# CT-MES solid core current transformers datasheet: specifications and ordering codes

> CT-MES datasheet as a web page: Compact plastic case current transformers for energy metering. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/ct-mes-solid-core-ct/

---

CT-MES · DATASHEET

# CT-MES solid core current transformers datasheet

Compact plastic case current transformers for energy metering.

Transcribed from the SATEC Australia datasheet [TBV1.0, 30 September 2026](https://satec-global.com.au/documentation/CT-MES-Solid-Core-Current-Transformers-Datasheet-TBV1-0.pdf) (PDF, 7 pages, 1580 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The CT-MES range is a family of compact solid core current transformers for energy metering and power monitoring. It is built for switchboard builders, electrical contractors and facility teams who need an accurate CT that fits tight panel space.

Eight frame sizes cover primary currents from 5A to 3000A with a 5A or 1A secondary. Every unit has integral hinged terminal covers that can be sealed and a self-extinguishing Class V0 case. Choose DIN rail, panel bracket or busbar clip mounting to suit the installation.

## Main features

- Eight frame sizes from 5A to 3000A primary
- 5A or 1A secondary current
- Accuracy Class 0.5, 1.0 or 3.0 subject to burden
- Rated output from 1.5VA to 25VA depending on model and ratio
- Compact plastic case with a smaller footprint
- Integral hinged terminal covers that can be sealed
- Self-extinguishing Class V0 casing
- DIN rail, foot, panel bracket or busbar clip mounting
- Insulation level 0.72/3kV for low voltage systems
- Rated frequency 50Hz to 60Hz
- Short-time thermal current Ith = 60 × In
- Instrument security factor FS < 5

## Feature capabilities

### CT-MES-62 Series

- 62/20B, 62/20, 62/30 and 62/40. Narrow 62mm body for 5/5A to 400/5A.

### CT-MES-80 Series

- 80/30 and 80/40. 80mm body with fixing feet for 30/5A to 500/5A.

### CT-MES-100 and 140 Series

- 100/60 and 140/100. Large windows for 600/5A to 3000/5A.

### Compact Solid Core Design

- Closed solid core with the primary conductor passed through the window
- Plastic case with a much smaller footprint than conventional CTs
- Eight frame sizes so one family covers most LV metering points
- CT-MES-62/20B low current model with an integral primary bar for 5/5A to 150/5A

### Metering Accuracy

- Class 0.5 ratings available in all eight frame sizes
- Class 1.0 and Class 3.0 ratings for general monitoring and low ratios
- Rated output of 1.5VA to 25VA listed per ratio in the ratings tables
- Select an output that covers the meter burden plus the secondary cabling

### Flexible Mounting Options

- Each CT-MES mounts the way the switchboard needs it. Fix it to DIN rail through an adapter, to a panel with the metal bracket or directly onto a busbar with a support clip.

### Safety and Protection

- Instrument security factor FS < 5 limits secondary current during faults to help protect connected meters
- Short-time thermal current of 60 × In
- Insulation level 0.72/3kV at 50Hz to 60Hz
- Self-extinguishing Class V0 casing
- Sealable terminal covers deter tampering and protect live terminals

### Part of a Complete SATEC Metering System

- Pair CT-MES transformers with any SATEC power meter that accepts 5A or 1A current inputs to build a complete metering point from one supplier. Where the conductor cannot be disconnected choose split core current transformers. For high accuracy applications see the HACS high accuracy current sensors. Browse the full range of current transformers for energy meters.

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Electrical
| Rated primary current |5A to 3000A (model dependent) |
| Rated secondary current |5A or 1A |
| Rated frequency |50Hz to 60Hz |
| Insulation level |0.72/3kV |
| Short-time thermal current |Ith = 60 × In |
| Instrument security factor |FS < 5 |

Accuracy and output
| Accuracy class |0.5, 1.0 or 3.0 (subject to burden) |
| Rated output |1.5VA, 2.5VA, 3.75VA, 5VA, 10VA, 15VA, 20VA, 25VA |
| Ratings by ratio |See ratings tables, pages 4 to 6 |

Construction
| Type |Solid core, window type |
| Casing |Plastic, self-extinguishing Class V0 |
| Terminals |Integral hinged terminal covers, sealable |
| Frame sizes |8 |
| Dimensions |See model overview and drawings |

Mounting
| DIN rail |Via DIN rail adapter |
| Panel |Metal mounting bracket or fixing feet |
| Busbar |Busbar support mounting clip |

Model overview: CT-MES-62/20B
| Ratio range |5/5A to 150/5A |
| Accuracy class |0.5, 1.0 |
| Rated output |1.5VA to 2.5VA |
| W × H × D (mm) |68 × 87.5 × 57 (79 incl. primary terminals) |
| Max. cable |Integral primary bar |

Model overview: CT-MES-62/20
| Ratio range |30/5A to 200/5A |
| Accuracy class |0.5, 1.0, 3.0 |
| Rated output |1.5VA to 5VA |
| W × H × D (mm) |68 × 87.5 × 57 |
| Max. cable |Ø22mm |

Model overview: CT-MES-62/30
| Ratio range |30/5A to 200/5A |
| Accuracy class |0.5, 1.0, 3.0 |
| Rated output |1.5VA to 5VA |
| W × H × D (mm) |68 × 87.5 × 57 |
| Max. cable |Ø30mm |

Model overview: CT-MES-62/40
| Ratio range |60/5A to 400/5A |
| Accuracy class |0.5, 1.0 |
| Rated output |1.5VA to 10VA |
| W × H × D (mm) |68 × 87.5 × 57 |
| Max. cable |Ø30mm |

Model overview: CT-MES-80/30
| Ratio range |30/5A to 200/5A |
| Accuracy class |0.5, 1.0, 3.0 |
| Rated output |1.5VA to 5VA |
| W × H × D (mm) |80 × 86.5 × 77 |
| Max. cable |Ø30mm |

Model overview: CT-MES-80/40
| Ratio range |100/5A to 500/5A |
| Accuracy class |0.5, 1.0 |
| Rated output |2.5VA to 10VA |
| W × H × D (mm) |80 × 86.5 × 77 |
| Max. cable |Ø30mm |

Model overview: CT-MES-100/60
| Ratio range |600/5A to 1200/5A |
| Accuracy class |0.5, 1.0 |
| Rated output |10VA to 20VA |
| W × H × D (mm) |101 × 118 × 77.4 |
| Max. cable |Ø50mm |

Model overview: CT-MES-140/100
| Ratio range |800/5A to 3000/5A |
| Accuracy class |0.5, 1.0 |
| Rated output |15VA to 25VA |
| W × H × D (mm) |140 × 155 × 53 |
| Max. cable |Ø86mm |

Dimensions are overall and taken from the factory drawings. Busbar window sizes are shown on each drawing on pages 4 to 6.

CT-MES-62/20B · 5/5A to 150/5A: rated output (VA) by rated current (A)
| 5/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 10/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 15/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 20/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 25/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 30/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 40/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 50/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 60/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 75/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 100/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 150/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |

CT-MES-62/20 · 30/5A to 200/5A: rated output (VA) by rated current (A)
| 30/5 |Class 0.5: n/a · Class 1.0: n/a · Class 3.0: 1.5 |
| 40/5 |Class 0.5: n/a · Class 1.0: n/a · Class 3.0: 1.5 |
| 50/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 60/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 75/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 80/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 100/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 150/5 |Class 0.5: 2.5 · Class 1.0: 3.75 · Class 3.0: n/a |
| 200/5 |Class 0.5: 3.75 · Class 1.0: 5 · Class 3.0: n/a |

Ratings shown are for a 5A secondary. n/a means the ratio is not offered in that accuracy class. Contact SATEC for 1A secondary ratings. All dimensions in millimetres.

CT-MES-62/30 · 30/5A to 200/5A: rated output (VA) by rated current (A)
| 30/5 |Class 0.5: n/a · Class 1.0: n/a · Class 3.0: 2.5 |
| 40/5 |Class 0.5: n/a · Class 1.0: n/a · Class 3.0: 2.5 |
| 50/5 |Class 0.5: n/a · Class 1.0: n/a · Class 3.0: 2.5 |
| 60/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 75/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 100/5 |Class 0.5: 1.5 · Class 1.0: 2.5 · Class 3.0: n/a |
| 150/5 |Class 0.5: 2.5 · Class 1.0: 3.75 · Class 3.0: n/a |
| 200/5 |Class 0.5: 3.75 · Class 1.0: 5 · Class 3.0: n/a |

CT-MES-62/40 · 60/5A to 400/5A: rated output (VA) by rated current (A)
| 60/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 75/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 100/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 150/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 200/5 |Class 0.5: 2.5 · Class 1.0: 3.75 · Class 3.0: n/a |
| 250/5 |Class 0.5: 2.5 · Class 1.0: 3.75 · Class 3.0: n/a |
| 300/5 |Class 0.5: 3.75 · Class 1.0: 5 · Class 3.0: n/a |
| 400/5 |Class 0.5: 5 · Class 1.0: 10 · Class 3.0: n/a |

CT-MES-80/30 · 30/5A to 200/5A: rated output (VA) by rated current (A)
| 30/5 |Class 0.5: n/a · Class 1.0: n/a · Class 3.0: 2.5 |
| 50/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 60/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 75/5 |Class 0.5: n/a · Class 1.0: 1.5 · Class 3.0: n/a |
| 100/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 150/5 |Class 0.5: 2.5 · Class 1.0: 3.75 · Class 3.0: n/a |
| 200/5 |Class 0.5: 5 · Class 1.0: 5 · Class 3.0: n/a |

Ratings shown are for a 5A secondary. n/a means the ratio is not offered in that accuracy class. Contact SATEC for 1A secondary ratings. All dimensions in millimetres.

CT-MES-80/40 · 100/5A to 500/5A: rated output (VA) by rated current (A)
| 100/5 |Class 0.5: n/a · Class 1.0: 2.5 · Class 3.0: n/a |
| 150/5 |Class 0.5: 2.5 · Class 1.0: 3.75 · Class 3.0: n/a |
| 200/5 |Class 0.5: 3.75 · Class 1.0: 5 · Class 3.0: n/a |
| 250/5 |Class 0.5: 3.75 · Class 1.0: 5 · Class 3.0: n/a |
| 300/5 |Class 0.5: 5 · Class 1.0: 5 · Class 3.0: n/a |
| 400/5 |Class 0.5: 5 · Class 1.0: 10 · Class 3.0: n/a |
| 500/5 |Class 0.5: 5 · Class 1.0: 10 · Class 3.0: n/a |

CT-MES-100/60 · 600/5A to 1200/5A: rated output (VA) by rated current (A)
| 600/5 |Class 0.5: 10 · Class 1.0: 15 |
| 800/5 |Class 0.5: 10 · Class 1.0: 15 |
| 1000/5 |Class 0.5: 10 · Class 1.0: 20 |
| 1200/5 |Class 0.5: 15 · Class 1.0: 20 |

CT-MES-140/100 · 800/5A to 3000/5A: rated output (VA) by rated current (A)
| 800/5 |Class 0.5: 15 · Class 1.0: 20 |
| 1000/5 |Class 0.5: 15 · Class 1.0: 20 |
| 1200/5 |Class 0.5: 15 · Class 1.0: 20 |
| 1500/5 |Class 0.5: 15 · Class 1.0: 20 |
| 1600/5 |Class 0.5: 15 · Class 1.0: 20 |
| 2000/5 |Class 0.5: 15 · Class 1.0: 25 |
| 2500/5 |Class 0.5: 15 · Class 1.0: 25 |
| 3000/5 |Class 0.5: 15 · Class 1.0: 25 |

Ratings shown are for a 5A secondary. n/a means the ratio is not offered in that accuracy class. Contact SATEC for 1A secondary ratings. All dimensions in millimetres. Accuracy Class 0.5, 1.0 and 3.0 subject to rated burden (p. 7).

## Standards compliance

### Instrument Transformers

- IEC 61869-2: Additional requirements for current transformers
- AS 61869.2: Additional requirements for current transformers
- IEC 60044-1: Current transformers
- AS 60044.1: Current transformers

### National Standards

- BS 7626: Current transformers
- VDE 0414: Instrument transformers

### Construction

- Self-extinguishing Class V0 casing
- Sealable terminal covers

## Ordering information

MODEL · PRIMARY / SECONDARY · ACCURACY CLASS · RATED OUTPUT · OPTIONS

Model
| 5/5A to 150/5A, integral primary bar |CT-MES-62/20B |
| 30/5A to 200/5A, Ø22mm |CT-MES-62/20 |
| 30/5A to 200/5A, Ø30mm |CT-MES-62/30 |
| 60/5A to 400/5A, Ø30mm |CT-MES-62/40 |
| 30/5A to 200/5A, Ø30mm |CT-MES-80/30 |
| 100/5A to 500/5A, Ø30mm |CT-MES-80/40 |
| 600/5A to 1200/5A, Ø50mm |CT-MES-100/60 |
| 800/5A to 3000/5A, Ø86mm |CT-MES-140/100 |

Primary / secondary
| Primary current 5A to 3000A (see ratings tables) |e.g. 100 |
| 5A secondary |/5 |
| 1A secondary |/1 |

Accuracy class
| Class 0.5 |0.5 |
| Class 1.0 |1.0 |
| Class 3.0 (selected low ratios) |3.0 |

Options
| Rated output per ratings table |VA |
| Mounting: DIN rail, panel or busbar |Specify |

Example: CT-MES-62/30 · 100/5A · Class 0.5 · 1.5VA

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 1580 KB)](https://satec-global.com.au/documentation/CT-MES-Solid-Core-Current-Transformers-Datasheet-TBV1-0.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-a69f713af47c/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).