Isolation / baud |3000VAC 1 min · up to 115.2 kbps |
| Protocols |Modbus RTU, DNP3, SATEC ASCII |

Communication ports: COM2 (optional module)
| Ethernet |Transformer-isolated 10/100BaseT · Modbus/TCP (502), DNP3/TCP (20000) · 4 simultaneous connections |
| App connection |eXpertConnect™ App — direct meter connection for setup and readings |
| Profibus DP (IEC 61158) |RS-485 isolated · 9600 bit/s–12 Mbit/s auto-detect · 32 bytes in/out |
| RS-232/422/485 |Isolated · up to 115.2 kbps · Modbus RTU, DNP3, SATEC ASCII |

Real-time clock
| Standard meter clock |Non-backed · ~1 min/month error @ 25°C · 30 s retention |
| TOU module clock |Battery-backed · ~7 s/month error @ 25°C (±2.5ppm) · 36-month retention |

Display module
| Type |High-brightness 7-segment LED, two 4-digit + one 5-digit window |
| Bar graph |3-colour LED, 40–110% load |
| Keypad |6 push buttons |

## Standards compliance

### Accuracy

- Complies with IEC 62053-22, Class 0.5S (PM130E / PM130EH)
- Meets ANSI C12.20-1998, Class 10, 0.5%

### Electromagnetic immunity

- Complies with IEC 61000-6-2
- IEC 61000-4-2 level 3 — electrostatic discharge
- IEC 61000-4-3 level 3 — radiated electromagnetic RF fields
- IEC 61000-4-4 level 3 — electrical fast transient
- IEC 61000-4-5 level 3 — surge
- IEC 61000-4-6 level 3 — conducted radio frequency
- IEC 61000-4-8 — power-frequency magnetic field
- Meets ANSI/IEEE C37.90.1 — fast transient SWC

### Electromagnetic emission

- Complies with IEC 61000-6-4 — radiated/conducted Class A
- Complies with IEC CISPR 22 — radiated/conducted Class A

### Safety and construction

- Meets IEC 61010-1:2006

### AC and impulse insulation

- Complies with IEC 62052-11 — 2500VAC for 1 minute
- 6kV/500Ω @ 1.2/50 μs impulse

## Ordering information

MODEL – CURRENT – CALIBRATION – POWER – PROTOCOL – MOUNTING – MODULE

Model
| Power version |PM130P-PLUS |
| Energy & harmonic version |PM130EH-PLUS |
| Energy only |PM130E-PLUS |

Current inputs
| 5 Ampere |5 |
| 1 Ampere |1 |
| High Accuracy Current Sensors (HACS) — 100–3000A, requires 3× HACS ordered separately |HACS |
| RS5 — remote split-core sensor, retrofit scheme underneath HACS, requires 3× RS5 HACS ordered separately |RS5 |

Calibration frequency
| 25 Hz / 50 Hz / 60 Hz / 400 Hz |25HZ / 50HZ / 60HZ / 400HZ |

Power supply
| 85–265V AC / 85–290V DC |ACDC |
| 9.5–18V DC |1DC |
| 18.5–58V DC (24VDC, 48VDC) |23DC |

Communication protocol
| Modbus and DNP 3.0 |— |
| Modbus and IEC 60870-101/104 |870 |

Mounting
| Panel mount (standard) |— |
| DIN rail mounting |DIN |

Expansion module (max. 1 per instrument, order separately) — see Expansion modules below.

### Expansion modules

Max. 1 per instrument, order separately.

Expansion module
| 4 Analogue Outputs: ±1mA / 0–20mA / 0–1mA / 4–20mA / 0–3mA / ±3mA / 0–5mA / ±5mA |AO1–AO8 |
| Ethernet (TCP/IP) |ETH |
| PROFIBUS |PRO |
| RS232/422/485 |RS232 |
| 4 Digital Inputs / 2 Relay Outputs, 250V/5A AC |DIOR |
| 4 Digital Inputs / 2 SSR Outputs, 250V/0.1A AC |DIOS |
| TOU + 4 Digital Inputs |TOD |
| 12 Digital Inputs (dry contact) / 4 Relay Outputs 250V/5A AC |12DIOR-DRC |
| 12 Digital Inputs (250VDC) / 4 Relay Outputs 250V/5A AC |12DIOR-250V |
| 12DIOR variants with Ethernet or RS-485 - optional |…-ETH / …-485 |

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 849 KB)](https://satec-global.com.au/documentation/PM130E-PLUS-Datasheet.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-7463d8aba840/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pm130-plus/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [Can I replace the clock battery in a PM130 PLUS TOU module?](https://satec-global.com.au/support/articles/pm130-plus-tou-module-clock-battery/)
- [Which PM130 PLUS model and current input do I have?](https://satec-global.com.au/support/articles/pm130-plus-model-and-current-input/)
- [Which PM130 PLUS wiring diagram applies to my installation?](https://satec-global.com.au/support/articles/pm130-plus-which-wiring-diagram/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).