# Which PM130 PLUS model and current input do I have?

> How to tell a PM130P, PM130E and PM130EH PLUS apart, which current input options exist, and where to find the information on an installed meter and in its ordering code.

Source page: https://satec-global.com.au/support/articles/pm130-plus-model-and-current-input/

---

PM130 PLUS · IDENTIFY

# Which PM130 PLUS model and current input do I have?

*[PM130 PLUS with the TOU add-on module, from its manufacturer manual]*PM130 PLUS and TOU add-on module, manufacturer manual page 42. Identification illustration only.

## Quick answer

The PM130 PLUS comes as three models: the PM130P, PM130E and PM130EH. Each can be ordered with different current inputs: 5 A or 1 A conventional CT inputs, or inputs for SATEC's HACS sensors. The manual doesn't say that the full ordering code is printed on the meter. **SATEC Australia's advice:** take the model and current input from the ordering code on your purchase order, quote or invoice, and read the serial number and firmware version from the meter's status display.

## The three models

| Model |What it offers |
| PM130P |The basic model: voltage, current, power and frequency measurements, and control capabilities. A special amp-demand version with a simplified display can be ordered |
| PM130E |Everything in the PM130P, plus energy measurements and data logging |
| PM130EH |Everything in the PM130E, plus harmonic analysis |

The billing and time-of-use energy registers and the event and data recorders are PM130E and PM130EH features. Harmonic analysis is a PM130EH feature. A PM130P doesn't have them, and a PM130E doesn't have harmonic analysis.

Options such as a second communication port, digital inputs and outputs, analogue outputs or the TOU clock module are separate expansion modules. A meter takes one module at most. Which of these a given unit has depends on what was ordered and fitted, not on the model name.

## Current input options

| Current input |What the manual says |
| 5 A secondary |Standard. For conventional 5 A CTs |
| 1 A secondary |Option. For conventional 1 A CTs |
| HACS |40 mA input for SATEC's external solid-core or split-core High Accuracy Current Sensors |
| RS5 |5 mA input for an external split-core sensor |

The factory's current datasheet also lists a DC current input, code DCC, for a shunt resistor output of up to 100 mV. The SATEC Australia datasheet doesn't list it.

The manual gives the HACS primary operating range as 100–1200 A. Both datasheets say 100–3000 A. **SATEC Australia's advice:** check the range for your sensors with SATEC Australia.

## How to check an installed meter

Read the serial number and firmware version from the front display. From the data display, press SELECT to reach the main menu, where the StA window is highlighted, and press ENTER. Scroll with the UP and DOWN buttons to the SEr.n page (serial number) and the SoFt page (firmware version).

**SATEC Australia's advice:** you can also check the rear labels and the CT connections, but only a qualified person should do this, following the site's isolation rules, with the meter de-energised if the check needs access to the terminals or the rear of the meter. Photograph the rear labels only if they can be seen without opening an energised panel. Before connecting the meter to the power source, the manual says to check the labels at the back of the instrument to ensure it is equipped with the appropriate power supply voltages, input voltages and currents. With the internal CT inputs, the meter has no current terminals, and each CT wire passes through the meter's CT core; a HACS meter has current terminals.

The manual says only qualified personnel familiar with the instrument and its associated electrical equipment must perform setup procedures, and that all incoming AC power and other power sources must be turned off before any work on the instrument.

## Reading the ordering code

Both datasheets build the ordering code from the model followed by option codes:

| Part |Codes |
| Model |PM130P-PLUS, PM130E-PLUS, PM130EH-PLUS |
| Current input |5, 1, HACS, RS5 (and DCC in the factory datasheet) |
| Calibration frequency |25HZ, 50HZ, 60HZ, 400HZ |
| Power supply |ACDC (85–265 V AC, 85–290 V DC), 1DC (9.5–18 V DC), 23DC (18.5–58 V DC) |
| Communication protocol |blank for Modbus and DNP 3.0; 870 for Modbus and IEC 60870-5-101/104 |
| Mounting |blank for panel mounting; DIN for DIN rail |

The factory datasheet also has a display resolution code, H for high resolution, which the SATEC Australia datasheet doesn't list. The SATEC Australia datasheet ends the code with a MODULE field. The factory datasheet's order string has no module field, and lists the expansion modules on a separate page.

The factory datasheet says the HACS and RS5 inputs are for 50/60 Hz only, and that 25 Hz and 400 Hz calibration is for the 1 A and 5 A models only.

## What to send if you need help

Contact SATEC Australia technical support through our [contact form](https://satec-global.com.au/contact/). **SATEC Australia's advice:** include the ordering code from your purchase records, the serial number and firmware version from the status display, the current input or sensor type, and any expansion module fitted.

## Manuals and source pages

- PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH Installation and Operation Manual, BG0425 Rev. A22:
- Safety warning, page 3. Models, page 12. Features, page 13. Available options, page 15.
- Current input connection, page 27.
- Status display, pages 62–63.
- Input ratings, page 148.
- Printed and PDF page numbers are the same in this manual.

- PM130 PLUS datasheet (SATEC Australia edition, TBV1.0, 2 September 2026), ordering information, page 7.
- PM130 PLUS datasheet (SATEC Ltd, July 2024), order string, page 8.
- All are available from the [SATEC Australia manuals and datasheets page](https://satec-global.com.au/manuals-datasheets/) or the [SATEC Ltd PM130 PLUS page](https://www.satec-global.com/products/pm130-plus/). Evidence checked 22 November 2026.

## Related answers

- [Which PM130 PLUS wiring diagram applies to my installation?](https://satec-global.com.au/support/articles/pm130-plus-which-wiring-diagram/)
- [Can I replace the clock battery in a PM130 PLUS TOU module?](https://satec-global.com.au/support/articles/pm130-plus-tou-module-clock-battery/)

Source review: 22 November 2026.
