# EM132 multi-function meter datasheet: specifications and ordering codes

> EM132 datasheet as a web page: Multi-function power meter and smart transducer. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/em132/

---

EM132 · DATASHEET

# EM132 multi-function meter datasheet

Multi-function power meter and smart transducer.

Transcribed from the SATEC Australia datasheet [TBV1.0, 21 September 2026](https://satec-global.com.au/documentation/EM132-Multi-Function-Meter-Datasheet-TBV1-0.pdf) (PDF, 9 pages, 1071 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

SATEC EM132 is a multi-function power meter, ideal for a wide range of applications such as energy management metering, industrial power monitoring and interfacing SCADA in utility substations. Based on SATEC’s PM13X family functionality, the EM132 is designed as a DIN-rail mount device equipped with a built-in communication port and an anti-tamper enclosure.

As a smart transducer, the EM132 provides four analogue outputs for selectable power parameters, together with load-shedding and alerting of irregularities, and supports a modular I/O system with up to 16 digital and analogue points. Broad-range frequency measurement from 25Hz to 400Hz and a choice of built-in and optional communication ports make it equally suited to retrofit and new-build metering projects.

EM132: Standard model with a single built-in RS-485 communication port.

EM132-TP: Includes a second built-in RS-485 port (AC/DC power supply model only).

## Main features

- Energy meter: Class 0.5S/0.5 accuracy per AS/IEC 62053-22 / ANSI
- Smart transducer: 4 analogue outputs for selectable power parameters, plus load-shedding and alerting of irregularities
- Digital & analogue I/O: modular I/O with up to 16 points
- Broad-range frequency measurement: 25–400 Hz
- Anti-tamper enclosure with DIN-rail mounting

## Feature capabilities

### Applications

- Energy management metering
- Industrial power monitoring
- SCADA interfacing in utility substations
- Retrofit and new-build sub-metering, including with SATEC HACS current sensors

### Multi-functional 3-phase smart meter

- True RMS volts, amps, power, power factor, neutral current, angles and unbalance for voltage and current, frequency, symmetrical components and many more
- Ampere/volt demand meter
- 25, 50, 60 and 400Hz measurements
- 128 samples per cycle

### Energy meter

- Accuracy Class 0.5S per AS/IEC 62053-22 / ANSI
- Four-quadrant active and reactive energy polyphase static meter
- Three-phase total and per-phase energy measurements: active, reactive and apparent energy counters
- Automatic logging of daily energy and maximum demand profiles

### Real-time waveform capture (via PC)

- Real-time “scope mode” waveform monitoring via PAS software.

### Programmable logical controller

- Embedded programmable controller
- 16 control set points; programmable thresholds and delays
- Relay output control
- 1-cycle response time

### Event and data recording

- Non-volatile memory for timestamped event and data recording: over 90 days of half-hourly writing of 4 parameters, recording more than 200 events over the entire period
- Event recorder for logging internal diagnostic events and setup changes
- Two data recorders; programmable data logs on a periodic basis; automatic daily energy log and maximum demand profile

### Voltage inputs

- Direct measurement 0–690V AC.

### Current input options

- 1A or 5A inputs from CT secondary
- 40mA input designed for SATEC HACS CTs (100–3,000A options)
- 63A or 100A direct connection
- RS: unique input for 5A-rated split-core HACS CTs, ideal for retrofit installation

### Digital and analogue I/O

- Built-in: 2 digital inputs and 1 form-A SSR output
- 4DIO module: 4 digital inputs, 2 relay outputs (SSR or EM relay)
- 12DIO module: 12 digital inputs, 4 relay outputs (with optional Ethernet or RS-485 port)
- 4AO, 8DI and 2AI modules also available

### Communication — ports and protocols

- On-board: standard 2-wire RS-485; optional second built-in RS-485 port
- Optional interfaces: RS-232/422/485, 10/100BaseT Ethernet, Profibus, 4G cellular modem
- Protocols: Modbus RTU, SATEC ASCII, DNP 3.0, IEC 60870-5-101/104 (optional)

### Display

- 2×16 character LCD display; adjustable update time
- Auto-scroll option; auto-return to a default page

### Meter security

- 3-level password access to meter setups and data.

### Software support and firmware

- Includes comprehensive Power Analysis Software (PAS) for configuration and data acquisition
- Compatible with SATEC’s Expertpower web-based energy management platform (subscription)
- Connect via the eXpertConnect™ App for on-the-go readings and diagnostics
- Any third-party software supporting the open protocol
- Easy firmware upgrading via serial or Ethernet ports

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Voltage inputs
| Installation category |Category III |
| Over-voltage withstand |1,000V AC continuous, 2,000V AC for 1 second |
| Input impedance |1 MΩ |
| Wire size |Up to 12 AWG (up to 2.5mm²) |

Model with aux. power supply
| Nominal voltage |400/690V AC (L-N/L-L) |
| Measurement range |15–480/828V AC (L-N/L-L) |
| Frequency range |25–400 Hz |
| Burden for 400V |< 0.4 VA |
| Burden for 120V |< 0.04 VA |

Model self-energised from voltage inputs*
| Nominal voltage (HACS, 1A/5A/RS5 models) |120/207V AC to 230/400V AC (L-N/L-L); 120/207V AC to 277/480V AC (L-N/L-L) |
| Frequency range |50/60 Hz |
| Burden for 277V |< 1.5 VA |
| Burden for 120V |< 2 VA |

* Not available with the EM132-TP model.

Current inputs
| Current connections |3 galvanically isolated inputs |
| Current ratings |../5A CT; ../1A CT; direct up to 63A**; remote CT (40mA) |
| Starting current |0.2% In |
| Burden per phase |<0.2 VA (../5A); <0.05 VA (../1A) |
| Overload (continuous) |2×In (1.2×In for 100A model) |
| Over current |50×In for 1 second |
| Galvanic isolation |4,000V AC (L-G) for 1 min. |
| Terminal blocks |6 sealed, pitch 7–10mm, 4 to 16 mm² |

** Connecting up to 100A is possible under certain conditions (up to 55°C ambient temperature).

Auxiliary power supply
| Rated input |57.7–277V AC; 48–290V DC |
| Tolerance |@V AC = ±15%; @V DC = ±10% |
| Insulation dielectric withstand |4,000V AC for 1 min. |
| Burden |5VA |
| Terminal blocks |2 sealed, pitch 7–10mm, 2.5 to 4mm² |

Optional power supply
| Rated input |12–24V DC |
| Tolerance |±20% |

Optional modular I/O – electromechanical relay
| Dry contact |1 contact (SPST Form A) |
| Rating |5A/250V AC; 5A/30V DC |
| Galvanic isolation |Contacts–coil: 3,000V AC 1 min; open contacts: 750V AC |
| Operate time |10 ms max |
| Release time |5 ms max |
| Update time |1 cycle |
| Wire size |14 AWG (up to 1.5 mm²) |

Optional modular I/O – solid state relay
| Dry contact |1 contact (SPST Form A) |
| Rating |0.15A/250V AC/DC |
| Galvanic isolation |3,750V AC 1 min |
| Operate time |1 ms max |
| Release time |0.25 ms max |
| Update time |1 cycle |
| Connector / wire size |Removable, 4 pins; 14 AWG (up to 1.5 mm²) |

Optional modular I/O – digital inputs
| Dry / wet contacts |Internally wetted @ 24V DC, or wet contact @ 250V DC (12DI/4DO only) |
| Sensitivity |Open >100kΩ; closed <100Ω |
| Galvanic isolation |3,750V AC 1 min |
| Internal power supply |24V DC, 4DI/2DO or 12DI/4DO |
| External power supply |250V DC (12DI/4DO only) |
| Scan time |1 ms |
| Connector / wire size |Removable, 5 pins; 14 AWG (up to 1.5 mm²) |

Optional modular I/O – analogue outputs
| Ranges (upon order) |±1mA / 0–1mA (max. 5kΩ, 100% overload); 0–20mA / 4–20mA (max. 510Ω) |
| Isolation |2,500V AC 1 min |
| Power supply |Internal |
| Accuracy |0.5% FS |
| Update time |1 cycle |
| Connector / wire size |Removable, 5 pins; 14 AWG (up to 1.5 mm²) |

Built-in communication – serial (RS-485)
| Max. baud rate |115.2 kb/s |
| Optical isolation |3,000V AC (L-G) for 1 min. |
| Max. cable length |1,000 m |
| Protocols |Modbus RTU/ASCII; DNP 3.0; IEC 60870-5-101 (option) |
| Terminal blocks |3 sealed, pitch 7–10mm, 2.5 to 4 mm² |

COM2 (optional module) – Ethernet port
| Availability |Independent module or add-on to 12DIOR module; plug-in DIN-rail mount 73×90×32mm, or plug-in no-mount |
| Interface |Transformer-isolated 10/100BaseT Ethernet |
| Supported protocols |Modbus/TCP (port 502), IEC 60870-5-104, DNP3/TCP (port 20000) |
| Simultaneous connections |4 (2 Modbus/TCP + 2 DNP3/TCP) |
| Connector type |RJ45 modular |
| Isolation |1,500V DC @ 1 min |

Cellular port
| Supported protocols |Modbus/TCP (port 502), DNP3/TCP (port 20000) |
| Connector type |SMA |

Profibus DP (IEC 61158)
| Interface |RS-485 optically isolated Profibus |
| Connector type |Removable, 5 pins |
| Baud rate |9,600 bit/s – 12 Mbit/s (auto-detect) |
| Data |32 bytes input, 32 bytes output; PROFIBUS DP |

RS-232/422-485 port
| Interface |RS-232 or RS-422/485, optically isolated |
| Isolation |3,000V AC 1 min |
| Baud rate |Up to 115.2 kbps |
| Supported protocols |Modbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101 |
| Connector type |Removable 5-pin (RS-422/485); DB9 (RS-232) |

Front panel
| Display type |2×16 character transflective LCD with backlight |
| Character size |3.2×1.85 mm |
| Viewing area |46×11 mm |
| LEDs |6 total: 1 pulse calibration output, 3 voltage indication, 2 RX/TX activity |
| Nameplate |According to IEC 60688 & IEC 62052-11 |

Construction
| Enclosure |DIN-rail mount, complies with EN50022 |
| Dimensions [W×H×D] |125 × 90 × 75mm |
| Enclosure material |Reinforced polycarbonate |
| Enclosure protection |IP20 |

Environmental conditions
| Operational |−25°C to 60°C (−13°F to 140°F) |
| Storage |−30°C to 85°C (−22°F to 185°F) |

## Standards compliance

### EMC immunity (IEC 60688 and IEC 62052-11)

- IEC 61000-4-2: Electrostatic discharge, 15/8kV air/contact
- IEC 61000-4-3: Electromagnetic RF fields, 10V/m @ 80MHz–1000MHz
- IEC 61000-4-4: Fast transients burst, 4kV on current and voltage circuits, 2kV for auxiliary circuits
- IEC 61000-4-5: Surge, 4kV on current and voltage circuits, 1kV for auxiliary circuits
- IEC 61000-4-6: Conducted radio-frequency, 10V @ 0.15MHz–80MHz
- IEC 61000-4-8: Power frequency magnetic field

### EMC emission (radiated / conducted)

- EN 55022:2010 Class A (CISPR 22)
- FCC Part 15 Class A (mandatory)

### Safety

- UL / IEC 61010-1
- UL 916

### Insulation

- IEC 62052-11: Insulation impulse 6kV/500Ω @ 1.2/50 µs
- AS/IEC 62053-22: AC voltage tests related to ground, 4kV AC @ 1 min, for power and signal ports (above 40V)
- 2.5kV AC r.m.s. @ 1 min, for other ports (below 40V)

### Accuracy according to

- AS/IEC 62053-22, Class 0.5S – active energy
- IEC 62053-21, Class 0.5 – reactive energy
- IEC 60688, Class 0.5S – active energy
- IEC 60688, Class 1 – reactive energy
- ANSI C12.20, Class 0.5

## Ordering information

MODEL – CURRENT – CAL. FREQ. – RES. – POWER – SEAL – PROTOCOL

Models
| EM132: Multi-function transducer |EM132 |
| EM132-TP: EM132 with two integral RS-485 ports (AC/DC power supply only) |EM132-TP |

Current inputs
| 5 Ampere |5 |
| 1 Ampere |1 |
| Direct current measurement up to 63A* |63 |
| Direct current measurement up to 100A* (up to 55°C ambient) |100 |
| 5A split-core remote High Accuracy Current Sensor (HACS)* |RS5 |
| High Accuracy Current Sensors (HACS)** |HACS |
| High Accuracy Current Sensors (HACS), with wires |HACS-SPDR |

Calibration at frequency
| 25 Hz (supports 1A and 5A models only) |25HZ |
| 50 Hz |50HZ |
| 60 Hz |60HZ |
| 400 Hz (supports 1A and 5A models only) |400HZ |

Resolution
| Low resolution 1A, 1V |– |
| High resolution 0.01A, 0.1V |H |

Power supply
| 40–300V AC/DC |ACDC |
| Self-energised: powered from measured voltages (120–277V L-N), 50/60Hz models only. Not suitable for EM132-TP |SE |
| 12V/24V DC power supply. Not suitable for EM132-TP |21DC |

Mechanical seal
| Standard seal |– |
| Special seal |S |

Electronic seal
| Energy register is accessible |– |
| Energy register is protected |P |

Communication protocol
| Modbus and DNP 3.0 |– |
| Modbus and IEC 60870-5-101/104*** |870 |

Order-code bar condensed for width — mechanical and electronic seal are two separate code positions; see the tables for the full breakdown. * For 50/60Hz only. ** For 50/60Hz only, requires ordering of 3 HACS. *** –104 requires ETH; not compatible with AR version, does not work over cellular network.

### Expansion modules

Maximum 1 module per instrument, can be ordered separately.

Analogue outputs
| 4 analogue outputs: ±1mA |AO1 |
| 4 analogue outputs: 0–20mA |AO2 |
| 4 analogue outputs: 0–1mA |AO3 |
| 4 analogue outputs: 4–20mA |AO4 |
| 4 analogue outputs: 0–5mA |AO7 |
| 4 analogue outputs: ±5mA |AO8 |

Communication
| Ethernet (TCP/IP) for DIN rail |ETHD |
| Profibus |PRO |
| RS232 (for DIN rail enclosure) |RS232D |
| RS232/422/485 |RS232 |
| CAT-M / LTE modem – x: G=Europe, V=Verizon (US), A=AT&T (US), T=Telstra (AUS); y: T=Top Antenna, F=Front Antenna* |LTEx-y |

* Does not support 870 protocol. Supplied with bendable antenna.

Digital inputs
| 4 DI (dry contact) / 2 relay outputs, 250V/5A AC |DIOR |
| 4 DI (dry contact) / 2 SSR outputs, 250V/0.1A AC |DIOS |
| 8 DI (dry contact) |8DI |

12 DIOR module
| 12 digital inputs / 4 relay outputs, 250V/5A AC |12DIOR |
| Digital input rating – dry contact (DRC), 48V, 125V or 250V |DRC/48V/125V/250V |
| Communication port: none |– |
| Communication port: RS-485 |485 |
| Communication port: Ethernet |ETH |

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 1071 KB)](https://satec-global.com.au/documentation/EM132-Multi-Function-Meter-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-d731005d5bc2/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/em132/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [Does the EM132 have a replaceable clock backup battery?](https://satec-global.com.au/support/articles/em132-clock-backup-battery/)
- [Which EM132 model and input variant do I have?](https://satec-global.com.au/support/articles/em132-identify-model-variant/)
- [What should I record before asking for help with an EM132?](https://satec-global.com.au/support/articles/em132-support-evidence/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).