# BFM-II DFR multi-feeder power monitor and digital fault recorder datasheet: specifications and ordering codes

> BFM-II DFR datasheet as a web page: Multi-Feeder Power Monitor and Digital Fault Recorder. Specifications, ordering codes and standards, transcribed from SATEC Australia datasheet TBV1.1.

Source page: https://satec-global.com.au/support/datasheets/bfm-ii-dfr/

---

BFM-II DFR · DATASHEET

# BFM-II DFR multi-feeder power monitor and digital fault recorder datasheet

Multi-Feeder Power Monitor and Digital Fault Recorder.

Transcribed from the SATEC Australia datasheet [TBV1.1, 16 September 2026](https://satec-global.com.au/documentation/BFM-II-DFR-Datasheet-TBV1-1.pdf) (PDF, 8 pages, 1322 KB). If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## Overview

The BFM-II DFR is a multi-feeder power monitor and digital fault recorder built for utility distribution substations. A single device monitors six, eight or up to twelve three-phase feeders on a common bus voltage. It connects to the existing CTs and PTs alongside legacy electromechanical protection relays, so it adds measurement and automation data without interfering with the protection scheme.

A modular design supports clip-on current sensors, plug-in digital and analogue I/O, relay outputs and an optional cellular modem. RS-485, Ethernet and USB ports are standard, with Modbus, DNP 3.0 and BACnet support. An integrated graphical touch screen, 256 MB of onboard memory and a universal AC/DC auxiliary supply complete the package.

## Main features

- Monitors six, eight or up to twelve three-phase feeders in a single device
- True RMS volts, amps, active, reactive and apparent power, power factor, frequency and THD
- Per-phase and total measurement for most parameters
- Power quality monitoring of voltage and current harmonics
- Digital fault recording with pre-fault and post-fault waveform capture
- Class 0.5S accuracy to AS/IEC 62053-22 and 0.2% to ANSI C12.20
- 256 MB of onboard memory for event, waveform and data logs
- Standard RS-485, Ethernet and USB ports, with an optional cellular modem
- Modbus RTU/ASCII, DNP 3.0 and BACnet protocol support
- Integrated graphical touch screen, with an optional remote display
- DIN rail or enclosure installation
- Universal auxiliary supply, 50 to 290 VAC or 40 to 290 VDC

## Feature capabilities

### Digital fault recording

- Pre-fault and post-fault waveform capture on recorded events
- Event records and captured waveforms viewed through Power Analysis Software (PAS)
- Waveform export to COMTRADE format for third-party fault analysis tools
- 256 MB of onboard memory for long-term event and waveform storage

### Multi-feeder power monitoring

- Six, eight or up to twelve three-phase feeders on a common bus voltage
- True RMS volts, amps, active, reactive and apparent power, power factor and frequency
- Per-phase as well as total measurement for most parameters
- Hundreds of parameters measured on each load through advanced digital signal processing

### Power quality monitoring

- Voltage and current harmonic measurement
- Total harmonic distortion on voltage and current
- Detailed harmonic capture with direction, viewed in PAS

### Energy measurement and accuracy

- Class 0.5S energy accuracy to AS/IEC 62053-22
- ANSI C12.20-2010, Class 100 and Class 400, accuracy 0.2%
- Three-phase and per-phase energy measurement on every monitored feeder
- Accuracy held across an operational ambient range of −25 °C to +60 °C

### Retrofit without an outage

- Clip-on current sensors fit onto existing 5 A secondary circuits
- Non-intrusive to the protection relays, with no change to the protection scheme
- Ultra low burden, up to 20 x 5 A (100 A) maximum
- CS1S split-core sensor with a 16 mm (0.63 in) opening and a 2.5 m cable
- Sensors can be located up to 274 m (900 ft) from the meter
- An entire substation can be updated in a single day

### Display options

- Integrated 3.5 inch touch-panel LCD graphic TFT display at 320 x 240
- View each circuit one at a time, with a programmable screen saver
- Optional RGM-180 remote display with a 5.7 inch touch colour screen
- Remote display connects over Ethernet or serial

### Communications

- COM1: optically isolated RS-485 up to 115,200 bps, Modbus RTU/ASCII and DNP 3.0
- Ethernet: transformer-isolated 10/100Base-T with Modbus TCP (502), DNP3/TCP (20000) and BACnet
- Up to five simultaneous Ethernet connections, with SNTP time synchronisation
- Isolated USB 1.1 port for local connection over Modbus RTU
- Optional cellular modem with a second RS-422/485 communications port

### Plug-in I/O modules — maximum 2 modules per device

- 18 optically isolated digital inputs, dry contact or 24, 48, 125 and 250 VDC variants
- Nine SPST Form A relay outputs rated 5 A at 250 VAC or 5 A at 30 VDC
- Four optically isolated analogue inputs with 0.5% FS accuracy
- Current input modules in six-channel and eighteen-channel versions

### Data recording and timekeeping

- 256 Mbytes of standard onboard memory
- Real-time clock accurate to better than 5 seconds per month at 25 °C
- Event, trend and waveform logs retrieved over any communications port

### Software support

- Power Analysis Software (PAS) configures the device and monitors real-time data, and is bundled with every SATEC device at no charge
- Expertpower is SATEC's browser-based energy management, billing and power quality platform, with no client software to install
- The eXpertConnect™ App gives mobile access to energy, demand and cost data drawn from Expertpower

### Installation

- DIN rail or enclosure installation
- Universal auxiliary power supply for AC or DC operation
- Removable plug-in connectors throughout for straightforward commissioning
- Installation requires no outage on the monitored circuits

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

## Specifications

Environmental conditions
| Operating temperature |−30 °C to +70 °C (−22 °F to 158 °F) |
| Storage temperature |−40 °C to +85 °C (−40 °F to 185 °F) |
| Humidity |0 to 95% RH, non-condensing |
| Altitude |≤ 2000 m |

Construction
| Width |278 mm (18 channels) to 554 mm (54 channels) |
| Height |128 mm |
| Depth |72.5 mm |
| Weight |1.6 kg (36 channels) |

Materials
| Enclosure & panels |Polycarbonate |
| PCB |FR4 (UL94-V0) |
| Terminals |PBT (UL94-V0) |
| Plug-in connectors |Polyamide PA6.6 (UL94-V0) |
| Packaging case |Carton and Stratocell polyethylene foam brackets |
| Labels |Polyester film (UL94-V0) |

Power supply
| Configuration |Three-phase supply, 1, 2 or 3-phase operation, 3 x 120/208 to 277/480 VAC |
| Input range |50 to 290 VAC / 40 to 290 VDC, 50/60 Hz |
| Max. power |10 W |
| Burden at 277 V |< 17 VA |
| Withstand insulation |4 kV AC at 1 min |
| Wire size |Up to 10 AWG (up to 6 mm²) |
| Terminal pitch |10 mm, 4 pins plus signal ground stud |

AC voltage inputs (V1, V2, V3, VN)
| Measuring range |3 x 120/208 to 277/480 VAC |
| Input impedance |10 MΩ |
| Burden at 277 V |≈ 0.08 VA |
| Burden at 120 V |≈ 0.02 VA |
| Galvanic isolation |4 kV AC at 1 min |
| Connector type |Removable, 4 terminals |
| Wire size |Up to 10 AWG (up to 6 mm²) |
| Terminal pitch |10 mm |

AC current inputs I1–I36 — standard HACS
| Input |Via SATEC HACS, 100 A to 3000 A |
| Operating range |Maximum continuous 120% of I max, 120 A for HACS 100 A |
| Nominal measured current |50 A RMS (HACS 100 A) |
| Burden |< 0.15 VA |
| Overload withstand |100 A RMS continuous |
| Connector type |Removable, 6 terminals for 3 current inputs |
| Wire size |10 AWG (2.5 to 6 mm²) |
| Terminal pitch |5 mm |

AC current inputs I1–I36 — optional RS5
| Input |Via SATEC HACS CS05S |
| Operating range |Maximum continuous 20 A primary current |
| Nominal measured current |5 A RMS primary current |
| Burden |< 0.15 VA |
| Overload withstand |12 A RMS continuous |
| Connector type |Removable, 6 terminals for 3 current inputs |
| Wire size |10 AWG (2.5 to 6 mm²) |
| Terminal pitch |5 mm |

Plug-in digital inputs — 18 DI
| Type |Optically isolated, dry contact sensing (voltage-free) |
| Internal power supply |5 VDC |
| Sensitivity |Open at input resistance > 16 kΩ, closed at < 10 kΩ |
| Scan time |½ cycle |
| Withstand insulation |4 kV AC at 1 min |
| Wire size |12 AWG (up to 2.5 mm²) |
| Terminal pitch |3.81 mm |

Plug-in analogue inputs — 4 AI
| Ranges (on order) |±1 mA (100% overload), 0 to 20 mA, 4 to 20 mA, 0 to 1 mA (100% overload) |
| Accuracy |0.5% FS |
| Scan time |2 cycles |
| Withstand insulation |4 kV AC at 1 min |
| Wire size |28 to 16 AWG (0.1 to 1.5 mm²), 600 V isolation |
| Terminal pitch |3.81 mm |

Relay outputs
| Type |9 relays, SPST Form A |
| Contact rating |5 A at 250 VAC, 5 A at 30 VDC |
| Update time |1 cycle |
| Recommended wire size |18 AWG (1 mm²), 600 V isolation |
| Terminal pitch |3.81 mm |

Current sensors
| CS1S split-core |100 A, 16 mm (0.63 in) inner diameter, 2.5 m cable |
| Rating |Up to 20 x 5 A (100 A) maximum |

Real-time clock and memory
| Clock accuracy |Better than 5 s/month at 25 °C |
| Onboard memory |256 Mbytes standard |

Display modules
| GDM (option) |3.5 inch touch-panel LCD graphic TFT, 320 x 240, serial TTL RS-232 non-isolated |
| GDM operating temp. |−20 °C to +70 °C |
| RGM-180 (option) |5.7 inch touch colour remote display, Ethernet or serial interface, programmable screen saver |

COM1 — RS-485 (standard, MCM)
| Port |Serial EIA RS-485, optically isolated |
| Withstand insulation |4 kV AC at 1 min |
| Baud rate |Up to 115,200 bps |
| Protocols |Modbus RTU/ASCII, DNP 3.0 |
| Connector type |Removable, 3 terminals |
| Wire size |Up to 12 AWG (up to 2.5 mm²) |
| Terminal pitch |5 mm |

COM3 — display port (standard, MCM)
| Port |Serial TTL RS-232, non-isolated, for the GDM |
| Baud rate |Up to 460,800 bps |
| Protocols |Modbus RTU |

USB port (standard, MCM)
| Port |Isolated USB 1.1 |
| Withstand insulation |4 kV AC at 1 min |
| Connector type |A male, standard USB cable, max. length 2 m |
| Protocols |Modbus RTU |

Ethernet port (standard, MCM)
| Port |Transformer-isolated 10/100Base-T |
| Withstand insulation |4 kV AC at 1 min |
| Connector type |RJ45 modular |
| Protocols |Modbus TCP (502), DNP3/TCP (20000), BACnet |
| Simultaneous connections |5 sockets |
| Time synchronisation |SNTP |

Cellular modem (optional module)
| Technology |Cellular modem, technology selected on order |
| Withstand insulation |4 kV AC at 1 min |
| Connector type |SMA |
| Protocols |Modbus TCP (502), DNP 3.0/TCP (20000) |

## Standards compliance

### Accuracy

- Complies with AS/IEC 62053-22, Class 0.5S
- Meets ANSI C12.20-2010, Class 100 and Class 400, accuracy 0.2%

### Electromagnetic compatibility

- Complies with AS/IEC 62052-11, AS/IEC 62053-22, ANSI C12.1 and ANSI C12.20
- IEC 61000-4-2: electrostatic discharge, air and contact
- IEC 61000-4-3: electromagnetic RF fields, 10 V/m at 80 MHz to 1000 MHz
- IEC 61000-4-4: fast transient burst, 4 kV on current and voltage circuits, 2 kV on auxiliary circuits
- IEC 61000-4-5: surge, 6 kV on current and voltage circuits, 1 kV on auxiliary circuits
- IEC 61000-4-6: conducted radio frequency, 10 V at 0.15 MHz to 80 MHz
- IEC 61000-4-8: power frequency magnetic field
- IEC 61000-4-12: damped oscillatory waves, 2.5 kV common mode and 1 kV differential mode
- CISPR 22, Class B

### Surge and transient withstand

- ANSI C12.1 clause 4.7.3.3.1: 100 kHz ring wave surge, 6 kV at 0.5 kA, per IEEE C62.41.2-2002
- ANSI C12.1 clause 4.7.3.3.2: line surge 1.2/50 µs and 8/20 µs, 6 kV at 3 kA, per IEEE C62.41.2-2002
- ANSI C12.1 clause 4.7.3.11: surge withstand capability 2.5 kV, per IEEE C37.90.1

### Insulation

- AS/IEC 62052-11: insulation impulse 12 kV/50Ω at 1.2/50 µs
- AS/IEC 62053-22: AC voltage tests related to ground, 4 kV AC at 1 min for power and signal ports above 40 V
- Alternatively per UL 61010-1 and UL 916 for basic and double insulation, Installation Category III

### Safety

- Meets UL 916

### Atmospheric environment

- Accuracy operational ambient temperature range: −25 °C to +60 °C
- Operational ambient temperature range: −40 °C to +70 °C
- Long-term damp heat withstand per IEC 68-2-3, below 95% non-condensing at +40 °C
- Transport and storage temperature range: −40 °C to +85 °C
- IEC 60529: IP50

### Vibration and shock

- AS/IEC 62052-11, referencing IEC 60068-2-6: vibration 10 Hz to 150 Hz, transition frequency 60 Hz, constant movement amplitude 0.075 mm below 60 Hz, constant acceleration 9.8 m/s² (1 g) above 60 Hz
- AS/IEC 62052-11, referencing IEC 60068-2-27: shock, half sine pulse, peak acceleration 30 gn (300 m/s²)
- Transport vibration and shock: longitudinal 2.0 g, vertical 1.2 g, transversal 1.2 g

## Ordering information

MODEL – POWER SUPPLY – FEEDER COUNT – FREQUENCY – CURRENT SENSOR – MODULE

BFM-II DFR multi-feeder monitor
| 6-Feeder Monitor. Monitors six three-phase feeders on a common bus voltage via clip-on current sensors for 5 A secondary circuits |BFM-II-DFR-ACDC-6F |
| 8-Feeder Monitor. Monitors eight three-phase feeders on a common bus voltage via clip-on current sensors for 5 A secondary circuits |BFM-II-DFR-ACDC-8F |
| 12-Feeder Monitor. Monitors twelve three-phase feeders on a common bus voltage via clip-on current sensors for 5 A secondary circuits |BFM-II-DFR-ACDC-12F |

Frequency
| 50 Hz |50HZ |
| 60 Hz |60HZ |

Current sensors
| 100 A split-core current sensor. Inner diameter 16 mm (0.63 in), cable length 2.5 m |CS1S |

Digital input and output modules — ordered separately
| 18 Digital Input Module, dry contact |DI18-DRC-BFM II |
| 18 Digital Input Module, 24 VDC |DI18-24V-BFM II |
| 18 Digital Input Module, 48 VDC |DI18-48V-BFM II |
| 18 Digital Input Module, 125 VDC |DI18-125V-BFM II |
| 18 Digital Input Module, 250 VDC |DI18-250V-BFM II |
| 9-channel Relay Output Module. Maximum 2 modules per device |RLY9-BFM II |

Analogue input modules — ordered separately
| 4AI Module, ±1 mA. Four optically isolated analogue inputs |AI1-BFM II |
| 4AI Module, 0 to 20 mA. Four optically isolated analogue inputs |AI2-BFM II |
| 4AI Module, 0 to 1 mA. Four optically isolated analogue inputs |AI3-BFM II |
| 4AI Module, 4 to 20 mA. Four optically isolated analogue inputs |AI4-BFM II |

Current input modules — up to 2 per instrument
| CIM 6, six-channel current input module |C6H |
| CIM 18, eighteen-channel current input module |C18H |
| CIM 6 for measuring with 5 A secondary |C6-RS5 |
| CIM 18 for measuring with 5 A secondary |C18-RS5 |

Communication modules
| None |0 |
| 4G modem plus a second RS-422/485 communications port |T4G-BFM-II |

## Downloads and related

- [Download the datasheet (PDF, TBV1.1, 1322 KB)](https://satec-global.com.au/documentation/BFM-II-DFR-Datasheet-TBV1-1.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-0a7bb899ef32/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/bfm/)
- [All datasheets as web pages](https://satec-global.com.au/support/datasheets/)
- [Which BFM-DFR records should I collect after a disturbance?](https://satec-global.com.au/support/articles/bfm-dfr-disturbance-records/)
- [How do I tell a BFM-II DFR, a standard BFM-II and a BFM136 apart?](https://satec-global.com.au/support/articles/bfm-dfr-bfm-ii-bfm136-identification/)

Questions about this datasheet? Use the [contact form](https://satec-global.com.au/contact/).