# Which PAS actions read from, save locally or write to my meter?

> In PAS, Upload Setups reads the meter's setup into the PC site file, Save as stores a setup in the PC site file, and Send and Download Setups write to the meter. Open copies another site's setup into the current site. SATEC Australia's advice is to back up the meter's setup before any write, and to check the write result separately from the local save prompt.

Source page: https://satec-global.com.au/support/articles/pas-read-save-write/

---

PAS · READ AND WRITE

# Which PAS actions read from, save locally or write to my meter?

*[PAS upload-complete screen from the recorded backup lesson]*Example PAS screen from the recorded backup lesson. Follow the article for the scope of each action.

## Quick answer

PAS keeps a meter's settings in two places: in the meter itself, and in a site database file on your PC. **Upload Setups** reads the meter's setups into the selected site file. **Save as** stores the setup you are editing in the site file. **Send** and **Download Setups** write to the meter. SATEC Australia's advice is to keep a backup of the meter's setup as it was found before any write.

## What each action does

| PAS action |Where it is |What it does |
| Upload Setups |Meter Setup menu, with On-line checked |Updates the selected site database on the PC with the setups now in the meter, after a PAS warning. |
| Save as |Button in a setup dialog |Stores the dialog's data in the site database on the PC. |
| Open |Button in a setup dialog |Copies that setup from another site database into your current site database. |
| Copy to |Meter Setup menu |Copies all setups from the selected site into another site database. |
| Send |Button in a setup dialog, with On-line checked |Writes that one setup to the meter. |
| Download Setups |Meter Setup menu, with On-line checked |Writes all setups from the site database to the meter, after a PAS warning. |
| Upload Logs |Logs menu, with On-line checked |Reads recorded logs from the meter into a log database you choose. |
| Reset |Monitor menu, with On-line checked |Clears energy accumulators, maximum demands, Min/Max log registers, counters or log files in the meter. |
| Clear |Monitor > Device Control > Device Diagnostics tab, with On-line checked |Clears the meter's device diagnostics. |

The manual describes each action that reads from or writes to the meter with the **On-line** button on the PAS toolbar checked. Setups can be prepared offline, without the meter connected, and stored with Save as.

## Points that catch people out

- **Upload Setups and the site file.** Upload Setups updates the selected site database with the setups currently in the meter. In SATEC Australia's practice run on an EM133-XM with PAS V1.5.8.9, PAS warned that the current contents of the site database would be overwritten. SATEC Australia's advice is to upload into a new backup site, not into a file holding settings you still need.
- **Saving locally and writing to the meter.** Save as stores a setup in the site database on the PC, while Send and Download Setups are the actions that write to the meter. SATEC Australia's advice is to back up the meter's setup before using Send or Download Setups.
- **Open copies.** Open copies another site's setup into the current site. SATEC Australia's advice is that, to look at another file's settings, you make that file the current site instead.
- **Basic Setup comes first.** PAS uses the Basic Setup data as a reference in all setup dialogs.
- **Checking a write.** In SATEC Australia's practice run on an EM133-XM with PAS V1.5.8.9, PAS asked whether to save changes after a write that the meter had rejected. SATEC Australia's advice is to check the write result itself, then read the setting back from the meter.

## SATEC Australia's advice before a change

SATEC Australia's advice is to work in this order:

- Confirm that the site database is set up for the right meter model and address.
- With On-line checked, use Upload Setups into a new, clearly named backup site file, and keep that file unchanged.
- Make a separate working copy of the backup, and make changes only in the copy.
- Send only the setup you are authorised to change, and check that the meter accepted it.
- Read the setting back from the meter, then save the accepted setup locally.
- Record the meter identity, the date, the file names and what was changed.

SATEC Australia's PAS lessons say that "PAS file-management steps apply across models; available programming menus differ". Their worked examples use an EM235 for creating a site, and an EM133-XM with PAS V1.5.8.9 for the backup, duplicate and CT-change lessons. In the CT lesson's practice run the write was rejected, so that lesson doesn't yet show an accepted change and read-back:

- [Create a blank site and check the connected meter](https://satec-global.com.au/support/pas-university/courses/site-config-workflow/lessons/create-and-identify/)
- [Upload the setups, then duplicate the backup](https://satec-global.com.au/support/pas-university/courses/site-config-workflow/lessons/backup-and-duplicate/)
- [Change a CT primary online and compare the offline file](https://satec-global.com.au/support/pas-university/courses/site-config-workflow/lessons/online-offline-ct/)

The manual refers you to each meter's own manual for detail on that meter, including its menus. PAS asks for the meter's password with the first command to a password-protected meter.

## Getting help

Contact SATEC Australia technical support through our [contact form](https://satec-global.com.au/contact/). SATEC Australia's advice is to have these details ready:

- the meter model and order code;
- your PAS version; in SATEC Australia's recorded installation, PAS showed it in the title bar;
- the action you used;
- the exact message PAS showed.

## Manuals and source pages

- PAS Getting Started, BG0337 Rev. A2:
- Section 1.1.2 File Format and section 1.1.5 General Note, printed page 5 (PDF 5).
- Section 2.1 Creating a New Site, printed pages 6–7 (PDF 6–7).
- Chapter 3 Setting Up the Device, printed page 10 (PDF 10).
- Section 4.1 Authorization, printed page 11 (PDF 11).
- Sections 4.4 and 4.6, printed pages 12–14 (PDF 12–14).
- Section 6.1 Uploading Files on Demand, printed pages 21–22 (PDF 21–22).
- Available from the [SATEC Australia manuals and datasheets page](https://satec-global.com.au/manuals-datasheets/). Evidence checked 22 November 2026.

Source review: 22 November 2026.

[Contact SATEC technical support](https://satec-global.com.au/contact/)
