# How do I set the CT ratio on an EM133-XM?

> Set EM133-XM CT primary current from the two-button front panel: check the input, open Basic, edit the digits, save, read back and exit.

Source page: https://satec-global.com.au/support/articles/em133-xm-ct-ratio/

---

EM133-XM · FRONT-PANEL KEYPAD GUIDE

# How do I set the CT ratio on an EM133-XM?

Open **Basic → CT**, enter the CT primary current in amps, save, check the value and return to the normal display.

This example uses a **250:5 A** CT and the meter's **5 A input**. Enter **250 A**; the calculated ratio is **50:1**. Use the primary current from your own CT nameplate.

## Watch the keypad demonstration

| Your browser does not support embedded video. [Open the video file](https://satec-global.com.au/support/media/em133-xm-ct-ratio/20261123-v3b/satec-em133-xm-ct-ratio-settings-keypad-guide.mp4).

3 minutes 37 seconds · English captions · Synthetic narration · Rendered keypad demonstration. Model and firmware menus can differ.

[Watch on YouTube](https://www.youtube.com/watch?v=7Dt30wRHIFQ) · [Download English captions](https://satec-global.com.au/support/media/em133-xm-ct-ratio/20261123-v3b/em133-xm-ct-ratio.en.srt) · [Read the text transcript](https://satec-global.com.au/support/media/em133-xm-ct-ratio/20261123-v3b/transcript.txt)

Jump to a chapter
- 
- 
- 
- 
- 
- 
- 
- 
- 
- 
- 
- 

## Check the input rating first

The demonstrated standard input is **5 A nominal / 10 A continuous**. Other input versions need the matching CT or sensor. For **HACS**, use only SATEC-supplied High-Accuracy Current Sensors; consult SATEC if unsure. The programmable CT-primary range in the selected manual is **1–50,000 A**.

## Know the two buttons and the LCD labels

- **Triangle: SCROLL.** A short press moves through menu items or increases the active digit.
- **Bent arrow: SELECT / ENTER.** A short SELECT press moves the active digit. A held ENTER confirms the action.
- **White translucent block:** shows the physical key being pressed. A continuous block with a countdown means hold; **Release** means let go.

Initial programming entry needs a longer hold, over five seconds. The film teaches ordinary ENTER actions as around three seconds and release. The manual describes ordinary ENTER as one to two seconds.

This meter has a two-line LCD. **Basic** means basic settings; **Conf** means wiring configuration; **PT Ratio** and **PT Factor** are voltage-transformer settings; **CT** is the primary-current field. PAS refers to these settings under **Meter Setup → General Setup**.

## Set CT primary to 250 A

- 

### Open programming

From the normal display, hold **SELECT / ENTER for more than five seconds**, then release. The film shows a six-second hold.

- 

### Enter the password

The default is **9, if unchanged**. In this example, give SCROLL nine short presses from zero. Hold ENTER for around three seconds, then release. Use your configured password if it has been changed.

- 

### Find Basic → CT

Use short SCROLL presses through Reset and RTC to **Basic**. Hold ENTER for around three seconds and release. Scroll past **Conf** (wiring configuration), **PT Ratio** and **PT Factor** to **CT**. The number below is the present primary current.

- 

### Edit the primary amps

Give SELECT a short press. The example starts at **00005**. SELECT moves the active digit; SCROLL increases it. Set the hundreds to 2 and tens to 5, then wrap the units from 5 through 9 to 0. Check **00250**.

These digit counts follow the film's starting value. Follow the actual active digit and value on your meter.

- 

### Save and check

Hold ENTER for around three seconds and release. Check that **CT reads 250**. Enter primary amps, **250**, rather than the calculated **50:1** ratio for this 250:5 A example.

- 

### Return to the normal display

Hold ENTER for around three seconds and release to return to the main menu. Give SELECT a short press to choose **Exit**. Hold ENTER again and release to return to the normal display.

## Manual and source references

- [EM132/EM133 User Manual — selected A15 reference (PDF, new tab)](https://satec-global.com.au/support/media/em133-xm-ct-ratio/20261122-v2/EM132-EM133-User-Manual-A15-reference.pdf#page=81): programming, printed pages 78–80 / PDF pages 81–83; Basic Setup and CT, printed page 95 / PDF page 98; current inputs, printed page 159 / PDF page 162.
- [Current online EM132/EM133 User Manual (PDF, new tab)](https://satec-global.com.au/documentation/EM132-133-installation-operation-manual.pdf#page=81). Match the manual to your meter and firmware.
- [Explore EM133-XM setup options in PAS](https://satec-global.com.au/support/pas-university/meter-menus/em133-xm/).

Guide reviewed 22 November 2026. Target recording firmware was not stated. This is an illustrated front-panel lesson, rather than verification of a particular installation's CT selection.

## Video transcript

Read the complete narrationWelcome to this demonstration on how to change the CT ratio, or primary current setting, on a SATEC EM133-XM meter. In this example, we've chosen a two hundred and fifty amp CT with a five amp secondary. We'll enter, save and check two hundred and fifty amps.

First, check your meter's current input rating. This example uses the five amp version. Other versions need a matching CT or sensor. For HACS, only use SATEC supplied High Accuracy Current Sensors. Please consult SATEC if you're unsure.

Let's get familiar with the two buttons. The triangle is SCROLL. The bent arrow is SELECT and ENTER. A short press means press and release straight away. For an ordinary ENTER action, hold for around three seconds, then release.

To open programming from the normal display, we need a longer hold. Hold SELECT and ENTER for more than five seconds, then release. The password screen will appear.

The default password is nine, if it hasn't been changed. Give SCROLL nine quick presses to set the last digit to nine. Now hold ENTER for around three seconds, then release. If you don't have the configured password, ask your administrator or contact SATEC.

Next, use SCROLL to move from Reset, through RTC, to Basic. Hold ENTER for around three seconds, then release to open the Basic menu.

Continue with short SCROLL presses through the wiring configuration, PT ratio and PT factor, until CT appears. The number below is the present CT primary current.

Now give SELECT a quick press to edit the number. The digits appear with leading zeros. Short SELECT presses move to the next digit, while SCROLL increases that digit. We'll change the example's existing five amps to two hundred and fifty.

Move to the hundreds digit and set it to two. Move to the tens digit and set it to five. Then move to the units digit and continue from five, through nine, to zero. Check that the display reads zero, zero, two, five, zero.

When it matches, hold ENTER for around three seconds, then release to save. Check that CT now shows two hundred and fifty. Our two hundred and fifty to five amp CT has a fifty to one ratio, but we enter the primary current, two hundred and fifty amps.

Finally, hold ENTER for around three seconds and release to return to the main menu. Give SELECT a short press to choose Exit. Hold ENTER again for around three seconds, then release to return to the normal display.

Great work! You've changed the CT primary current and checked the saved setting. Scan the code for the EM132/EM133 User Manual. Get in touch with us any time, we're here to help.

## Continue learning

- [Identify an Australian EM133-XM](https://satec-global.com.au/support/articles/em133-xm-identify/)
- [EM133-XM menus in PAS](https://satec-global.com.au/support/pas-university/meter-menus/em133-xm/)

[Contact SATEC technical support](https://satec-global.com.au/contact/)

Get in touch with us any time, we're here to help.

[Back to Knowledge Base home](https://satec-global.com.au/support/#top)