# EM720 power quality analyser and revenue meter datasheet: specifications and ordering codes

> EM720 datasheet as a web page: Power quality analyser and Class 0.2S revenue meter. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/em720/

---

EM720 · DATASHEET

# EM720 power quality analyser and revenue meter datasheet

Power quality analyser and Class 0.2S revenue meter.

Transcribed from the SATEC Australia datasheet [TBV1.0, 24 September 2026](https://satec-global.com.au/documentation/EM720-Power-Quality-Analyser-Revenue-Meter-Datasheet-TBV1-0.pdf) (PDF, 7 pages, 517 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The EM720 eXpertmeter™ is SATEC's high accuracy revenue meter and power quality analyser in one three-phase instrument. It combines a Class 0.2S energy meter with a fault recorder, data recorder and programmable controller. It is built for utility, substation, industrial and commercial billing sites where reliable power quality monitoring and high device availability are essential.

The meter records fault currents up to 10 times nominal current (50A), performs harmonic analysis to the 50th order and captures disturbances in detail. The EM720T model adds a fast transient recorder for voltage transients up to 2kV. A backlit graphical LCD, a front infrared port and plug-in RS-232/RS-485, USB and Ethernet modules support local reading and remote automatic meter reading. Three hot-swap expansion slots let you add I/O, communications and backup power in the field.

## Main features

- AS/IEC 62053-22 Class 0.2S active energy metering
- Time-of-use billing with 8 tariffs, 4 seasons and 4 day types
- EN 50160 power quality recorder with compliance reports
- IEC 61000-4-30 Class A power quality methods
- Harmonics and interharmonics to the 50th order
- IEC 61000-4-15 flicker measurement
- Digital fault recorder for currents up to 10 × In (50A)
- Transient recording up to 2kV peak (EM720T)
- 8MB standard or 16MB expanded log memory
- Three hot-swap expansion slots for I/O and communications
- Optional IEC 61850 over Ethernet
- Optional Li-ion battery for up to 6 hours full operation

## Feature capabilities

### Models and versions

- EM720: Class 0.2S revenue energy meter with EN 50160 power quality analyser, fault and event recording, metering and control
- EM720T: All EM720 functionality plus a high-voltage fast transient recorder for impulsive and oscillatory overvoltages
- 120V or 480V versions: 120V version for connection via PTs, or 480V version for direct connection to the network

### Billing/TOU energy meter

- AS/IEC 62053-22 Accuracy Class 0.2S active and reactive energy polyphase static meter
- Time-of-use with 10 billing energy and maximum demand registers, 8 tariff rates, 4 seasons × 4 day types and 8 tariff changes per day
- One-time programmable tariff calendar schedule; one-time programmable or calendar scheduled daylight saving switch dates
- Configurable end of billing period: automatic monthly, local from the front display (password protected) or via communications
- Automatic recording of billing energy, maximum demand and cumulative maximum demand registers for the last 24 billing periods
- Automatic 120-day daily energy and maximum demand profile
- Automatic 120-day/15-minute or 240-day/30-minute energy load profile
- Easy access to the three previous billing periods from the front display
- Transformer and line loss compensation
- PT/CT corrections at up to 8 points

### Multi-functional power meter

- Enhanced three-phase power meter: true RMS volts and amps, powers, power factors, unbalance, neutral current and frequency
- Demand meter: amps, volts, harmonic demands, block and sliding power demands
- Harmonic analyser: volts and amps to the 50th harmonic; fundamental volts, amps, power and power factor; phasors and symmetrical components

### Waveform recorders

- Seven channel simultaneous recording of three voltage and four current channels
- Selectable sampling rate of 32, 64, 128 or 256 samples per cycle
- 20 pre-fault cycles and up to 3 minutes of continuous recording at 32 samples per cycle
- Optional 4-channel transient voltage recording at 1024 samples per cycle (EM720T)
- Synchronised waveforms from multiple devices in a single plot
- Waveform export in COMTRADE and PQDIF file formats

### Power quality

- EN 50160 power quality recorder with onboard analyser, programmable limits, event log, compliance statistics and harmonics survey statistics
- Power frequency, voltage variations, rapid voltage changes, IEC 61000-4-15 flicker, voltage dips, interruptions, temporary and transient overvoltages and voltage unbalance
- IEC 61000-4-7 harmonic and interharmonic voltage and mains signalling voltage
- High-voltage fast transient recorder (EM720T) for impulsive and low frequency oscillatory overvoltages with peaks up to 2kV and durations from 20 microseconds
- Ready-to-use compliance statistics reports

### Fault recorder

- Fast digital fault recorder with up to 8 external digital triggers from protection relays
- Onboard voltage and current fault detector: zero-sequence currents and volts, current and voltage unbalance
- Programmable fault thresholds and hysteresis
- Records fault currents up to 10 × nominal current (50A)
- Ready-to-use fault reports: fault current magnitudes and duration, coincident voltage magnitude, fault waveforms and fast RMS trace

### Data recorders

- Sixteen fast data recorders
- Programmable periodic data logs, or logs on any internal or external trigger, including the fault recorder, PQ recorder or control setpoints
- Data trend export in PQDIF file format
- Fast fault and PQ data profiling (trending) triggered from the fault and PQ recorders: ½ cycle to 10-minute RMS envelopes with up to 20 pre-fault and post-fault cycles

### Event recorder

- Logs internal diagnostic events, setpoint operations and I/O operations

### Programmable logical controller

- Embedded programmable controller with 16 control setpoints
- OR/AND logic, extensive triggers, programmable thresholds and delays, relay control and event-driven data recording
- 8 digital counters for pulses from external sources and internal events
- 4 programmable timers from 1 cycle to 24 hours for periodic recording and time-based triggering

### Time and clock

- High accuracy real-time clock with lithium backup battery
- 1ms digital input synchronisation
- Satellite-synchronised clock option (IRIG-B time-code input)
- SNTP clock synchronisation option
- One-time programmable or calendar scheduled daylight saving time (DST) switch dates with configurable DST start and end times

### Display

- High contrast graphical 128 × 32 pixel LCD with backlight
- Multi-page data display with auto-scroll: time, billing, instrumentation and service data
- Menu-driven setups

### Extended security

- 3-level password security protects meter setups and accumulated data from unauthorised changes

### Communications

- Front infrared port to IEC 62056-21 (IEC 62056-21, Modbus RTU/ASCII and DNP3 protocols)
- Plug-in RS-232/RS-485 serial port (Modbus RTU/ASCII and DNP3 protocols)
- Plug-in full speed USB 1.1 port (Modbus RTU protocol)
- Plug-in Ethernet port (Modbus/TCP and DNP3/TCP protocols, optional IEC 61850) with up to 5 simultaneous connections

### Expansion I/O and communication slots

- 3 hot-swap expansion slots for plug-in I/O and communication modules

### Digital I/O

- Four embedded digital inputs with 1ms scan time
- Replaceable 2DI/2DO expansion I/O modules with ½ cycle scan and update time

### Memory

- 8MB or 16MB flash memory for long-term billing, event, waveform and data recording

### Backup power supplies

- Heavy-duty lithium backup battery for the RTC, setup and data logging information
- Optional high-capacity rechargeable Li-ion battery for up to 6 hours full operation
- Optional auxiliary 24V DC backup power supply module

### Upgradeable firmware

- New features can be added by updating the firmware through any communication port

### Software support

- Power Analysis Software (PAS): free software for meter configuration, control, data acquisition and power quality reporting
- Expertpower: SATEC’s internet-based energy management platform for data collection, billing, dashboards and power quality analysis
- eXpertConnect™ App: mobile connection to the meter for configuration, readings and diagnostics
- Supplemental communication software or your own data acquisition software via Modbus and DNP3

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

AC voltage inputs
| Inputs |V1, V2, V3, VN and VG, 50/60Hz |
| Versions |120V: for connection via PTs; 480V: for direct connection |
| Voltage rating, 120V version |3 × 57.73/100V; 3 × 63/110V; 3 × 69/120V; 3 × 57.73V, 3 × 63V, 3 × 69V |
| Voltage rating, 480V version |3 × 120/207V; 3 × 220/380V; 3 × 230/400V; 3 × 277/480V; 3 × 220V, 3 × 230V, 3 × 277V |
| Voltage range and crest factor |120V: 0 to 144V, ≥2 (peak up to 300V); 480V: 0 to 320V RMS, ≥2 (peak up to 700V) |
| Temporary overvoltage, live conductors to earth |240V RMS (120V version); 1000V RMS (480V version) |
| Transient overvoltage, live conductors to earth (15µs to milliseconds) |2kV peak |
| Starting voltage |0.5% Un |
| Burden per phase |<0.2VA (120V version); <0.5VA (480V version) |
| Overload withstand, 1 minute phase to ground (AS/IEC 62053-22, protective class II) |4000V RMS |
| Rated impulse voltage (AS/IEC 62052-11, protective class II) |6000V |
| Terminal wire size |2.5 to 6mm² |

AC current inputs
| Inputs |4 galvanically isolated inputs |
| Reference current |In = 5A or In = 1A |
| Continuous overload (Imax) |2 × In |
| Maximum measurable short circuit current |10 × In |
| Burden per phase |<0.2VA (In = 5A); <0.05VA (In = 1A) |
| Starting current |0.1% In (I1, I2, I3); 0.5% In (I4) |
| Overcurrent withstand, 1 second non-recurring |50 × In |
| Galvanic isolation rating |4000V RMS |
| Terminal wire size |2.5 to 6mm² |

Real-time clock
| Accuracy |5ppm at 25°C (2.7 minutes per year) |
| RTC backup data retention |5 years |

Environmental conditions
| Operating temperature |−40°C to +70°C |
| Full accuracy operating temperature |−25°C to +60°C |
| Storage temperature |−45°C to +85°C |
| Humidity |0 to 95% RH, non-condensing |

Construction
| Enclosure |Reinforced, corrosion resistant plastic with sealing cover |
| Flammability |UL94V0 |
| Size (H × W × D) |303 × 177 × 144mm |
| Weight (including battery) |3.95kg |
| Mounting |DIN 43857 |

Power supply: 3P power supply (MPS), from measured AC voltage inputs
| High range (480V version) |Nominal 207–480V AC 50/60Hz; operating range 96–575V AC |
| Low range (120V version) |Nominal 100–120V AC 50/60Hz; operating range 45–250V AC |
| Burden (IEC 62053-61 multi-function meter requirements) |3W and <15VA per phase |

Power supply: battery backup power supply (BPS), optional
| Built-in rechargeable Li-ion battery, redundant to MPS |Up to 6 hours backup |

Power supply: auxiliary power supply (APS), optional
| 24V DC module, redundant to MPS |24V DC ±15%; 6W maximum |
| AC/DC module |88–265V AC 50/60Hz or 90–290V DC |
| Dielectric insulation withstand |4kV AC for 1 minute |
| Terminal wire size |2 × 4mm² |

Console display unit
| Display |Backlit graphic LCD, multiple screens, 128 × 32 dot resolution |
| Viewing area |99.0 × 24.0mm |
| Display operating temperature |−20°C to +70°C |
| Backlight |Timeout operation |
| LEDs |2 (active and reactive energy pulse) |
| Buttons |2 sealed buttons (SCROLL and SELECT/ENTER) for monitoring and configuration |

Digital inputs: basic
| Inputs |4 dry contact, optically isolated |
| Wetting |24V DC internal supply (5mA wetting current per contact) |
| Open / closed contact impedance |>1MΩ / <100Ω |
| Sampling rate |1ms |
| Dielectric insulation withstand |4kV AC for 1 minute |
| Terminal wire size |8 × 2.5mm² |

2DI/2DO module: digital inputs (optional)
| Inputs |2 dry contact, optically isolated |
| Wetting |24V DC internal supply (5mA wetting current per contact) |
| Open / closed contact impedance |>1MΩ / <100Ω |
| Sampling rate |½ cycle (50/60Hz) |
| Dielectric insulation withstand |4kV AC for 1 minute |
| Terminal wire size |4 × 2.5mm² |

2DI/2DO module: solid state outputs (optional)
| Outputs |2 SSR, Form C |
| Maximum switching voltage |250V AC/DC |
| Make and carry capacity |0.12A maximum |
| Maximum operate / release time |1ms / 1ms |
| Dielectric insulation withstand |4kV AC for 1 minute |
| Terminal wire size |6 × 2.5mm² |

2DI/2DO module: relay outputs (optional)
| Outputs |2 electromechanical relays, Form C |
| Maximum switching voltage |250V AC / 110V DC |
| Make and carry capacity |10A maximum |
| Maximum operate / release time |7ms / 5ms |
| Dielectric insulation withstand |4kV AC for 1 minute |
| Terminal wire size |6 × 2.5mm² |

Log memory
| Type |Non-volatile, 20 years data retention |
| Standard / expanded |8MB / 16MB |

Communication ports: COM1, infrared (front panel)
| Port type |Optical communication port, IEC 62056-21 |
| Maximum baud rate |19.2kb/s |
| Protocols |Modbus RTU/ASCII and DNP3.0 |

Communication ports: COM3, RS-232/RS-485 (plug-in, isolated)
| Port type |Versatile RS-232/RS-485, field installable |
| Maximum baud rate |115.2kb/s |
| Protocols |Modbus RTU/ASCII and DNP3.0 |
| Isolation |4kV AC for 1 minute |
| Terminal wire size |5 × 2.5mm² |

Communication ports: IRIG-B module
| Isolation |4kV AC for 1 minute |
| Time code signal |Unmodulated (pulse-width coded), unbalanced 5V |
| Connector |BNC |
| Recommended cable |51Ω low loss RG58A/U (Belden 8219 or equivalent) |
| Recommended GPS time code generator |Masterclock GPS-200A |

Communication ports: Ethernet 10/100Base-T (optional plug-in module)
| Port type |Wired LAN, IEEE 802.3, field installable |
| Baud rate |10/100Mb/s, auto-negotiation |
| Protocols |Modbus/TCP or DNP3.0/TCP, up to 5 non-intrusive simultaneous connections; Telnet service port |
| Isolation |3kV AC for 1 minute |
| Connector |Standard RJ-45 |

Communication ports: USB (optional plug-in module)
| Port type |Full speed device, field installable |
| Baud rate |12Mb/s |
| Protocols |Modbus RTU/ASCII and DNP3.0 |
| Isolation |1.5kV AC for 1 minute |
| Connector |Mini-USB type B |

Real-time clock battery backup
| Standard |According to IEC 61038 |
| Field replaceable lithium battery |More than 3 consecutive years backup; more than 10 years service life |

## Standards compliance

### EMC

- IEC 61000-2

### Immunity

- ESD: IEC 61000-4-2 / AS/IEC 62052-11, 15kV air/contact
- Electromagnetic RF fields: IEC 61000-4-3 / AS/IEC 62052-11, 30V/m at 80MHz to 1000MHz
- Fast transient burst: IEC 61000-4-4 / AS/IEC 62052-11, 4kV on current and voltage circuits and 2kV on auxiliary circuits
- Surge: IEC 61000-4-5 / AS/IEC 62052-11, 4kV on current and voltage circuits and 1kV on auxiliary circuits
- Conducted radio frequency: IEC 61000-4-6 / AS/IEC 62052-11, 10V at 0.15MHz to 80MHz
- Power frequency magnetic fields: IEC 61000-4-8
- Damped oscillatory waves: IEC 61000-4-12 / AS/IEC 62052-11, common mode 2.5kV and differential mode 1kV at 100kHz and 1MHz

### Emission

- Radiated and conducted: CISPR 22 Class A

### Safety

- IEC 61010

### Insulation

- Impulse, protective class II: AS/IEC 62052-11, 6kV/500Ω at 1.2/50µs
- Dielectric withstand, protective class II: AS/IEC 62053-22, 4kV RMS for 1 minute

### Measurement and accuracy

- AS/IEC 62052-11
- AS/IEC 62053-22: active energy measurement, Class 0.2S
- IEC 62053-23: reactive energy measurement, Class 0.5S

### Power quality

- PQ measurement methods: IEC 61000-4-30 Class A
- Harmonics and interharmonics: IEC 61000-4-7 Class I
- Flicker: IEC 61000-4-15 Class I
- Reporting: EN 50160

## Ordering information

MODEL – VOLTAGE – FREQ. – CURRENT – BATTERY – MEMORY – MODULES

Model
| Basic model |EM720 |
| Transient Power Master |EM720T |

Voltage inputs
| 480V AC (L-L) |480V |
| 120V AC (L-L) |120V |

Calibration at frequency
| 50Hz |50HZ |
| 60Hz |60HZ |

Current inputs
| 5 Ampere |5 |
| 1 Ampere |1 |

Rechargeable battery
| Without battery |– |
| With battery |B |

Memory
| Standard memory: 8MB |– |
| Expanded memory: 16MB |XM |

Optional modules (see notes)
| [1] Ethernet, USB and 2nd RS-232/485 |COM-ETH |
| [1] Ethernet with IEC 61850 support, USB and 2nd RS-232/485 |COM-IEC |
| [1] Exchanging the IRIG-B with Ethernet and USB |COM-UPG |
| [2] 2DI/2 relay outputs (Form C) 250V AC/5A |DIO-R |
| [2] 2DI/2 solid state relay outputs (Form A) 250V AC/0.1A |DIO-S |
| [3] Auxiliary PS: 88–265V AC and 90–290V DC |AUX-ACDC |
| [3] Auxiliary PS: 24V DC |AUX-24 |

Notes: Maximum 2 modules per device, with the following limitations: [1] Maximum 1 module with Ethernet per device; [2] Maximum 2 I/O modules per device; [3] Maximum 1 auxiliary power supply module per device.

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 517 KB)](https://satec-global.com.au/documentation/EM720-Power-Quality-Analyser-Revenue-Meter-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-30a74cfe85ba/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/em720/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [The two batteries in the EM720](https://satec-global.com.au/support/articles/em720-batteries/)
- [What to identify on an EM720 before commissioning](https://satec-global.com.au/support/articles/em720-identify-before-commissioning/)
- [Which EM720 communication document applies to your port](https://satec-global.com.au/support/articles/em720-communication-documents/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).