# What information and records should I preserve before a PM180 service or change?

> What to record and copy from a PM180 before servicing, a firmware upgrade, a module change, a memory change or a replacement: its identity, diagnostics, a PAS copy of every setting and an upload of its logs, and which actions change or remove that information.

Source page: https://satec-global.com.au/support/articles/pm180-preserve-before-service-or-change/

---

PM180 · BEFORE A CHANGE

# What information and records should I preserve before a PM180 service or change?

*[PM180 product illustration]*PM180 product illustration; confirm the installed unit and fitted options.

## Quick answer

SATEC Australia's advice: before any authorised service or change, record the PM180's identity and diagnostics, then use PAS to copy its settings and its recorded logs to the PC. In PAS, Upload Setups uploads the setup from the device to the site database, and Upload Logs retrieves log files from the device. Download Setups downloads all setups from the site database to the device. The Reset dialog clears accumulators, counters and log files, and a firmware upgrade reboots the meter. SATEC Australia's advice: make and check the copies before any of these.

## Applies to

This page covers the PM180 and its Operation Manual, BG0525 Rev. A7, and Installation Manual, BG0521 Rev. A10. SATEC Australia's advice: don't use it for the portable EDL180 enclosure or its sensors.

## 1. Record the unit's identity

SATEC Australia's advice: note the serial number and order code from the labels, the firmware version, the display type, and the modules in each of the three optional slots. The Operation Manual uses firmware references to show the device's power quality and IEC 61850 options. The Installation Manual gives a minimum firmware version for several plug-in modules, and says the PMU module only can function with PM180 N3 with the new CPU board (AP1451).

## 2. Record the diagnostics before anything clears them

All diagnostic events are recorded in the device Event log. The diagnostics status is also stored in a non-volatile register, which is not affected by loss of power and may be read and cleared via PAS, from the RDM, or from a user application.

- The RDM Status Information Display allows you to view device diagnostics, the status of digital inputs and relays, counters and the phase rotation order.
- In PAS, check the On-line button, select Device Control from the Monitor menu, and click the Device Diagnostics tab. To clear the device diagnostics events, the manual says to click Clear.

SATEC Australia's advice: photograph or write down the diagnostics before anyone clicks Clear.

The manual divides device failures into three categories:

- Non-critical intermittent faults with auto-reset, like IRIG-B time code signal faults.
- Non-critical recoverable hardware or configuration faults with manual reset. These faults normally cause the device to restart followed by repairing of the configuration data, and must be cleared manually.
- A critical unrecoverable hardware or configuration failure, which causes the device to release all its outputs and to stop normal operation until the faults that caused the critical error are cleared.

In the event of a configuration reset, the manual says to determine the device setup affected by the fault via the event log, and then verify it. Appendix F lists the diagnostic codes, including 8 (Power down/Up), 9 (Warm restart/Device reset), 10 (Configuration reset), 11 (RTC fault, critical error) and 12 (Configuration fault, critical error).

## 3. Copy every setting to the PAS site database

To upload the setup from the device to the site database, the manual says to check the On-line button on the PAS toolbar, select the device site from the list box, and then select Upload Setups from the Meter Setup menu.

The manual describes the other PAS setup actions this way:

| PAS action |What the manual says it does |
| "Save as…" |Stores the data to the site database |
| Upload Setups |Uploads the setup from the device to the site database |
| Send |Downloads the setup on the open tab to the device |
| Download Setups |Downloads all setups to the device at once |

*From BG0525, printed pages 54–55.*

SATEC Australia's advice: keep the uploaded site database unchanged as the as-found record, and make any planned edits in a separate copy. The PAS lesson [Upload the setups, then duplicate the backup](https://satec-global.com.au/support/pas-university/courses/site-config-workflow/lessons/backup-and-duplicate/) shows the general approach using an EM133-XM example.

## 4. Upload the recorded logs

To retrieve the log files from your device, the manual gives these steps:

- Select a device site from the list box on the PAS toolbar.
- Check the On-line button.
- Select Upload Logs from the Logs menu.
- Select a database, or type the name for a new database, and select a directory where you want to save it.
- Click on the "Select Logs" button and check boxes for logs you want to be retrieved from the device.
- If you wish to retrieve data starting with a known date, check the "From" box and select the start date for retrieving data.
- If you wish to retrieve data recorded before a known date, check the "To" box and select the last date for retrieving data.
- Click OK.

The PM180 memory can be partitioned for a total of 28 log files: the Event log, 16 Data logs, 8 Waveform logs, the SOE log, an IEEE 1159 or EN 50160 or GOST 32144 PQ log, and the Fault log. SATEC Australia's advice: before a service, upload every log in use, not only the one under investigation.

## How far back the logs go

The manual says memory is allocated for each file statically and does not change unless you re-organize the files. Each file is either Wrap around, where recording continues over the oldest records, or Non-wrap, where recording is stopped until the file is cleared; data logs #15 and #16 can be TOU profile logs. The Memory/Log setup, on the Log Memory tab, shows each file's allocation. SATEC Australia's advice: work out how far back a log reaches from its allocated records, its type and how often it actually records.

## Actions that change or remove information

The manual describes these actions:

- **Reset.** PAS allows you to clear energy accumulators, maximum demands, Min/Max log registers, counters and log files.
- **Clearing diagnostics.** Clear on the Device Diagnostics tab clears the device diagnostics events.
- **Firmware upgrade.** The meter completes burning firmware into the flash and reboots. The Internet connection may be temporarily lost. If you are connected through a wireless cellular network using a temporary IP address, the IP address you used will no longer be in effect.
- **Changing the memory allocation.** The PM180 automatically performs de-fragmentation of the memory each time the file allocation changes.
- **Send or Download Setups.** These download setups to the device.

The Operation Manual doesn't say what happens to existing records when the file allocation changes. SATEC Australia's advice: treat every action above as a separate authorised change made only after the copies are kept, and treat a memory reallocation as a change that may lose records. For battery work, see [How do I replace the backup battery in a PM180?](https://satec-global.com.au/support/articles/pm180-battery-replacement/).

## After the work

The Installation Manual says the first power-on after battery installation may take about 7 minutes, while regular initialisation takes 40 seconds. SATEC Australia's advice: once the unit is running, compare its settings with the as-found copy, check the clock, and confirm that new records are being written. This page doesn't give a procedure for restoring settings to a replacement unit. SATEC Australia's advice: contact SATEC Australia before writing an old configuration to different hardware or firmware.

## What to send SATEC Australia

SATEC Australia's advice: send:

- the serial number, order code, firmware version and the modules in each slot;
- the diagnostic codes, with photos of the RDM or PAS screen;
- the uploaded site database (the as-found copy);
- the log database;
- what is planned, and why.

Contact SATEC Australia technical support through our [contact form](https://satec-global.com.au/contact/).

## Manuals and source pages

- **PM180 Operation Manual**, BG0525 Rev. A7, April 2019. Firmware references, printed page 11 / PDF page 12; device diagnostics, printed page 31 / PDF page 32; RDM status display, printed page 36 / PDF page 37; PAS setups, printed pages 54–55 / PDF pages 55–56; memory, printed pages 84–85 / PDF pages 85–86; diagnostics, reset and firmware, printed pages 133–135 / PDF pages 134–136; log upload, printed page 141 / PDF page 142; diagnostic codes, printed page 194 / PDF page 195. [Open the manual in a new tab](https://satec-global.com.au/documentation/PM180-Expertmeter-Operation-Manual.pdf#page=56).
- **PM180 Installation Manual**, BG0521 Rev. A10, June 2025. Initialisation time, printed page 6 / PDF page 10; module firmware conditions, printed pages 13–20 / PDF pages 17–24. [Open the manual in a new tab](https://satec-global.com.au/documentation/PM180-Installation-Manual.pdf#page=10).

## Related help

- [How do I replace the backup battery in a PM180?](https://satec-global.com.au/support/articles/pm180-battery-replacement/)
- [Knowledge Base home](https://satec-global.com.au/support/#top)
- [PAS](https://satec-global.com.au/support/pas-university/)

Source review: 22 November 2026.
