# EM133-XM energy meter datasheet: specifications and ordering codes

> EM133-XM datasheet as a web page: Smart multifunction energy meter: 5A CT and direct input. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.1.

Source page: https://satec-global.com.au/support/datasheets/em133-xm/

---

EM133-XM · DATASHEET

# EM133-XM energy meter datasheet

Smart multifunction energy meter: 5A CT and direct input.

Transcribed from the SATEC Australia datasheet [TBV1.1, 6 October 2026](https://satec-global.com.au/documentation/EM133-XM-NMI-Approved-Energy-Meter-Datasheet-TBV1-1.pdf) (PDF, 9 pages, 715 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The EM133-XM is SATEC's advanced expertmeter™ smart multifunction, DIN rail mounted, tariff (TOU) energy meter for commercial, industrial, solar and residential applications. It is designed for revenue billing, energy management and NABERS/Green Star reporting. The XM is the enhancement of SATEC's discontinued AR model.

The EM133-XM provides 2 built-in digital pulse inputs for direct connection to pulse-output water, hot water, gas and steam meters, with expansion modules available to add 4, 8 or 12 further pulse inputs. It measures three-phase and per-phase active, reactive and apparent energy across four quadrants, with time-of-use registers spanning 8 tariffs, 4 seasons and 4 day types, alongside an embedded programmable logic controller, harmonic analyser and real-time waveform capture.

## Current input options

- 

### 5A / 10A (CT operated)

Standard current input via conventional 5A current transformers or extended range CTs

- 

### Direct connect up to 100A

Direct current measurement up to 100A, no external CTs required

- 

### HACS remote sensor

100–3000A remote current sensor input (CS1, CS1L, CS1S only — see the HACS datasheet)

## Main features

- Four (4) quadrant import/export, 3 phase and 3 single-phase configuration
- True RMS volts, amps, power, power factor, voltage and current unbalance, frequency
- Neutral current calculation
- Ampere/Volt demand meter
- 50Hz measurement (400Hz optional)
- Extended range CT input (5A/10A)
- Energy test mode and transformer correction
- 128 samples per cycle, *8MB of memory
- 3 year warranty

## Feature capabilities

### Billing / TOU energy meter

- Energy accuracy Class 0.5S
- Four-quadrant active and reactive energy
- Import/export per phase as single-phase configuration
- Three-phase total and per-phase energy measurement — active, reactive and apparent energy counters
- Time-of-Use: 8 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 types of days, 8 tariff changes per day
- One-time easy programmable tariff calendar schedule
- Automatic daily energy and maximum demand profile log for total and tariff registers
- Cost calculation (upon application)
- CO2 (upon application)

### Water and gas measurement

- Direct connection to pulse output water and gas meters
- Setting of multiplication factors and units
- Display of consumption in real values
- Up to 14 digital pulse inputs

### Harmonic analyser

- Voltage and current THD, TDD and K-Factor, up to 40th order harmonic
- Voltage and current harmonic spectrum and angles

### Real-time waveform capture (via PC with PAS free licensed software)

- Real-time "scope mode" waveform monitoring capability
- Simultaneous 6-channel 8-cycle waveform capture at a rate of 64 samples per cycle
- Vector analysis

### Programmable logical controller

- Embedded programmable controller
- 16 control set points; programmable thresholds and delays
- Relay output control
- 1-cycle response time

### Event and interval data recording

- Non-volatile memory with interval data logging for load surveys and energy usage
- *Interval data logging @ 30 minutes = 1365 days
- *Interval data logging @ 15 minutes = 682 days
- *Interval data logging @ 5 minutes = 227 days
- *Interval/data logging time period user-definable 1–60 minutes
- *Interval/data logging for up to 16 parameters/channels, user-definable
- Event recorder for logging internal diagnostic events and setup changes
- Two data recorders; programmable data logs on a periodic basis; automatic daily energy and maximum demand profile log

### Display

- Easy to read 2 × 16 characters LCD display, adjustable update time
- Signal strength display reading for modem and WiFi module
- Auto-scroll option with adjustable page exposition time; auto-return to a default page

### Real-time clock

- With backup battery
- Low battery indication

### Meter security

- 3 levels password security protecting meter setups and accumulated data from unauthorised changes

### Upgradeable firmware

- Easy upgrading of device firmware through serial, Ethernet, WiFi or modem communications

### Inputs / outputs

- Built-in 2 digital inputs and 1 form-A solid state digital output
- Optional module 4 digital inputs and 2 digital outputs (solid state or electro-mechanical)
- Optional module 8 digital inputs
- Optional module 12 digital inputs and 4 digital outputs (plus Ethernet or RS-485)
- Optional module 4 analogue outputs

### Communications

- Standard 2-wire RS-485 communication
- Built-in IR communication port (IEC)

### Dual communications (add-on module)

- Optional multipurpose RS-232/422/485 port
- Optional 10/100Base T port
- Optional external 4G modem (on application)

### Communication protocols

- Modbus RTU
- Modbus TCP/IP
- Modbus assignable registers
- MV-90 xi Translation Interface Module (TIM) for EM133-XM

### Software support and firmware

- Power Analysis Software (PAS) — free licensed software for configuration, data acquisition and forensic analysis
- Expertpower — SATEC's internet-based energy management software
- eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics

### eXpertConnect™ cloud-based software as a service (SaaS)

- KWH (energy) billing, water billing, gas billing
- Energy management and power monitoring
- Power quality forensic analysis
- Data pushed to cloud service via Ethernet, WiFi or modem communications

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Voltage inputs
| Voltage connections |3 phases, 1 neutral |
| Voltage ratings |Direct voltage connection: 220 to 400V (L-N); 380 to 690V (L-L); range 0–800VAC. Via PT (power transformer): 57.7 to 120V (L-N); 100 to 207V (L-L); range 0–250VAC |
| Starting voltage |0.2% UN |
| Input impedance |≥ 1MΩ |
| Overload withstand |4000 VAC (L-G) for 1 min. |
| Impulse voltage |12kV |
| Terminal blocks |4 sealed, pitch 7–10mm, 2.5 to 4 mm² |

Current inputs
| Current connections |4 galvanic isolated inputs |
| Current ratings |Choice of 3 options: ../5A CT connection; direct up to 100A; HACS input (refer HACS datasheet for inputs up to 3000A) |
| Starting current |0.2% IN |
| Burden per phase |<0.2 VA (../5A) |
| Overload (continuous) |2×IN (1.2×IN for 100A model) |
| Over current |50×IN (for 1 second) |
| Galvanic isolation |4000 VAC (L-G) for 1 min. |
| Terminal blocks |6 sealed, pitch 7–10mm, 4 to 16 mm² |

Auxiliary power supply
| Rated input |Self powered |
| Insulation dielectric withstand |4000 VAC for 1 min. |
| Terminal blocks |2 sealed, pitch 7–10mm, 2.5 to 4 mm² |

Built-in communication
| Communication type |RS-485 |
| Max. baud rate |115.2 kb/s |
| Isolation |4000 VAC (L-G) for 1 min. |
| Max. cable length |1000 m |
| Terminal blocks |3 sealed, pitch 7–10mm, 2.5 to 4 mm² |

Infra-red communication
| Baud rate |To be confirmed |
| Protocols |Modbus RTU |

Add-on modules
| Max. number of modules |1 |
| Available modules |RS485/RS-232; Ethernet; digital I/O; analogue output |

Front panel
| Display type |2×16 characters transflective LCD with backlight |
| Character size |3.2×1.85 mm |
| Viewing area |46×11 mm |
| LEDs |Total 6 LEDs: 1 pulse calibration output; 3 voltage indication; 2 RX/TX activity |
| Keypad |2 buttons |
| Nameplate |According to IEC 60688 and IEC 62052-11 |

Mechanical
| Enclosure |DIN rail mount, complies with EN50022 |
| Dimensions [W×H×D] |125 × 90 × 75mm |
| Enclosure material |Reinforced polycarbonate |

Temperature
| Operational |−25°C to 60°C |
| Storage |−30°C to 85°C |

## Standards compliance

### EMC immunity (per IEC 60688 and IEC 62052-11)

- IEC 61000-4-2: electrostatic discharge — to be confirmed
- IEC 61000-4-3: electromagnetic RF fields, 10V/m – 80MHz–1000MHz
- IEC 61000-4-4: fast transients burst, 4KV on current and voltage circuits and 2KV for auxiliary circuits
- IEC 61000-4-5: surge 4KV on current and voltage circuits and 1KV for auxiliary circuits
- IEC 61000-4-6: conducted radio-frequency, 10V @ 0.15MHz–80MHz
- IEC 61000-4-8: power frequency magnetic field

### Emission (radiated / conducted)

- EN55022: 2010 Class A (CISPR 22)
- FCC p.15 Class A mandatory

### Safety

- UL/IEC 61010-1

### Insulation

- Impulse tested to SP-Method 1618, impulse voltage 12kV @ 1.2/50 µs
- AS/IEC 62053-22: AC voltage tests related to ground, 4kV AC @ 1 min, for power and signal ports (above 40V)
- 2.5KVAC r.m.s. @ 1 min, for other ports (below 40V)

### Atmospheric environment

- Operational ambient temperature range: −25°C to +60°C
- Long-term damp heat withstand according to IEC 68-2-3, <95% (non-condensing), +40°C
- Transport and storage temperature range: −30°C to +85°C
- IEC 60068-2-6: vibration
- Frequency range: 10Hz to 150Hz
- Transition frequency: 60Hz
- Constant movement amplitude 0.075mm, f<60Hz
- Constant acceleration 9.8 m/s² (1g), f > 60Hz
- Additional transport vibration and shocks — longitudinal acceleration 2.0g, vertical acceleration 1.2g, transversal acceleration 1.2g
- Enclosure protection: IP50

### Accuracy according to

- AS/IEC 62053-22, class 0.5S — active energy
- IEC 62053-21, class 0.5 — reactive energy
- IEC 60688, class 0.5S — active energy
- IEC 60688, class 1 — reactive energy

### AER / AEMO / AEMC

- NEM12/13 data, available via Expertpower or eXpertConnect™

## Approvals in Australia

- NMI pattern approval 14/2/72 Rev 6: EM133 Class 0.5, including the EM133-XM-100A and EM133-XM-5A variants.
- Verification per NITP14 test procedures (ordering option CC).

## Ordering information

EM133-XM – CURR. – 50HZ – SE – CC

Current inputs (CURR.)
| 5 Ampere (CT operated) |5 |
| Direct current measurement up to 100A |100 |
| HACS (refer HACS datasheet) — CS1, CS1L, CS1S only |HACS |

Calibration at frequency
| 50Hz |50HZ |
| 400Hz |400HZ |

Power supply
| Self energised / powered |SE |

RS485/Modbus communications
| RS485/Modbus (standard) |— |

Verification
| NITP 14 verification |CC |

Expansion module (max. 1 per instrument) is ordered separately — see Expansion modules below.

### Expansion modules

Maximum 1 per instrument, ordered separately.

Analogue outputs
| 4 analogue output: ±1mA |AO1 |
| 4 analogue output: 0–20mA |AO2 |
| 4 analogue output: 0–1mA |AO3 |
| 4 analogue output: 4–20mA |AO4 |
| 4 analogue output: 0–3mA |AO5 |
| 4 analogue output: ±3mA |AO6 |
| 4 analogue output: 0–5mA |AO7 |
| 4 analogue output: ±5mA |AO8 |

Communication
| Ethernet (TCP/IP) |ETHD |
| RS232/422/485 |RS232D |
| Modem – 4G (optional external on application)* |T4T-x |

*Modem antennas: x = T – top, or F – front

Digital I/O and relay outputs
| 4 digital inputs (dry contact) / 2 relay output 250V/5A AC |DIOR |
| 4 digital inputs (dry contact) / 2 SSR output 250V/0.1A AC |DIOS |
| 8 digital inputs (dry contact) / 2 SSR output 250V/0.1A AC |8DI |
| 12 digital inputs (dry contact) / 4 relay outputs 250V/5A AC |12DIOR-DRC |
| 12 digital inputs (48VDC) / 4 relay outputs 250V/5A AC |12DIOR-48V |
| 12 digital inputs (125VDC) / 4 relay outputs 250V/5A AC |12DIOR-125V |
| 12 digital inputs (250VDC) / 4 relay outputs 250V/5A AC |12DIOR-250V |
| As above, with RS485 — dry contact / 48V / 125V / 250V |…-485 |
| As above, with Ethernet — dry contact / 48V / 125V / 250V |…-ETH |

## Downloads and related

- [Download the datasheet (PDF, TBV1.1, 715 KB)](https://satec-global.com.au/documentation/EM133-XM-NMI-Approved-Energy-Meter-Datasheet-TBV1-1.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-b28a578c35cc/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/em133-xm/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [How do I identify an Australian EM133-XM?](https://satec-global.com.au/support/articles/em133-xm-identify/)
- [How do I set the CT ratio on an EM133-XM?](https://satec-global.com.au/support/articles/em133-xm-ct-ratio/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).