1000A Hall Effect solid core DC current sensor.

Transcribed from the SATEC Australia datasheet [TBV1.0, 16 September 2026](https://satec-global.com.au/documentation/HCS-1000A-Hall-Effect-Sensors-Datasheet-TBV-1-0.pdf) (PDF, 4 pages, 2917 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The HCS-1000A is a solid-core Hall effect sensor for measuring DC currents up to 1,000A nominal, designed for use with the range of SATEC devices that offer DC metering. The primary conductor or busbar passes directly through the sensor’s solid core. The unit then outputs a proportional current signal to the connected meter.

With ±0.2% accuracy across its 500A–2,000A rated range, a compact enclosure and 6kV galvanic isolation, the HCS-1000A suits demanding DC applications from photovoltaic arrays and battery storage through to variable speed drives and UPS systems.

## Main features

- High accuracy of ±0.2% for rated current
- Compact solid-core enclosure
- Wide current measuring range, 0 to ±2,000A

## Feature capabilities

### Applications

- Photovoltaic applications
- General purpose inverters
- AC/DC variable speed drives
- Battery / energy storage
- Uninterruptible Power Supply (UPS)

### Important

- Temperature of the primary conductor / busbar running through the sensor must not exceed 100°C.

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

General characteristics
| Nominal input current |1,000A |
| Measuring range |0 to ±2,000A |
| Nominal output signal |±20mA |
| Supply voltage |±15V DC to ±24V DC |
| Current consumption |≤30mA + Input current / 5,000 |
| Galvanic isolation |6kV, 50Hz, 1 min |

Accuracy
| Accuracy |±0.2% for rated current 500A–2,000A |
| Linearity |≤0.1% for rated current 500A–2,000A |

Environmental
| Operating temperature |-25°C to +85°C |
| Storage temperature |-40°C to +100°C |

Connections
| + |+15 to +24V DC |
| − |-15 to -24V DC |
| M |Current output |
| G |Ground |

Construction
| Unit weight |1,150g |

## Ordering information

HCS-1000A

The HCS-1000A is supplied as a single fixed-specification unit with no configurable order-code options.

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 2917 KB)](https://satec-global.com.au/documentation/HCS-1000A-Hall-Effect-Sensors-Datasheet-TBV-1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-051ccb77a83a/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).