## Quick answer

Read the label on the meter and the Device Info display on its front panel. Between them they give the model, the rated current input, the supply or voltage rating, the serial number and the firmware version. The manual and the current datasheet don't use the same names for every variant. If the label leaves any doubt, SATEC Australia's advice is to send a photo of it to SATEC Australia technical support.

## Applies to

This page covers the plain EM133: the EM133 with an AC/DC auxiliary supply, the EM133-21DC with a DC auxiliary supply, and the self-energised EM133-SE. It does not cover the EM133-XM, which the EM133 datasheet lists as the extended-memory version, or the EM133-XM-AR and EM133-MID, which its order string lists as separate models. It also does not cover the EM132.

## Which manual to use

The plain EM133 is covered by the EM13X Series Smart Multifunction Meter Installation and Operation Manual, BG0491. The copy linked from the [SATEC Australia manuals and datasheets page](https://satec-global.com.au/manuals-datasheets/) is the same file as the copy on the manufacturer's EM133 page: Rev. A15 on the cover, with Rev. A16 in the footer of its contents page.

## The three plain EM133 models

The manual lists the plain EM133 in three supply versions:

| Model |Power supply, as the manual states it |
| EM133 |AC/DC auxiliary supply, 40–318 V AC/DC |
| EM133-21DC |DC auxiliary supply, 9.5–36 V DC |
| EM133-SE |Self-energised, from any combination of the measured phases |

The May 2025 EM133 datasheet's order string states these differently: 40–300 V AC/DC for the AC/DC supply, 120–277 V L-N for SE, and 12 V/24 V DC for 21DC. One of the manual's own label examples prints "PS: 40-300V". We have not confirmed which wording matches a meter's label.

## Current input variants

The manual names these current input variants for each supply version:

| Suffix in the manual |Connection |Rated input |
| -5 |Internal CT, transformer operated |In 5 A, Imax 10 A |
| -1 |Internal CT, transformer operated |In 1 A, Imax 2 A |
| -RS5 |External CT, transformer operated |Secondary current from the external CT |
| -50 |Internal CT, direct connection |In 50 A, Imax 63 A; the manual's footnote gives Imax 63 A at 60 °C maximum ambient and 100 A at 55 °C |
| -HACS |External CT, direct connection |In 20 mA, Imax 40 mA secondary |

The datasheet's order string lists current input codes 5, 1, 63, 100, RS5, HACS and HACS-SPDR instead. The manual's "-50" and the datasheet's "63" and "100" codes are not cross-referenced in either document. SATEC Australia's advice is not to assume one equals the other, and to check with support.

## The terminal drawings

The manual's terminal drawings label terminals 9 and 10 as power supply terminal screws on both the EM133 and the EM133-SE. The EM133 schematic shows a 40–318 V AC/DC supply on them, and the EM133-SE schematics show the meter wired from the measured phases. Because both drawings label these terminals the same way, SATEC Australia's advice is to tell the models apart by the label and order code, not the terminals.

[*[Manufacturer terminal views for the EM133 and EM133-SE from manual BG0491, printed page 32]*](https://satec-global.com.au/support/media/em133-identify-model-variant/20261122-v5/bg0491-a15-p32-terminal-views.png)Figures 2-7a and 2-7b, EM13X Series manual BG0491 Rev. A15, printed page 32. Manufacturer drawing, unmodified. [Open figure in a new tab](https://satec-global.com.au/support/media/em133-identify-model-variant/20261122-v5/bg0491-a15-p32-terminal-views.png).

## Read the label and the Device Info display

The manual's label examples show the model designation, the rated current input, the voltage rating and a serial number. Some labels also carry approval or certification markings. This page doesn't interpret those markings.

The front-panel Device Info display shows the serial number (S/N), the device software version (S/W), the boot software version, the modem setting and the settings of communication ports COM1, COM2 and COM3. SATEC Australia's advice is to write these down or photograph them.

## If you're still not sure

SATEC Australia's advice is to send a clear photo of the label and the Device Info values to technical support before ordering a replacement, choosing a wiring drawing or changing settings. Contact SATEC Australia technical support through our [contact form](https://satec-global.com.au/contact/).

## Related answers

- [Can I replace the clock backup battery in an EM133?](https://satec-global.com.au/support/articles/em133-clock-backup-battery/)
- [What should I record before asking for help with an EM133?](https://satec-global.com.au/support/articles/em133-what-to-record-for-support/)

Source review: 22 November 2026.

[Contact SATEC technical support](https://satec-global.com.au/contact/)

[Back to Knowledge Base home](https://satec-global.com.au/support/#top)