# BFM-II multi-circuit branch feeder monitor and revenue meter datasheet: specifications and ordering codes

> BFM-II datasheet as a web page: Multi-circuit branch feeder monitor and revenue meter. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.0.

Source page: https://satec-global.com.au/support/datasheets/bfm-ii/

---

BFM-II · DATASHEET

# BFM-II multi-circuit branch feeder monitor and revenue meter datasheet

Multi-circuit branch feeder monitor and revenue meter.

Transcribed from the SATEC Australia datasheet [TBV1.0, 3 September 2026](https://satec-global.com.au/documentation/BFM-II-datasheet.pdf) (PDF, 9 pages, 1127 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The BFM II is a modular multi-circuit power meter that monitors up to 18 three-phase (54 single-phase) branch circuits from a single device, suiting applications from medium-voltage substation branch monitoring to commercial multi-tenant billing in shopping centres and office buildings. Suitable for both new and retrofit projects, it installs directly into new or existing switchboards.

Built around SATEC’s High Accuracy Current Sensors (HACS), the BFM II combines a Class 0.5S revenue meter with built-in RS-485 and Ethernet communications, modular digital and analogue I/O, and an optional 4G cellular modem. An optional Digital Fault Recorder (DFR) adds 36-channel waveform capture at 40×In for substation fault analysis.

## Main features

- Modular multi-circuit metering — up to 54 single-phase or 18 three-phase current channels from a single device
- Dual input voltage — an optional second 3-phase voltage input module (VIM) for measuring a parallel power source
- Modular digital & analogue I/O — up to 72 I/O points for pulse output, circuit-breaker status, analogue parameters and more
- Optional Digital Fault Recorder (DFR) — 36-channel (12×3-phase) waveform capture at 40×In, triggered internally or externally
- Multi-option current inputs — HACS (100–3,000A), RS5 5A split-core retrofit sensors, or FLEX 3VAC current-sensor interface
- Communication — built-in RS-485 and Ethernet, with an optional 4G cellular modem
- Open protocols — Modbus RTU/ASCII, DNP3.0, BACnet, IEC 60870-5-101/104
- Revenue-grade, anti-tamper design to Class 0.5S accuracy

## Feature capabilities

### BFM II

- Base multi-circuit meter — up to 18 three-phase or 54 single-phase current channels, Class 0.5S revenue metering and submetering

### BFM II + DFR

- Adds digital fault recording — 36-channel (12×3-phase) pre/post-fault waveform capture at 40×In for substation fault analysis

### BFM II + VIM

- Adds a second 3-phase voltage input module for measuring a parallel power source

### Multi-Functional 3-Phase Smart Meter

- True RMS volts, amps, power, power factor, neutral current and frequency, and many more
- Ampere/Volt demand meter
- 50/60 Hz measurement

### Billing / TOU Energy Meter

- Class 0.5S AS/IEC 62053-22 four-quadrant active and reactive energy poly-phase static meter
- Three-phase total and per-phase energy measurement — active, reactive and apparent energy counters
- Time-of-Use: 8 energy/demand registers × 8 tariffs, 4 seasons × 4 day types, 8 tariff changes per day
- Easily programmable tariff calendar schedule
- Automatic 120-day daily profile log for energy and maximum demand (total and tariff registers), per submeter

### Waveform and Digital Fault Recorder (optional — DFR version)

- Independent product; limited to 12 three-phase current channels
- Digital fault recording with pre/post-fault waveform capture on 36 current channels and 4 voltage channels, at 40×In
- Triggered externally through digital inputs, or internally from the embedded fault detector
- Automatic detection of fault category using sub-cycle measurements
- Fault triggers include programmable thresholds and hysteresis, adjustable for specific substation conditions
- Time-tagged fault events included in the fault event report

### Harmonic Analyser

- Individual voltage and current harmonic spectrum and angles, up to the 25th order harmonic
- Voltage and current THD, TDD and K-Factor

### Programmable Logical Controller

- Embedded programmable controller
- 4 control setpoints — programmable thresholds and delays
- Relay output control
- 1-cycle response time

### Event and Data Recording

- Non-volatile memory for timestamped event and data recording, per channel
- Event recorder for internal diagnostic events and setup changes
- Two data recorders — 2 separate programmable periodic data logs per channel

### Real-Time Clock

- Accuracy: maximum error of 5 seconds/month @ 25°C

### Current Input Options

- The BFM II features unique milliamp current inputs — each current-input module (CIM) is ordered for compatibility with one of three CT options below
- HACS — 40mA input designed for SATEC HACS CTs (100–3,000A)
- RS5 — 40mA input designated for 5A split-core HACS, reading 5A from a CT secondary; ideal for retrofit installation
- FLEX — for interfacing 3VAC current-sensor output
- Modules may be mixed and matched across up to 54 channels (max. 2 CIM modules per device)

### I/O Options

- 9DI / 18DI — 9 or 18 digital inputs (dry contact / 24, 125 or 250VDC), 1-cycle update time; unlatched, latched, pulse and KYZ operation; energy pulses
- 9RO — 9 Form A relay outputs, 5A @ 250VAC or 30VDC, 1-cycle update time (max. 2 modules per device)
- 4AI — 4 analogue inputs; selection of ±1mA, 0–20mA, 4–20mA and 0–1mA ranges, 0.5% FS accuracy, 2-cycle update time
- Up to 4 I/O modules per device

### Modular Design and Expansion

- Add-on modular design — up to 2 current-input modules, up to 4 digital/analogue I/O modules, 1 voltage-input module and 1 auxiliary power supply module per device
- EXT-BFM II extension cable for connecting optional modules remotely
- DIN-rail mounting

### Communications

- Built-in 2-wire RS-485 port, plus Ethernet 10/100Base-T
- Optional 4G cellular modem, with automatic fallback to 2G/3G
- Protocols: Modbus RTU, SATEC ASCII, DNP3.0; optional IEC 60870-5-101/104

### Display

- Optional 3.5″ touch-panel colour TFT graphic display module (GDM), 320×240 resolution, with backlight
- Serial TTL RS-232 connection to the meter, up to 460.8 kbps

### Meter Security

- 3-level password access, protecting meter setups and accumulated data from unauthorised changes

### Upgradeable Firmware

- Firmware upgrade via a serial or Ethernet port

### Software Support

- PAS — SATEC’s bundled configuration and data-acquisition tool, including waveforms, phasors and harmonics
- eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics
- Any third-party software supporting the open-protocol suite

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Voltage inputs — main voltage module and VIM module
| Installation |Category III |
| Nominal voltage |277/480V AC |
| Voltage range tolerance |±15% |
| Input impedance |0.35 MΩ |
| Measurement burden, powered by AUX supply — burden for 277V |≈ 0.08 VA |
| Measurement burden, powered by AUX supply — burden for 120V |≈ 0.02 VA |
| Measurement burden, powered by measurement inputs — burden for 277V |≈ 24 VA |
| Measurement burden, powered by measurement inputs — burden for 120V |≈ 16 VA |
| Galvanic isolation |4kV AC @ 1 min withstanding insulation |
| Connector type |Removable, 4 terminals |
| Wire size |Up to 10 AWG (up to 6 mm²) |
| Terminal pitch |10 mm |

AC current inputs
| Burden |<0.15 VA |
| Recommended wire size |18 AWG (1 mm²) |
| Isolation |600V |
| Terminal pitch |5 mm |

The BFM II is compatible with SATEC High Accuracy Current Sensors (HACS) only. These CTs, supplied as solid-core or split-core, range from 5A to 3,000A primary input. Caution: Connecting the device’s built-in current inputs (5mA for RS5 and 40mA for other HACS) with standard 1A or 5A outputs will irreparably harm your device! For full HACS specs, see the HACS datasheet.

Power supply — self-energised (three or single-phase, from any phase)
| Nominal voltage |120/208–277/480V AC (L-N/L-L) |
| Input range |70–561V AC, 50/60 Hz |
| Burden for 277V |<17 VA |

Unit may be self-energised from voltage inputs, or by the AUX power supply module

AUX power supply module
| Withstanding insulation |4kV AC @ 1 min |
| AC/DC power supply |L/+, N/− and GND |
| Rated input @ operating temperature −25°C to 60°C |50–290V AC 50/60Hz · 40–290V DC |
| Max. power output @ operating temperature −25°C to 60°C |10 W |
| Rated input @ operating temperature −40°C to 70°C |50–290V AC @ 50/60Hz · 90–290V DC |
| Max. power output @ operating temperature −40°C to 70°C |10 W |
| Recommended wire size |18 AWG (1 mm²), 600V isolation |
| Terminal pitch |7.5 mm, three pins |

Built-in communication — serial communication (RS-485), optically isolated port
| Isolation |4kV AC @ 1 min |
| Connector type |Removable, 3 terminals |
| Terminal pitch |5 mm |
| Wire size |Up to 12 AWG (up to 2.5 mm²) |
| Baud rate |Up to 115,200 bps |
| Supported protocols |Modbus RTU/ASCII, DNP3.0 |

Built-in communication — Ethernet port
| Transformer-isolated |10/100Base-T port |
| Isolation |4kV AC @ 1 min |
| Connector type |RJ45 modular |
| Supported protocols |Modbus TCP (port 502), DNP3/TCP (port 20000) |
| Simultaneous connections |5 sockets; SNTP time synchronisation |

Built-in communication — USB port, isolated USB 1.1
| Withstanding insulation |4kV AC @ 1 min |
| Connector type |A male, standard USB cable, max. 2 m |
| Supported protocols |Modbus RTU |

Optional modular communication — cellular modem
| Type |4G, with fallback to 2G/3G per network |
| Withstanding isolation |4kV AC @ 1 min |
| Connector type |SMA |
| Supported protocols |Modbus TCP (port 502), DNP3.0/TCP (port 20000) |

Optional modular communication — display COM / connector
| Baud rate |Up to 460,800 bps |
| Supported protocols |Modbus RTU |

Serial TTL RS-232 non-isolated port, for connecting to the Graphic Display Module

Optional modular I/O — 18 digital inputs — 9/18 DI (up to 4 modules)
| Sensitivity |Open @ >16kΩ · Closed @ <10kΩ |
| Scan time |½ cycle |
| Wire size |12 AWG (up to 2.5 mm²) |
| Terminal pitch |3.81 mm |

Optically isolated input, dry contact sensing (voltage-free); internal power supply 5VDC

Optional modular I/O — 9 relay output — SPST Form A
| Contact rating |5A @ 250VAC · 5A @ 30VDC |
| Update time |1 cycle |
| Recommended wire size |18 AWG (1 mm²), 600V isolation |
| Terminal pitch |3.81 mm |

Optional modular I/O — 4 analogue inputs
| Ranges (upon order) |±1mA · 0–20mA · 4–20mA · 0–1mA (100% overload) |
| Accuracy |0.5% FS |
| Scan time |2 cycles |
| Withstanding insulation |4kV AC @ 1 min |
| Recommended wire size |18 AWG (1 mm²), 600V isolation |
| Terminal pitch |3.81 mm |

Real-time clock
| Accuracy |Maximum error of 5 sec/month @ 25°C |

Graphical display module — GDM (option)
| Resolution |320 × 240 |
| Operating temperature |−20°C to +70°C |
| Communication |Serial TTL RS-232 non-isolated port |

3.5-inch touch-panel LCD graphic TFT display

Environmental conditions
| Operating temperature |−30°C to +70°C (−22°F to 158°F) |
| Storage temperature |−40°C to +85°C (−40°F to 185°F) |
| Humidity |0–95% RH, non-condensing |
| Altitude |≤ 2000 m |

Construction — overall dimensions
| Width |278 mm / 10.94″ (18 channels) · 554 mm / 21.81″ (54 channels) |
| Height |128 mm / 5.04″ |
| Depth |72.5 mm / 2.85″ |
| Weight |1.6 kg (36 channels) |
| Mounting |DIN-rail mount |

Construction — materials
| Enclosure |Reinforced polycarbonate |
| Panels |Polycarbonate |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Packaging case |Carton and Stratocell (polyethylene foam) brackets |
| Labels |Polyester film (UL94-V0) |

Measurement accuracy — Voltage
| Full scale @ input range |VL = 120V · VL = 230V |
| Accuracy — % reading |0.1 |
| Accuracy — % FS |0.005 |
| Conditions |100 to 300V |
| Range |0 to Imax = 10,000A (HACS primary current) |

Measurement accuracy — Line current
| Full scale @ input range |Instrument current transformer CTs IL = 100A |
| Accuracy — % reading |0.2 |
| Accuracy — % FS |0.005 |
| Conditions |1 to 100% FS |
| Range |0 to Imax = 10,000A (HACS primary current); starting current 0.1% FS |

Measurement accuracy — Active power
| Full scale @ input range |2×Vmax×IL/1000, kW |
| Accuracy — % reading |1 |
| Accuracy — % FS |0.02 |
| Conditions ||PF| ≥ 0.5 |
| Range |−120.000 to 120.000 kW |

Measurement accuracy — Reactive power
| Full scale @ input range |2×Vmax×IL/1000, kvar |
| Accuracy — % reading |1 |
| Accuracy — % FS |0.02 |
| Conditions ||PF| ≤ 0.9 |
| Range |−120.000 to 120.000 kvar |

Measurement accuracy — Apparent power
| Full scale @ input range |2×Vmax×IL/1000, kVA |
| Accuracy — % reading |1 |
| Accuracy — % FS |0.02 |
| Conditions ||PF| ≥ 0.5 |
| Range |0 to 120.000 kVA |

Measurement accuracy — Power factor
| Full scale @ input range |1.0 |
| Accuracy — % reading |— |
| Accuracy — % FS |1.0 |
| Conditions ||PF| ≥ 0.5, I ≥ 2% FSI |
| Range |−0.999 to +1.000 |

Measurement accuracy — Frequency
| Full scale @ input range |— |
| Accuracy — % reading |0.02 |
| Accuracy — % FS |— |
| Conditions |50Hz: 39.00 to 65.00Hz · 60Hz: 45.00 to 70.00Hz |
| Range |39Hz up to 70Hz |

Measurement accuracy — Active energy import
| Accuracy |Class 0.5 under conditions as per AS/IEC 62053-22; Class 0.5 under conditions as per ANSI C12, IEC 61557-12 |
| Range |0 to 99,999,999.9 kWh |

Measurement accuracy — Reactive energy import/export
| Accuracy |Class 0.5 under conditions as per IEC/AS 62053-24, |PF| ≤ 0.9 |
| Range |0 to 99,999,999.9 kvarh |

Measurement accuracy — Apparent energy
| Accuracy |Class 0.5 under conditions as per IEC 61557-12 |
| Range |0 to 99,999,999.9 kVAh |

FS: full scale (voltage or current). 1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ±1 digit. This does not include inaccuracies introduced by the user’s potential and current transformers. Accuracy calculated at 1-second average. 2. Specifications assume voltage and current waveforms with THD ≤ 5% for kvar, kVA and PF; reference operating temperature 20°C–24°C. 3. Measurement error is typically less than the maximum error indicated here. 4. Accuracy of the device complies with the AS/IEC 62053-22 Class 0.5S standard using solid-core HACS, and Class 1 when using split-core HACS.

## Standards compliance

### Accuracy

- Complies with AS/IEC 62053-22, Class 0.5S
- Meets ANSI C12.20-2010, Class 100, 400, accuracy 0.5%

### Electromagnetic immunity

- EMC per IEC 62052-11, AS/IEC 62053-22, ANSI C12.1 and ANSI C12.20
- IEC61000-4-2 — electrostatic discharge, 15kV air / 8kV contact
- IEC61000-4-3 — electromagnetic RF fields, 10V/m @ 80MHz–1000MHz
- IEC61000-4-4 — fast transients burst, 4kV on current and voltage circuits, 2kV for auxiliary circuits
- IEC61000-4-5 — surge, 6kV on current and voltage circuits, 1kV for auxiliary circuits
- IEC61000-4-6 — conducted radio-frequency, 10V @ 0.15MHz–80MHz
- IEC61000-4-8 — power-frequency magnetic field
- IEC61000-4-12 — damped oscillatory waves, 2.5kV CM and 1kV DM
- ANSI C12.1 – 4.7.3.3.1 — 100kHz ring wave surge, 6kV @ 0.5kA (per IEEE C62.41.2-2002)
- ANSI C12.1 – 4.7.3.3.2 — line surge, 1.2/50μs–8/20μs, 6kV @ 3kA (per IEEE C62.41.2-2002)
- ANSI C12.1 – 4.7.3.11 — SWC 2.5kV (per IEEE 37.90.1)
- CISPR 22 — Class B

### Insulation

- AS/IEC 62053-22 — AC voltage tests related to ground, 4kV AC @ 1 min, for power and signal ports above 40V, or per UL 61010-1/916 for basic and/or double insulation and Installation Category III

### Safety

- UL 916

### Atmospheric environment

- Accuracy operational ambient temperature range: −25°C to +60°C
- Operational ambient temperature range: −40°C to +70°C
- Long-term damp heat withstand per IEC 68-2-3, <95% non-condensing, +40°C
- Transport and storage temperature range: −40°C to +85°C
- IEC 62052-11 (ref. IEC 60068-2-6) — vibration: 10Hz–150Hz, transition frequency 60Hz, constant movement amplitude 0.075mm (f<60Hz), constant acceleration 9.8 m/s² / 1g (f>60Hz)
- IEC 62052-11 (ref. IEC 60068-2-27) — shock: half-sine pulse, peak acceleration 30gn (300 m/s²); additional transport vibration and shocks — longitudinal 2.0g, vertical 1.2g, transversal 1.2g
- IEC 60529 — IP50

## Ordering information

BFM II – CURRENT – CALIBRATION – DISPLAY – TEST / CERT

Model
| BFM-II Branch Feeder Monitor |BFM II |

Current — for standard 18 channels
| 100A to 3000A High Accuracy Current Sensors (HACS). Requires ordering of up to 18 HACS |HACS |
| 5A split-core remote high accuracy current sensor (HACS). Requires ordering of up to 18 CS05S |RS5 |
| Use of 3VAC current clamps |FLEX |

Calibration frequency
| 50 Hz |50HZ |
| 60 Hz |60HZ |

Display options
| Detachable Graphic Display Module |G |
| Blank panel |X |

Test / cert
| Full functional test, calibration at various work loads & detailed test report |— |

Extension
| Extension cable for connecting optional modules remotely (ordered separately) |EXT-BFM II |

### Expansion modules

Optional modules, ordered separately

Current input module (CIM) — up to 2 CIM modules per device; no more than 1 CIM when using the VIM module
| 6 current input module (CIM 6) — HACS version |C6H-BFM II |
| 6 current input module (CIM 6) — RS5 version |C6R-BFM II |
| 6 current input module (CIM 6) — FLEX version |C6F-BFM II |
| 18 current input module (CIM 18) — HACS version |C18H-BFM II |
| 18 current input module (CIM 18) — RS5 version |C18R-BFM II |
| 18 current input module (CIM 18) — FLEX version |C18F-BFM II |

Voltage input module (VIM) — 1 VIM only per device
| Additional 3-phase voltage input module — 50Hz |VIM50Hz |
| Additional 3-phase voltage input module — 60Hz |VIM60Hz |

Communication options
| 4G modem, supplied with bendable antenna |T4G-BFM II |

I/O options — max. 4 modules per device
| 9 digital inputs module — dry contact |DI9-DRC-BFM II |
| 9 digital inputs module — 24VDC |DI9-24V-BFM II |
| 9 digital inputs module — 125VDC |DI9-125V-BFM II |
| 9 digital inputs module — 250VDC |DI9-250V-BFM II |
| 18 digital inputs module — dry contact |DI18-DRC-BFM II |
| 18 digital inputs module — 24VDC |DI18-24V-BFM II |
| 18 digital inputs module — 125VDC |DI18-125V-BFM II |
| 9 Form A relay outputs module (max. 2 modules per device) |RLY9-BFM II |
| 4 analogue inputs module — ±1mA |AI1-BFM II |
| 4 analogue inputs module — 0–20mA |AI2-BFM II |
| 4 analogue inputs module — 0–1mA |AI3-BFM II |
| 4 analogue inputs module — 4–20mA |AI4-BFM II |

Auxiliary power supply — max. 1 module per device
| Auxiliary power supply 50–290V AC, 40*–290V DC |AUX-ACDC-BFM II |

* Above 60°C — minimum 90V DC

## Downloads and related

- [Download the datasheet (PDF, TBV1.0, 1127 KB)](https://satec-global.com.au/documentation/BFM-II-datasheet.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-e9704a51eeb0/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/bfm/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [How do I address multiple BFM meters on RS-485 or Ethernet?](https://satec-global.com.au/support/articles/bfm-rs485-ethernet-addressing/)
- [Replacing the BFM-II backup battery](https://satec-global.com.au/support/articles/bfm-ii-battery-replacement/)
- [Which BFM-II module combination fits my circuits?](https://satec-global.com.au/support/articles/bfm-ii-module-combination-capacity/)
- [What to record on a new BFM-II before commissioning](https://satec-global.com.au/support/articles/bfm-ii-identify-before-commissioning/)
- [How BFM-II current inputs, phases and submeters relate](https://satec-global.com.au/support/articles/bfm-ii-inputs-phases-submeters/)
- [How do I tell a BFM-II DFR, a standard BFM-II and a BFM136 apart?](https://satec-global.com.au/support/articles/bfm-dfr-bfm-ii-bfm136-identification/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).